M0301_N_Series_DM_Manual V1.4 2012-06-12 

 

1.0

 

Introduction 

Congratulations on your choice of the Always 

O

n NDM Series On-Line Uninterruptible Power 

System (UPS). The NDM Series Slimline/Doormount features the very latest, top of the line, 
microprocessor technology and IGBT transistors for clean, highly regulated, PWM (Pulse 
Width Modulated) True Sine Wave power all in a convenient, lightweight package.  This 
package allows for the easy installation of the UPS into a compact enclosure or cabinet doors 
with the batteries located remotely for simple power conditioning and battery backup retrofit. 
 
For ease of use, the NDM Series Slimline/Doormount utilizes an LCD display to indicate load 
percentage, battery capacity, input voltage, output voltage, input frequency, output frequency, 
internal UPS temperature and the mode of operation.  It also provides self-diagnostics, a 
combination On/Alarm Silence/Manual Battery Test button, a combination Off/Bypass button, 
and two levels of alarms when the unit is operating on battery. 
 
The NDM Series Slimline/Doormount incorporates an interface port for communications 
between a status contact module, with dry contacts and programmable timer relay, or a PC and 
provisions to connect an external charger and additional monitoring features described later in 
the manual. 
 

1.1.

 

Modes of Operation  

The NDM Series Slimline/Doormount UPS is designed to continuously operate on-
line as a dual conversion system in the following modes: 

 
Normal - 

The critical AC load is continuously supplied by the UPS Inverter.  The 

input Rectifier derives power from a utility AC source and supplies power to the 
Inverter while simultaneously float-charging the storage batteries. 
 

Back-Up - 

Upon failure of utility AC power, the Inverter obtains power from the 

batteries without interruption.  There are no interruptions in power to the critical load 
upon failure or restoration of the utility AC source. 
 

Recharge 

- Upon restoration of utility AC power after an outage, the Rectifier will 

automatically restart and supply power to the inverter and battery charger.  For larger 
battery banks, an external boost charger may be necessary to aid in reducing recharge 
time. 
 

Automatic Restart

 - Upon restoration of utility AC power, after an extended outage 

and complete battery discharge, the UPS will automatically restart and resume 
supplying power to the critical load.  Also the battery charger will automatically 
recharge the batteries.  This feature is enabled in the factory and is capable of being 
disabled (consult factory). 
 

Static Bypass

 - The bypass will provide an alternate path for power to the critical 

load and is capable of operating in the following manner: 

Automatic

 - In the event of the inverter overload capacity being exceeded or 

should an internal failure occur, the UPS will perform an automatic transfer of 
the critical AC load from the inverter to the bypass source. 

Manual

 - Should the UPS need to be taken out of service for limited 

maintenance or repair, manual activation of the bypass will cause an immediate 
transfer of the critical AC load from the inverter to the bypass source.  The input 
rectifier, inverter, and battery charging operations will be inhibited until the user 
transfers the UPS back to normal operation. 

Summary of Contents for GES-102NDM

Page 1: ...SLIMLINE DOORMOUNT UPS For Traffic Applications GES 102NDM GES 152NDM On Line 1kVA 1 5kVA Operators Manual M0301_N_Series_DM_Manual V1 4 2012 06 12...

Page 2: ...M0301_N_Series_DM_Manual V1 4 2012 06 12 THIS PAGE IS INTENTIONALLY BLANK...

Page 3: ...oid all warranties and may void UL cUL CSA listing Unauthorized modifications also can result in personal injury death or destruction or the equipment Uninterruptible Power Supply Uninterruptible Powe...

Page 4: ...NSULTED WHEN 1 LIQUID HAS BEEN SPILLED INTO THE UNIT 2 THE UNIT DOES NOT OPERATE NORMALLY EVEN THOUGH THE OPERATING INSTRUCTIONS HAVE BEEN FOLLOWED DO NOT PLACE MAGNETIC STORAGE MEDIA ON TOP OF THE UN...

Page 5: ...UNIT IS LEAKING LIQUID OR IF A WHITE POWDERY RESIDUE IS PRESENT BATTERIES MAY CONTAIN METALS AND OTHER CHEMICAL HAZARDOUS WASTE FOR PROPER DISPOSAL CONSULT YOUR LOCAL STATE AND FEDERAL EPA AND OTHER E...

Page 6: ...SPLAY 12 6 2 UPS METERING DISPLAY 12 6 3 BUTTON OPERATION 13 6 4 CONTROL PANEL FUNCTIONS 13 6 5 UPS CONFIGURATIONS 13 7 0 AUDIBLE ALARM 16 7 1 BACKUP MODE 16 7 2 LOW BATTERY 16 7 3 BYPASS 16 7 4 FAULT...

Page 7: ...supplied by the UPS Inverter The input Rectifier derives power from a utility AC source and supplies power to the Inverter while simultaneously float charging the storage batteries Back Up Upon failu...

Page 8: ...rue sine wave Thus it may be used to protect your loads from any power fluctuations e g blackouts brownouts over voltage conditions The UPS will supply a sufficient amount of steady constant AC power...

Page 9: ...tery system and raises the DC voltage to the DC Bus operating voltage for the inverter This allows the inverter to operate continuously at its optimum efficiency and voltage thus increasing reliabilit...

Page 10: ...maximizes efficiency and reduces power consumption Alternating between bypass and on line modes is achieved automatically and in accordance with the conditions of the AC supply power On line mode may...

Page 11: ..._N_Series_DM_Manual V1 4 2012 06 12 5 Other than during the initial 24 hours after startup or while the UPS is in charging mode diagnostic tests please see chapter 6 5 can be performed manually from t...

Page 12: ...mage or anything is missing contact the dealer from whom you purchased the unit and save the packaging for future shipment When the unit has passed the initial inspection record the installation date...

Page 13: ...room at an ambient temperature of 15 C to 25 C Battery life decreases by half for every 10 C above 25 C IMPORTANT Maximum battery life is obtained by placing the battery in a room at an ambient temper...

Page 14: ...anel Breaker Size Input Output Voltage Current Voltage Current 1000VA 700W 1000VA 110 50 60 15A 80 138Vac 12A max 120V 8 3A 1000VA 700W 1000VA 220 50 60 15A 160 276Vac 6A max 208 220 4 8A 4 55A 1500VA...

Page 15: ...UPS system Cables have been provided with the battery package for connection to the UPS system The 1000VA and 1500VA unit both use 36VDC battery systems A minimal battery system uses three 3 12VDC nom...

Page 16: ...s should be observed when working on batteries Remove watches rings and other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batt...

Page 17: ...FF button located on the front panel for at least three seconds The UPS should now start its self test testing the internal functions main synchronization and inverter startup After a successful test...

Page 18: ...O P VOLT V Shows Output AC voltage O P FREQ Hz Shows Output Frequency I P VOLT V Shows Input AC Voltage I P FREQ Hz Shows Input Frequency BAT VOLT V Shows Battery Voltage O P Load Shows of Maximum Rat...

Page 19: ...ction d Push the FUNC button to choose other function e Push the ENTER button to enable your function f Push the ENTER button to confirm and enable the selected function g If nothing has been pressed...

Page 20: ...ther confirm or save your selection Other options are saved and started automatically See Table 6 5 1 for further details 6 If no buttons are pressed for 10 seconds the UPS shall exit the configuratio...

Page 21: ...o bypass when unsynchronized Enable Disable Disable HE Mode Setting HE Mode Set Select if UPS runs in efficiency optimizer mode ON OFF OFF Frequency Conversion Freq Conv Setting Allows the UPS to outp...

Page 22: ...charge level of the batteries will be maintained automatically Under normal operating conditions the supplied batteries are expected to last approximately five 5 years or 200 discharges from date of...

Page 23: ...nstallation If used in conjunction with a status module the status module will have to be disconnected from the UPS Other advanced power protection solutions such as SNMP are provided by your dealer 1...

Page 24: ...n the USA at all times Using cables of improper size may damage your equipment and cause fire hazards Ground the UPS and the load equipment to a common point to prevent looping 1 Batteries should be i...

Page 25: ...ement product that uses multiple open standards such as Telnet HTTP and SNMP to provide full management of supported devices The SNMP Adapter is designed to connect directly to the network and allow f...

Page 26: ...1 second Output signal pin assignment Fault Pin 1 2 3 On Battery Pin 4 5 6 Battery Low Pin 7 8 On Bypass Pin 9 10 On Inverter Pin 11 12 M0301_N_Series_DM_Manual V1 4 2012 06 12 20 Dry Contact Capacity...

Page 27: ...er Charge Constant Beep Batteries are over charged Turn off protected loads Turn off UPS and call local dealer Low Battery 2 beeps every 5 seconds The unit is operating on Battery Power and will shutd...

Page 28: ...YES Via No 30 to 60 C Extended r Common LCD LED Status Depends Auto Self test Temperat Battery Bank 4 1 125 for 1 Sealed Lead Acid Mainte CONFORMANCE PROTECTION BATTERY External OUTPUT GENERAL INPUT...

Page 29: ...775 Email sales alwayson com Website www alwayson com 13 2 QA Warranty Questions Always On UPS Systems Inc Bldg 1 150 Campion Road Kelowna BC Canada V1X 7S8 Phone 250 491 9777 Ext 209 Fax 250 491 9775...

Reviews: