- 2 - 

ULXB Power Supply/Chargers

Stand-by Specifications:

AL400ULXB2:

Output

Burg. Application

4 hr. of Stand-by/

5 min. of Alarm

Fire Applications

24 hr. of Stand-by/

5 min. of Alarm

60 hr. of Stand-by/

5 min. of Alarm*

Access Control 

Applications 

Stand-by

12VDC / 40AH Battery

Stand-by = 4.0A

Alarm = 4.0A

Stand-by = 1.0A

Alarm = 4.0A

Stand-by = 300mA

Alarm = 4.0A

4 hrs./4A

24VDC / 12AH Battery

Stand-by = 200mA

Alarm = 3.0A

24VDC / 40AH Battery

Stand-by = 3.0A

Alarm = 3.0A

Stand-by = 1.0A

Alarm = 3.0A

Stand-by = 300mA

Alarm = 3.0A

4 hrs./3A

AL600ULXB:

Output

Burg. Applications

4 hr. of Stand-by/

5 min. of Alarm

Fire Applications

24 hr. of Stand-by/

5 min. of Alarm

60 hr. of Stand-by/

5 min. of Alarm*

Access Control 

Applications 

Stand-by

12VDC / 40AH Battery

Stand-by = 6.0A

Alarm = 6.0A

Stand-by = 1.0A

Alarm = 6.0A

Stand-by = 300mA

Alarm = 6.0A

4 hrs./6A

24VDC / 12AH Battery

Stand-by = 200mA

Alarm = 6.0A

24VDC / 40AH Battery

Stand-by = 6.0A

Alarm = 6.0A

Stand-by = 1.0A

Alarm = 6.0A

Stand-by = 300mA

Alarm = 6.0A

4 hrs./6A

AL1012ULXB:

Output

Access Control Applications Stand-by

12VDC / 12AH Battery

30 minutes of backup @ 10A

AL1024ULXB2:

Output

15 min. of 

Stand-by/

5 min. of Alarm

Burg. Applications

4 hr. of Stand-by/

5 min. of Alarm

Fire Applications

24 hr. of Stand-by/

5 min. of Alarm

60 hr. of Stand-by/

5 min. of Alarm*

Access Control 

Applications 

Stand-by

24VDC / 12AH 
Battery

Stand-By = 8A

Alarm = 10A

Stand-By = 1.5A

Alarm = 10A

Stand-By = 200mA

Alarm = 10A

Stand-By = 100mA

Alarm = 10A

20 mins./8A

Output

15 min. of 

Stand-by/

5 min. of Alarm

Burg. Applications 

4 hr. of Stand-by/

5 min. of Alarm

Fire Applications

24 hr. of Stand-by/

15 min. of Alarm

60 hr. of Stand-by/

15 min. of Alarm*

Access Control 

Applications 

Stand-by

24VDC / 65AH 
Battery

Stand-By = 8.0A

Alarm = 10A

Stand-By = 1.5A

Alarm = 10A

Stand-By = 500mA

Alarm = 10A

4 hrs./8A

*Not evaluated by UL.

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, the Canadian 
Electrical Code and with all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Refer to Sub-Assembly Installation Instructions for mounting Rev. MS020119. 
2.  Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board 
  (Fig. 1e, pg. 4)
3.  Connect unswitched AC power (115VAC 60Hz) to the terminals marked [L, N] (Fig. 1a, pg. 4). Use 14 AWG 
  or larger for all power connections (Battery, AC input, DC output). Use 22 AWG to 18 AWG for power-
  limited circuits (AC Fail/Low Battery reporting).
  Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, DC Output 
  (refer to specification chart pg. 1)
, Battery Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 
  equipment. There are no user serviceable parts inside. 
  Refer installation and servicing to qualified service personnel.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered to the terminals marked [+ DC –] (Fig. 1d, pg. 4).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 
  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. 
  Connect battery to terminals marked [– BAT +] (Fig. 1c, pg. 4).
 

Note: Separate enclosure must be used for housing 40AH or 65AH batteries.

7. It is required to connect appropriate signaling notification devices to [AC FAIL] & [BAT FAIL] 
  (Fig. 1b, pg. 4) supervisory relay outputs. Use 22AWG to 18AWG wires. AC fail will report in 5 minutes. 
  To delay report for 6 hours cut “AC Delay” jumper (Fig. 1, pg. 4).

Summary of Contents for ULXB Series

Page 1: ... a power limited output is required in the end product application the DC output from the power supply must be connected to a separately Listed control unit or accessory board that provides power limited outputs The product s providing the power limited output s must be listed as appropriate for the particular end product application fire alarm burglar alarm access control and wired in accordance ...

Page 2: ...tand By 500mA Alarm 10A 4 hrs 8A Not evaluated by UL Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI the Canadian Electrical Code and with all local codes and authorities having jurisdiction Product is intended for indoor use only 1 Refer to Sub Assembly Installation Instructions for mounting Rev MS020119 2 Set desired DC outpu...

Page 3: ...ON OFF Loss of AC Stand by is battery supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Terminal Identification Terminal Legend Function Description L G N Connect 115VAC to these terminals L to hot N to neutral Fig 1a pg 4 DC AL400ULXB2 12VDC 4A or 24VDC 3A continuous output Power Limited output Fig 1d pg 4 AL600ULXB 12VDC or 24VDC 6A continuous ...

Page 4: ... Maximal77 BC300 BC400 BC800 Maximal Trove1 and Trove2 Fig 1 ULXB configuration Output Voltage Selection Dip Switch Not applicable for AL1012ULXB and AL1024ULXB2 AL1012ULXB terminals marked DC AL1024ULXB2 terminals marked BAT DC BAT FAIL NC C NO NC C NO BAT AC FAIL DC AC BAT L G N 5A 250V OFF 24V ON 12V 1a 1b 1c 1d 1e ON Altronix is not responsible for any typographical errors 140 58th Street Broo...

Reviews: