- 2 -  

Trove3 Mercury Kits Installation Guide

Overview:

Altronix Trove Mercury kits are pre-assembled and consist of Trove3M3 enclosure/backplane with factory installed Altronix power supply/

charger(s) and sub-assemblies. These kits also accommodate various combinations of Mercury boards for up to sixteen (16) doors in a 

single enclosure.

Configuration Chart:

Altronix

Model Number

120VAC 60Hz Input Current (A)

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

Nominal DC Output Voltage

Maximum 

Supply

Current for 

Main and Aux. 

Outputs on Power 

Supply board and 

ACM8(CB) Access 

Power Controller’s 

outputs

Fail-Safe/Fail-Secure or  Dry Form “C” Outputs

Current Per  ACM8(CB) Output 

(A)

ACM8(CB) Board  Input Fuse Rating

ACM8 Board Output Fuse Rating

ACM8CB Board Output PTC Rating

PD8UL Board Output Fuse Rating

PD8ULCB Board Output Fuse Rating

Power Supply 1 Power Supply 2

[DC]

[Aux]

[DC]

[Aux]

Output Range  (VDC)

Output Range  (VDC)

Output Range  (VDC)

Output Range  (VDC)

T3MK75F16

8

6.3A/250V

5A/250V

15A/

32V

20.17-

26.4

20.28-

26.4

9.7-

13.2

10.03-

13.2

12VDC @ 9.3A

24VDC @ 9.2A

16

2.5

10A/

250V

2.5A/

250V

3.5A/

250V

T3MK75F16D

8

6.3A/250V

5A/250V

15A/

32V

20.17-

26.4

20.28-

26.4

9.7-

13.2

10.03-

13.2

12VDC @ 9.3A

24VDC @ 9.2A

16

2.5

10A/

250V

2A

2.5A

T3MK77F16

9

6.3A/

250V

15A/

32V

20.17-

26.4

20.28-

26.4

20.17-

26.4

20.28-

26.4

24VDC @ 9.2A

16

2.5

10A/

250V

2.5A/

250V

3.5A/

250V

T3MK77F16D

9

6.3A/

250V

15A/

32V

20.17-

26.4

20.28-

26.4

20.17-

26.4

20.28-

26.4

24VDC @ 9.2A

16

2.5

10A/

250V

2A

2.5A

Hardware and Accessories:

•  Two (2) tamper switches (Altronix Model TS112 or equivalent).

•  Cam lock.

•  Battery leads.

Mechanical:

•  16 Gauge enclosure with ample knockouts for convenient access.

•   Enclosure Dimensions (H x W x D): 36.12” x 30.125” x 7.06” (917.5mm x 768.1mm x 179.3mm).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Remove backplane from enclosure. Do not discard hardware.

2.  Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws 

  in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure.

  Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install 

  the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. 

  Install the three lower screws and make sure to tighten all screws.

3.  Mount included UL Listed tamper switches (Altronix Model TS112 or equivalent) in desired location, 

  opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” 

  from the right side 

(Fig. 1, pg. 2)

. Connect tamper switch wiring to the Access Control Panel input 

  or the appropriate UL Listed reporting device. 

  To activate alarm signal open the door of the enclosure.

4.  Mount Mercury boards to backplane, refer to

 pg. 3, 4.

5.  Refer to the 

eFlow Power Supply/Charger Installation Guide

 for eFlow104NB, eFlow102NB 

  and corresponding 

Sub-Assembly Installation Guides

 for PD8UL(CB) and ACM8(CB) for 

  further installation instructions.

6.  Position Mercury access controller module over corresponding spacers and depress onto 

  snap on spacers 

(Fig. 2-3, pg. 3-4)

.

7.  Mount backplane to enclosure with hardware.

Hardware:

Fig. 1

Tamper Switch

(provided)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Snap On Spacer

 |            5/16” Pan Head Screw |         Lock Nut

Summary of Contents for TROVE T3MK75F16

Page 1: ...er Supply Charger Two 2 ACM8CB PTC Protected Access Power Controllers One 1 PD8ULCB PTC Protected Power Distribution Module One 1 Rocker Switch Bracket with Two 2 Rocker Switches Not evaluated by UL T3MK77F16D 16 Door Kit with PTC Outputs Fully assembled kit includes Trove3 enclosure with TM3 Altronix Mercury backplane Two 2 eFlow104NB Power Supply Chargers Two 2 ACM8CB PTC Protected Access Power ...

Page 2: ...ss Enclosure Dimensions H x W x D 36 12 x 30 125 x 7 06 917 5mm x 768 1mm x 179 3mm Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 ANSI and with all local codes and authorities having jurisdiction Product is intended for indoor use only 1 Remove backplane from enclosure Do not discard hardware 2 Mark and predrill holes in the wall to line ...

Page 3: ...UT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N N COMMON POWER OUTPUTS P FUSED P...

Page 4: ...COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND 1 2 3 4 5 6 7 8 INPUT TRIGGER 10A 250V INP T RET NO C NC FACP INTERFACE Power Control MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT P N R1 LED Altronix PD8UL CB N COMMON POWER OUTPUT...

Page 5: ...Trove3 Mercury Kits Installation Guide 5 Notes ...

Page 6: ... RMR LINQ2 Features UL Listed in the U S and Canada Local or remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state change and unit temperature Access control and user managment Restrict read write Restrict users to specific resources Two 2 integr...

Page 7: ...ts Installation Guide 7 TM3 Dimensions 34 x 28 x 0 3125 863 6mm x 711 2mm x 7 9mm 0 45 11 4mm 2 5 63 5mm 2 50 8mm 13 5 342 9mm 13 5 342 9mm 13 5 342 9mm 25 635mm 0 156 3 96mm 1 0 25 4mm 1 0 25 4mm 34 863 6mm 28 711 2mm ...

Page 8: ...12 768 1mm 14 01 355 9mm 14 01 355 9mm 1 25 31 8mm 1 55 39 4mm 1 78 45 2mm 1 25 31 8mm 1 07 27 2mm 1 10 27 9mm 2 50 8mm 10 75 273 1mm 10 75 273 1mm 10 62 269 8mm 2 00 50 8mm 10 75 273 1mm 10 75 273 1mm 10 62 269 8mm 36 12 917 5mm 33 63 854 2mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 web site www altron...

Reviews: