Always
O
n UPS Systems
4.0
Installation
The Slimline/Doormount UPS is intended for installation in a relatively temperature-controlled
indoor area, free of conductive contaminants. Installation should be conducted by qualified
individuals.
lled
indoor area, free of conductive contaminants. Installation should be conducted by qualified
individuals.
4.1.
Location
4.1.
Location
The NDM Series UPS is intended for installation in a temperature and humidity
controlled environments, free of conductive contaminants with unrestricted airflow.
Absolute maximum ambient temperature at sea level must not exceed 60
º
C (140
º
F)
for the standard N-DM model and 74
º
C (165
º
F) for the high temperature option.
The NDM Series UPS is intended for installation in a temperature and humidity
controlled environments, free of conductive contaminants with unrestricted airflow.
Absolute maximum ambient temperature at sea level must not exceed 60
º
C (140
º
F)
for the standard N-DM model and 74
º
C (165
º
F) for the high temperature option.
IMPORTANT: Maximum battery life is obtained by placing the battery in a room at
an ambient temperature of 15
º
C to 25
º
C. Battery life decreases by half for every
10
º
C above 25
º
C.
IMPORTANT: Maximum battery life is obtained by placing the battery in a room at
an ambient temperature of 15
º
C to 25
º
C. Battery life decreases by half for every
10
º
C above 25
º
C.
Air vents are located on the front and sides of the UPS system. Do not position the
UPS in an area with restricted airflow. Try to allow a minimum of 100mm (4 inches)
around the UPS for easy operator access to the connections. (Figure 4.1.1)
Air vents are located on the front and sides of the UPS system. Do not position the
UPS in an area with restricted airflow. Try to allow a minimum of 100mm (4 inches)
around the UPS for easy operator access to the connections. (Figure 4.1.1)
Maintenance and Servicing of the Slimline/Doormount UPS requires access to the
front and sides of the UPS system. Provide the necessary free space and flexible
wiring to allow complete access to the UPS system.
Maintenance and Servicing of the Slimline/Doormount UPS requires access to the
front and sides of the UPS system. Provide the necessary free space and flexible
wiring to allow complete access to the UPS system.
4.2.
Cabinet View
4.2.
Cabinet View
4.3.
4.3.
Figure 4.2.1
M0301_N_Series_DM_Manual V1.4 2012-06-12
7