M0301_N_Series_DM_Manual V1.4 2012-06-12
16
7.0
Audible Alarm
7.1.
Backup mode
The UPS will beep once every five (5) seconds and the BACKUP LED will light,
when the unit is in back-up mode.
(beep - - - - beep - - - - beep) [Slow beep]
7.2.
Low Battery
The UPS will beep twice every five (5) seconds and the BACKUP LED will flash,
when the batteries are almost depleted.
(beep - beep - beep) [Fast beep]
7.3.
Bypass
The UPS BYPASS LED will illuminate. The UPS will not beep.
7.4.
Fault
The UPS will sound a continuous beep and the FAULT LED will illuminate and the
LCD will display the cause.
(beeeeep) [Continuous beep]
8.0
Battery Maintenance
•
On initial start-up it is recommended the batteries have a minimum of eight (8) hours of
charging to ensure proper operation.
•
During normal operation of the UPS, the charge level of the batteries will be maintained
automatically.
•
Under normal operating conditions, the supplied batteries are expected to last
approximately five (5) years, or 200 discharges, from date of receipt.
•
Refer to the purchase date you recorded in this manual if you suspect that the batteries
have been exhausted.
•
If the UPS is to remain in storage for an extended period of time, it is strongly
recommended that the UPS be powered up for a period of twenty-four (24) hours, every
three (3) months, to recharge the batteries and prevent premature failure.
9.0
Environmental Protection
The UPS incorporates sealed maintenance free lead-acid batteries or absorbent glass mat valve
regulated lead acid (AGM-VRLA) batteries. When replacing the batteries, the defective
batteries must be disposed of carefully to prevent any risk of environmental pollution by the
harmful products they contain (lead and acid). Please refer to local and regional environmental
codes when disposing of the batteries.