TR-3019-230E-ICU / TR-3019-400E-ICU
38
38
SETTING THE OPERATION PARAMETERS
Y
ATTENTION!
After re-setting the end positions and, if additional settings were previously per-
formed to deactivate input
SE
and / or input
PH
(section 7.1 and / or section 7.2), it is necessary
to test the safety device operation connected to the inputs mentioned. Testings are described in
table
5 (
DIP9
,
DIP10
switch). If necessary, repeat the additional setting to deactivate the input.
7.
SETTING THE OPERATION PARAMETERS
The operation parameters are set up with DIP-switches
SW1
. In the drive
TR-3019-230E-ICU
SW1
is located on the unit board (
Fig.
11). In the drive
TR-3019-400E-ICU
SW1
is located on
the optional module A1 of the unit (
Fig.
12). Positions of the DIP-switches are described in
table
4. The settings are described in
table
5.
Y
ATTENTION!
Operation parameters setup is performed when the drive is powered off (drive
mains switch is cut off the line)! The settings become activated when the power is restored.
Table
4
DIP DESCRIPTION
SWITCH POSITION
OFF
*
ON
1
Operation mode
Manual (without latching)
Pulse (with latching) /
Manual mode in the closing
direction
**
2
Safety edge type (
SE
input)
Resistive (8.2 kOhm)
Optoelectronic (
OSE
)
3
Activation of
XP6
connector contacts
(operation of light signal device)
Activation when the door
moves (signal lamp)
Activation when the door is
fully opened (traffic light)
4
3 s delay of movement
Disabled
Enabled
5
Automatic verification of safety devices
connected to the input
PH
Disabled
Enabled
6
Pause time before automatic closing
DIP № 6
DIP № 7
OFF
OFF
Disabled
ON
OFF
10 s
OFF
ON
20 s
ON
ON
30 s
7
8
Automatic closing 5 s after
PH
input
activation
Disabled
Enabled
9
Failure of input
SE
to operate near the floor
Off
On
10
Failure of input
PH
to operate at a distance
from the floor
Off
On
Table
5
DIP SETTING
DESCRIPTION
1
Operation mode
In the manual operation mode
press and hold the control button
or
to move the door to the correspondent end position (
Fig.
13). If the button is
released, door leaf movement stops. To stop the movement or block the start
of movement, press
/ input
S
(
table
2). Inputs
SBS
,
PH
and
SE
in the manual
operation mode are disabled.
In the pulse mode
press the required control button
or
and the door
will move automatically to the corresponding end position end position. To stop
the movement, press
. Inputs
SBS
,
PH
and
SE
in the pulse operation mode
are enabled
*
When the drive is delivered, all DIP-switches are in
OFF
position (factory settings).
**
In case of a failure or malfunctioning of safety devices when closing (inputs
SE
,
PH
).