TR-3019-230E-ICU / TR-3019-400E-ICU
43
43
INDICATION
ACTION
SETUP OPERATIONS
3
Deactivation posi-
tion of input
PH
Use the button
or the button
to set the
door leaf to the required position, from which input
PH
will be deactivated
4
Confirm
deactivation of
input
PH
and exit
the set-up mode
Press and hold the button
. Then press both
buttons simultaneously
and hold all the
buttons at least 3 seconds.
When the LED fades (there will be no rapid flashes),
release the buttons in the reverse sequence.
Exit to Standby mode will occur automatically after
the LED fades
Y
ATTENTION!
After the set-up, test the security device operation connected to input
PH
, de-
scribed in
table
5 for
DIP10
switch.
8.
INDICATION
During operation, the indication of LED 1 (
Fig.
13) of the control station informs on the drive
operation and failures (
table
8).
Table
8
INDICATION
DESCRIPTION
lights continuously
button is pressed or input
S
is activated (
table
2, connector
XP3
), or motor thermal
protection is activated.
Performing door movement commands is not allowed; stop of the movement
1 flash
End position.
Stop of the movement in the set end position
2 flashes
Input
PH
is activated (
table
2, connector
XP3
).
Performing door closing commands is not allowed
3 flashes
Input
SE
is activated (
table
2, connector
XP7
).
Preforming door closing commands is not allowed
4 flashes
A failure occurs during automatic verification of safety devices connected to the input
PH
(
table
5,
DIP5
).
Performing door closing commands is not allowed.
5 flashes
Motion absence error.
Stop operation
6 flashes
End positions are not set (Section 6).
Performing door movement commands is not allowed
7 flashes
Encoder error (incorrect encoder signal, malfunctions).
Performing door movement commands is not allowed; stop of the movement
8 flashes
Power voltage value is out of operation range.
Performing door movement commands is not allowed
9 flashes
Time of continuous door movement in one direction (70 s) is exceeded.
Stop of the movement