Vertiline24C 

- 3 -

Automotive
Blade Fuse

Installation Instructions:

1.  Attach mounting brackets to Vertiline unit for rack or wall mount installation (Figs. 4-5, pg. 7)
 

Affix rubber pads to Vertiline for shelf installation (Fig. 6, pg. 7).

2.  Secure the unit in a rack, mount unit to a wall or place unit on a shelf as desired (unit should be spaced at 
 

least 3” from any video monitors). When installing the unit in a rack, allow for one half of a U spacing 

 

above the unit for ventilation.

3.  Plug the grounded AC line cord (included) into the IEC 320 connector of the Vertiline unit (Fig. 1f, pg. 4)
 

Insert the plug end of the line cord into a grounded AC receptacle.

4.  Set illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3, pg. 6).
5.  Select 24VAC or 28VAC power output for cameras 1-24 with the corresponding voltage adjustment 
 switches 

(Fig. 1b, pg. 4).

6.  Measure output voltage before connecting cameras. This helps avoiding potential damage.
 

All terminals with common suffix (P) “1P, 2P ...” are the same polarity.

7.  Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3, pg. 6)
8.  Connect the power outputs of terminals marked [1P & 1N] to the power inputs of camera 1 (Fig. 2, pg. 5).
 

Repeat this step for each additional camera (Outputs 2-24). After the wiring is completed, insert terminal 

 

block into the corresponding connector and secure by tightening the screws.

9.  Upon completion of the wiring, set illuminated master power disconnect circuit breaker to the 
 

ON (RESET) position (Fig. 3, pg. 6).

10.  The power LEDs (Green) on the faceplate for Outputs 1-24 will illuminate when AC power is present 
 

(Fig. 1a, pg. 4). If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a 

 

tripped PTC caused by a short circuit or overload condition. If all of the LEDs are OFF, there may be a 

 

complete loss of supply power to the Vertiline unit or the illuminated master power disconnect circuit 

 

breaker is in the OFF position or the main fuse 1-12 or 13-24 is blown (Fig. 1c, pg. 4).* 

 

To restore the power output for Vertiline24C or Vertiline246C:

 

1-  Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).

 

2-  Eliminate the trouble condition.

 

3-  Replace the corresponding automotive blade fuse.*

 

4-  Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).

 

To restore the power output for Vertiline24CD or Vertiline246CD:

 

1-  Switch corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).

 

2-  Eliminate the trouble condition.

 

3-  Allow 1 minute for PTC to cool off.

 

4-  Switch output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).

*Note: Replace fuses with same type and rating:
 

 

Output fuses are rated @ 3A for all models.

 

 

Main fuse ratings:

 

 

10A for Vertiline24C and Vertiline24CD.

 

 

15A for Vertiline246C and Vertiline246CD.

Summary of Contents for Vertiline24C

Page 1: ...s Include Vertiline24C 24VAC or 28VAC 10A Twenty four 24 fuse protected outputs Vertiline246C 24VAC or 28VAC 14A Twenty four 24 fuse protected outputs Vertiline24CD 24VAC or 28VAC 10A Twenty four 24 PTC protected outputs Vertiline246CD 24VAC or 28VAC 14A Twenty four 24 PTC protected outputs ...

Page 2: ...cal Units can be rack wall or shelf mounted Modular 1U standard EIA 19 rack mount chassis Enclosure Dimensions H x W x D approx 1 625 x 19 125 x 8 5 41 3mm x 486mm x 216mm Twenty four 24 Output Rack Mount Configuration Reference Chart Altronix Model Number Output Voltage VAC Total Output Current Power Number of Outputs Output Protection Class 2 Rated Power Limited Output Protection Current max per...

Page 3: ...nal block into the corresponding connector and secure by tightening the screws 9 Upon completion of the wiring set illuminated master power disconnect circuit breaker to the ON RESET position Fig 3 pg 6 10 The power LEDs Green on the faceplate for Outputs 1 24 will illuminate when AC power is present Fig 1a pg 4 If any of these LEDs are off a loss of AC power output may be due to a blown fuse or a...

Page 4: ... 21 22 23 24 N P N P N P N P Main Fuse 1 12 28VAC OFF 24VAC 28VAC OFF 24VAC 1b Output voltage switches Selects 24VAC or 28VAC or OFF for each output 1a LED s 1 24 Power LED indicators 1f IEC 320 Connector 115VAC 60Hz grounded line cord included Fig 1 1d Power Outputs 24VAC or 28VAC 1e Output Fuses Automotive blade fuses Vertiline24C or Vertiline246C rear Vertiline24C Vertiline24CD Vertiline246C or...

Page 5: ... 11 12 5 6 7 8 1 2 3 4 21 22 23 24 Main Fuse 13 24 1 2 3 4 N P N P N P N P 5 6 7 8 N P N P N P N P 9 10 11 12 N P N P N P N P 13 14 15 16 N P N P N P N P 17 18 19 20 N P N P N P N P 21 22 23 24 N P N P N P N P Main Fuse 1 12 28VAC OFF 24VAC 28VAC OFF 24VAC AC POWER Fig 2 Typical Hookup ...

Page 6: ...sis Mechanical Drawing Dimensions H x W x D 1 625 x 19 125 x 8 5 41 3mm x 486mm x 216mm OFF RESET 28VAC OFF 24VAC 28VAC OFF 24VAC 17 18 19 20 13 14 15 16 9 10 11 12 5 6 7 8 1 2 3 4 21 22 23 24 28VAC OFF 24VAC 28VAC OFF 24VAC AC POWER Main Fuse 13 24 1 2 3 4 N P N P N P N P 5 6 7 8 N P N P N P N P 9 10 11 12 N P N P N P N P 13 14 15 16 N P N P N P N P 17 18 19 20 N P N P N P N P 21 22 23 24 N P N P...

Page 7: ...l Mount Installation 1 Install mounting brackets A on the left and right side of rack chassis using two 2 flat head screws B included Fig 5a 2 Place unit at desired location and secure with mounting screws not included Fig 5b Caution It is necessary to make sure mounting screws are securely fastened to a beam when installing Fig 5 B A Fig 5b Fig 5a Fig 6 Shelf Installation 1 Position and affix rub...

Page 8: ...onsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIVertiline24CSeries G23R MEMBER Notes ...

Reviews: