7.   BATTERY REPLACEMENT 

 

1. 

Your battery should run anywhere from 3-5 years before it needs to be 
replaced. 

2. 

Please follow the instructions below for easy, trouble free, battery replacement. 

3. 

Turn the UPS off.  Follow procedure previously mentioned. 

4. 

Unplug the UPS from utility power source and disconnect all connected loads. 

5. 

Disconnect AC power cord from unit. 

6. 

Turn unit upside down. Using a Philips screwdriver, unscrew the four (4) 
screws holding the top of the unit to the bottom.  Put screws in a safe place for 
reassembly. 

7. 

Holding the top together firmly with the bottom, turn the entire unit right side 
up. 

8. 

Carefully lift top cover off and place it to the side.  The connecting wires and 
electronics will be exposed.   

 

 

CAUTION:  

Be careful not to touch any inner components of the Limousin UPS when 
changing the battery. Electrical shock hazards may be present.

 

 
9. 

Remove the two (2) connecting wires from the battery. 

10. 

You can now easily remove the battery from the unit 

 

 

CAUTION:  

Do not dispose of battery in a fire. Do not attempt to open the battery.

 

 

 

 

CAUTION:  

When replacing the battery, only use tools with insulated handles and 
remove metal jewelry like watches, rings, etc., to avoid risk of electrical 
shock and burns.

 

 

11. 

Place your new battery in the same position, direction and reconnect the wires.  
The red wire to the positive (+) pole and black wire to the negative (-) pole. 

12. 

Reverse steps 5, 4 and 3 (in that order) to reassemble the unit. 

13. 

Follow start-up instructions in order to properly reconnect your equipment. 

Summary of Contents for Limousin II

Page 1: ...Always On UPS Systems Inc Limousin II Single Phase Input Single Phase Output Uninterruptible Power Supply 600VA User Manual Version 1 4...

Page 2: ...and performance of the UPS never load the UPS with a hair dryer heater laser printer or other types of inductive loads 9 The UPS has its own internal energy source battery therefore the output recepta...

Page 3: ...Switching Off the UPS 4 4 3 Self Test 4 4 4 Silence the Alarm 4 4 5 Cold Start 4 4 6 Green Function 4 5 AUDIBLE ALARM 5 5 1 Back Up Slow Alarm 5 5 2 Low Battery Rapid Alarm 5 5 3 Overload Continuous...

Page 4: ...eration of the UPS and the condition of the battery The Limousin provides two single phase 120VAC outlets for ease of connection to you equipment Overload protection is also a feature of this unit The...

Page 5: ...or more than 3 seconds to turn the UPS ON or OFF press and hold the button less than 1 second to activate a self test or silence the back up alarm Figure 2 1 Limousin Front Rear Panel 2 2 Rear Panel 3...

Page 6: ...load into the power outlets on the rear of the Limousin UPS To use the UPS as a master on off switch make sure all of the loads connected to the UPS are switched on CAUTION Never connect a laser print...

Page 7: ...to on line operation On completion of the test the LED stops flashing and remains on If the UPS fails the self test it immediately returns to on line operation If a failure occurred recharge the batte...

Page 8: ...test See replace battery section for battery replacement or call your dealer for services 6 SOFTWARE OPTIONS 6 1 UPSMON Software The UPSMON software uses the standard RS 232 interface to perform monit...

Page 9: ...open files before the battery reserves are exhausted 3 The ability to turn off the UPS 4 The ability to make the UPS perform a self test Some computers are equipped with a serial connector to link wit...

Page 10: ...r off and place it to the side The connecting wires and electronics will be exposed CAUTION Be careful not to touch any inner components of the Limousin UPS when changing the battery Electrical shock...

Page 11: ...center to replace batteries UPS has no reaction while AC power is connected yet starts after pushing power on off switch Fuse at back panel burnt No AC input UPS AC detecting circuit fail Check power...

Page 12: ...ealed Lead Acid Typical Recharge Time 4 hours to 90 of full capacity Protection Automatic self test discharge protection replace battery indicator BATTERY Back up Time 10 30 minutes depending on load...

Page 13: ...nups com Website www alwaysonups com 10 2 QA Warranty Questions Always On UPS Systems Inc Bldg 1 150 Campion Road Kelowna BC Canada V1X 7S8 Phone 250 491 9777 Ext 209 Fax 250 491 9775 Email qa alwayso...

Reviews: