background image

 Always 

O

n UPS Systems

 

 

M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12 

vi 

 

THIS PAGE IS INTENTIONALLY BLANK

Summary of Contents for GES-302N

Page 1: ...N Series Single Phase Input Single Phase Output ABS Approved UPS System GES 701N GES 302N ABS On Line 700VA 1kVA 1 5kVA 2kVA 3kVA Operators Manual M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06...

Page 2: ...M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 THIS PAGE IS INTENTIONALLY BLANK...

Page 3: ...Power Supply Please complete the Warranty Card supplied with this UPS and return it by mail to Always On UPS Systems Inc This activates the warranty If additional information or technical assistance...

Page 4: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 ii THIS PAGE IS INTENTIONALLY BLANK...

Page 5: ...EN SPILLED INTO THE UNIT 3 THE UNIT DOES NOT OPERATE NORMALLY EVEN THOUGH THE OPERATING INSTRUCTIONS HAVE BEEN FOLLOWED DO NOT PLACE MAGNETIC STORAGE MEDIA ON TOP OF THE UNIT AS THIS CAN RESULT IN DAT...

Page 6: ...ALS AND OTHER CHEMICAL HAZARDOUS WASTE FOR PROPER DISPOSAL CONSULT YOUR LOCAL STATE AND FEDERAL EPA AND OTHER ENVIRONMENTAL LAWS AND REGULATIONS USE ONLY THE POWER SUPPLY CORD PROVIDED WITH THIS UNIT...

Page 7: ...PERATION 16 6 4 CONTROL PANEL FUNCTIONS 16 6 5 UPS CONFIGURATIONS 16 7 AUDIBLE ALARM 19 7 1 BACKUP MODE 19 7 2 LOW BATTERY 19 7 3 BYPASS 19 7 4 FAULT 19 8 BATTERY MAINTENANCE 19 9 ENVIRONMENTAL PROTEC...

Page 8: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 vi THIS PAGE IS INTENTIONALLY BLANK...

Page 9: ...ne dual conversion system in the following modes Normal The critical AC load is continuously supplied by the UPS Inverter The input Rectifier derives power from a utility AC source and supplies power...

Page 10: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 2 THIS PAGE IS INTENTIONALLY BLANK...

Page 11: ...your loads from noticing any power fluctuations eg Blackouts brownouts over voltage conditions The UPS will supply a sufficient amount of steady constant AC power during these power fluctuations allo...

Page 12: ...energy from the battery system and raises the DC voltage to the DC Bus operating voltage for the inverter This allows the inverter to operate continuously at its optimum efficiency and voltage thus i...

Page 13: ...ass can be activated in the LCD panel though on line can be run permanently if preferred Free Run Mode The UPS operates in free run mode when input frequency is outside of the selected Input Frequency...

Page 14: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 6 THIS PAGE IS INTENTIONALLY BLANK...

Page 15: ...dealer from whom you purchased the unit and save the packaging for future shipment When the unit has passed the initial inspection record the Installation date on the back panel of the unit and in the...

Page 16: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 8 THIS PAGE IS INTENTIONALLY BLANK...

Page 17: ...perature of 15 C to 25 C Battery life decreases by half for every 10 C above 25 C Air vents are located on the front rear and sides of the UPS system Do not position the UPS in an enclosed area with r...

Page 18: ...VA 1400W 2000VA 110 50 60 20A 80 138Vac 20 3A max 120V 12 6A 2000VA 1400W 2000VA 220 50 60 15A 160 276Vac 10 2A max 208 220 9 61A 9 1A 3000VA 2100W 3000VA 110 50 60 30A 80 138Vac 30 5A max 120V 24 9A...

Page 19: ...1 Location The cable sizes input breakers outlets and distribution methods used during installation are subject to the local and national electrical codes of practice therefore are not detailed here P...

Page 20: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 12 THIS PAGE IS INTENTIONALLY BLANK...

Page 21: ...ded outlet The UPS can be started by pushing the ON OFF button located on the front panel for at least three seconds The UPS should now start its self test testing the internal functions main synchron...

Page 22: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 14 THIS PAGE IS INTENTIONALLY BLANK...

Page 23: ...Description O P VOLT V Shows Output AC voltage O P FREQ Hz Shows Output Frequency I P VOLT V Shows Input AC Voltage I P FREQ Hz Shows Input Frequency BAT VOLT V Shows Battery Voltage O P Load Shows of...

Page 24: ...Push the FUNC button to choose other function e Push the STATUS button to enable your function f Push the STATUS button to confirm and enable the selected function g If nothing has been pressed for 1...

Page 25: ...onfirm or save your selection Other options are saved and started automatically See Table 6 5 1 for further details 6 If no buttons are pressed for 10 seconds the UPS shall exit the configuration mode...

Page 26: ...N 1 OFF 2 ON 1 OFF 2 OFF 1 ON 2 OFF Do Battery Test Battery Test Detect battery is within normal parameters Silence Function Silence Set Enable or disable silence function ON OFF OFF Number of Externa...

Page 27: ...UPS the charge level of the batteries will be maintained automatically The typical recharge time to 90 from 0 charge level is 6 8 hours Under normal operating conditions the supplied batteries are ex...

Page 28: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 20 THIS PAGE IS INTENTIONALLY BLANK...

Page 29: ...uired precautions Keep unauthorized personnel away from the batteries Do not dispose of batteries in a fire They may explode Do not open or mutilate the battery or batteries Released electrolyte is ha...

Page 30: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 22 THIS PAGE IS INTENTIONALLY BLANK...

Page 31: ...cable provided with UPS may be used to connect to your computer which is accomplished through the UPS RS232 port Also ensure that the operating system on your computer is supported Instructions provi...

Page 32: ...eled IN and the output connector to the jack labeled OUT 11 6 Load segments 700 3000 VA The power management software controls the sets of receptacles known as load segments which provides organized s...

Page 33: ...Caution Observe the appropriate cable connections regulation e g National Electrical Code NEC in the USA at all times Using cables of improper size may damage your equipment and cause fire hazards Gro...

Page 34: ...tems may require an additional 120VAC supply to power the additional charger Cable not supplied Start up Procedure 1 Once all connections are secure turn the Battery Breaker On 2 Connect the UPS to th...

Page 35: ...5V 12V the UPS will power off after 1 second Output signal pin assignment Fault Pin 1 2 3 On Battery Pin 4 5 6 Battery Low Pin 7 8 On Bypass Pin 9 10 On Inverter Pin 11 12 Dry Contact Capacity 3A 250V...

Page 36: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 28 THIS PAGE IS INTENTIONALLY BLANK...

Page 37: ...test Over Charge Constant Beep Batteries are over charged Turn off protected loads Turn off UPS and call local dealer Low Battery 2 beeps every 5 seconds The unit is operating on Battery Power and wil...

Page 38: ...Always On UPS Systems M0309_N_Series_ABS_700 3kVA_User_Manual V2 8 2012 06 12 30 THIS PAGE IS INTENTIONALLY BLANK...

Page 39: ...ealed Lead Acid Maintenance Free Hot Swappable Cartridge Quantity 2 3 3 6 6 Voltage 24VDC 36VDC 36VDC 72VDC 72VDC Recharge Time 4 Hrs to 90 Recovery Advanced Battery Management Auto Self test Temperat...

Page 40: ...Email sales alwaysonups com Website www alwaysonups com 15 2 QA Warranty Questions Always On UPS Systems Inc Bldg 1 150 Campion Road Kelowna BC Canada V1X 7S8 Phone 250 491 9777 Ext 209 Fax 250 491 9...

Reviews: