SPECIFICATIONS 

MODEL 

P.O.S. Pro 600 

INPUT 

Capacity 600VA 

Voltage 

120V, 220V +/-25% 

Frequency 

50 or 60Hz +/-10% (auto sensing) 

OUTPUT 

Voltage (on battery) 

Simulated sine wave at Line Input +/-5% 

Frequency (on battery) 

50 or 60Hz +/- 1Hz 

DC Output 

24V/1.5A (24VDC Printer cord) 

Auto Voltage Regulation 
AVR 

±

13% of nominal (120V) 

Transfer Time 

2/4 milliseconds, including detection time 

PROTECTION and 
FILTERING 

Spike Protection 

480 joules, 2ms 

Overload Protection 

UPS automatic shutdown if overload exceeds 110% of 

nominal for 60 second or 130% for 3 seconds. 

Unit Input 

Fuse or circuit breaker for overload & short circuit 

protection 

Short Circuit 

UPS output cut off immediately or input fuse protection 

BATTERY 

Type 

Maintenance-free, Sealed Lead Acid 

Typical Recharge Time 

6 hours (to 90% of full capacity) 

Protection 

Automatic self-test & discharge protection, replace 

battery indicator 

Back-up Time 

20 - 30 minutes (depending on load) 

PHYSICAL 

Net Weight kg(lbs) 

6.8 (15 lbs.) 

Shipping Weight kg(lbs)

7.3 (16 lbs.) 

Dimension (mm)WxDxH

97x320x135 (3.8” X 12.5” X 5.3”) 

Input Inlet 

Nema 5-15P power inlet 

Output 

 5 X Nema 5-15R (3 output power, 2 surge protection 

only) +1 DC printer power connector 

ALARM 

Battery Back-Up 

Slow beeping sound (about 0.47Hz) 

Battery Low 

Rapid beeping sound (about 1.824Hz) 

Overload 

Continuous beeping sound 

CONFORMANCE 

Safety 

cUL UL1778, CSA C22.2 and FCC Class B 

Surge 

IEEE C62.41 CAT. A 

ENVIRONMENT 

Ambient Operation 

6,000 meters max. elevation, 0-95% humidity non-

condensing 0-40

°

Audible noise 

<40dBA (1 meter from surface) 

Summary of Contents for P.O.S. Pro 600VA

Page 1: ...OS_Pro_Manual V1 0 2012 06 12 P O S Pro Series Single Phase Input Single Phase Output Uninterruptible Power Supply P O S Pro 600VA Line Interactive UPS PWM 600VA with Integrated DC Power Supply User s...

Page 2: ...ful to the skin and eyes It may be toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on or with th...

Page 3: ...ions below 1 Do not remove the UPS cover unless authorized by factory Removing the cover will void the warranty 2 The UPS can only be connected to a 2 pole 3 wire plug 3 Do not install the UPS in an e...

Page 4: ...n the UPS 5 4 2 Switching Off the UPS 5 4 3 Self Test 5 4 4 Silence the Alarm 5 4 5 Cold Start 5 4 6 Shutdown Mode 5 4 7 Green Function 6 4 8 Back Up Slow Alarm 6 4 9 Low Battery Rapid Alarm 6 4 10 Ov...

Page 5: ...w voltage state Also included with our UPS system is a cyclic self testing function to verify both the operation of the UPS and the condition of the battery The integrated DC power supply and multiple...

Page 6: ...the loads and flash rapidly when the battery requires replacement 2 ON OFF TEST SILENCE button Press and hold the button for more than 3 seconds to turn the UPS ON or OFF press and hold the button les...

Page 7: ...ry The UPS charges its battery whenever the UPS is in LINE mode For best results charge the battery for 4 hours initially before connecting the load 3 5 Connecting the Loads Plug the loads into the ou...

Page 8: ...onditions Store the UPS covered and upright in a cool dry location with its battery fully charged Before storing charge the UPS for at least eight 8 hours Remove any accessories in the accessory slot...

Page 9: ...the self test the UPS operates in back up mode During the self test the UPS briefly operates the loads with battery power the LED flashes every 2 seconds If the UPS passes the self test it returns to...

Page 10: ...normal operation Press the On Off Test Silence Button during back up mode to silence the beeping 4 9 Low Battery Rapid Alarm In back up mode when the battery energy runs low the UPS beeps rapidly unti...

Page 11: ...ith the bottom turn the entire unit right side up 8 Carefully lift top cover off and place it to the side The connecting wires and electronics will be exposed Be careful not to touch any inner compone...

Page 12: ...ile AC power is connected yet starts after pushing power on off switch Breaker at back panel open No AC input UPS AC detecting circuit fail Switch breaker Check AC power Call for service UPS goes into...

Page 13: ...cut off immediately or input fuse protection BATTERY Type Maintenance free Sealed Lead Acid Typical Recharge Time 6 hours to 90 of full capacity Protection Automatic self test discharge protection re...

Page 14: ...ge without prior notice to reflect upgrades and improvements in technology 7 1 DC Power Supply Specifications Output Voltage 24VDC Regulation 1 Ripple and Noise 150mV Rated Current 1 5A Continuous 2A...

Page 15: ...s alwayson com Website www alwayson com 8 2 QA Warranty Questions Always On UPS Systems Inc Bldg 1 150 Campion Road Kelowna BC Canada V1X 7S8 Phone 250 491 9777 Ext 209 Fax 250 491 9775 Email qa alway...

Reviews: