- 2 -  

T1MK Kits

Overview:

Altronix Trove Mercury kits are pre-assembled and consist of Trove1M1 enclosure/backplane with factory installed Altronix power 
supply/charger and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to four (4) doors in a 
single enclosure.

Configuration Chart:

Altronix

Model

Number

120VAC 60Hz Input Current (A)

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

Nominal DC

Output Voltage

Maximum 

Supply Current

for Main and 

Aux. Outputs

on Power 

Supply board

and ACM4/

ACM4CB

Access Power 

Controller’s

outputs (A)

Fail-Safe/Fail-Secure or Dry Form “C” Outputs

Fail-Safe/Fail-Secure Outputs (auto-resettable)

Current Per ACM4 Output 

(A)

Current Per ACM4CB Output 

(A)

ACM4/ACM4CB Board Input Fuse Rating

ACM4 Board Output Fuse Rating

ACM4CB Board Output PTC Rating

PDS8/PDS8CB Board Input Fuse Rating

PDS8 Board Output Fuse Rating

PDS8CB Board Output PTC Rating

[DC]

[Aux]

24VDC Output Range (V)

24VDC Output Range (V)

T1MK1F4

3.5

5A/

250V

7.5A/

32V

20.28-

26.4

20.28-

26.4

24VDC @ 3.6A

4

2.5

10A/

250V

3A/

250V

T1MK1F4D

3.5

5A/

250V

7.5A/

32V

20.28-

26.4

20.28-

26.4

24VDC @ 3.6A

4

2.0

10A/

250V

2.0A

T1MK1F4S

3.5

5A/

250V

7.5A/

32V

20.28-

26.4

20.28-

26.4

24VDC @ 3.6A

4

2.5

10A/

250V

3A/

250V

10A/

250V

3A/

250V

T1MK1F4SD

3.5

5A/

250V

7.5A/

32V

20.28-

26.4

20.28-

26.4

24VDC @ 3.6A

4

2.0

10A/

250V

2.0A

10A/

250V

2.0A

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI and with all local codes and authorities having 
jurisdiction. Product is intended for indoor use only. 
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top two (2) keyholes in the enclosure. Install two upper fasteners and screws 
  in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure.
  Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the
  enclosure’s upper keyholes over the three upper screws. Install the two lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model T112 or equivalent) in desired location, opposite hinge. 
  Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 1, pg. 2)
  Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. 
  To activate alarm signal open the door of the enclosure.
4. Position Mercury access controller modules over corresponding standoffs and depress onto 
  snap on standoffs, Fig. 2, pg. 3.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow4NB, 
  and corresponding Sub-Assembly Installation Guide for ACM4(CB), PDS8(CB)
  and VR6 for further installation instructions.
6. Mount backplane to enclosure with hardware.

Fig. 1

Tamper Switch

(provided)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure