background image

SS-AMVM96

 www.amana-hac.com 

5

4 www.amana-hac.com 

SS-AMVM96

P

roduCt

 s

PeCiFiCAtions

P

roduCt

 s

PeCiFiCAtions

AMVM96 d

iMensions

M

iniMuM

 C

leArAnCes

 

to

 C

oMbustible

 M

AteriAls

Position

Sides

Rear

Front

Bottom

Flue

Top

Upflow

0”

0”

3”

C

0”

1”

Horizontal

6”

0”

3”

C

0”

6”

C = If placed on combustible floor, the floor MUST be wood ONLY.
Notes:

•  For servicing or cleaning, a 24” front clearance is required.
•  Unit connections (electrical, flue and drain) may necessitate greater clearances than the minimum clearances listed above.
•  In all cases, accessibility clearance must take precedence over clearances from the enclosure where accessibility clearances are greater.

28¾

19⅞

RIGHT SIDE VIEW

LEFT SIDE VIEW

22 ¹/₁₆ 

FOLDED FLANGES

23 ⁹/₁₆

UNFOLDED FLANGES

FRONT VIEW

FOLDED FLANGES

UNFOLDED FLANGES

D

E

11¾

30¼

¾

¾

30¼

11¾

32¹³/₁₆

19³/₁₆

24⁹/₁₆

2¹¹/₁₆

2¹/₁₆

19³/₁₆

¾

21¼

2⅝

7⅜

1⅝

4⅛

16⅝

2⅝

27⅛

6⅛

Model

W

D

H

A

B

C

D

E

AMVM960603BX

17½”

28¾"

40¾"

17½”

16"

13⅛"

12⅛"

13⅝"

AMVM960805CX

21"

28¾"

40¾"

21"

19½”

16⅛"

16"

17½”

AMVM961005DX

24½”

28¾"

40¾"

24½”

23"

20⅝"

19⅜"

20⅞"

AMVM961155DX

24½”

28¾"

40¾"

24½”

23"

20⅝"

19⅜"

20⅞"

Notes:

•  Installer must supply one or two PVC pipes: one for combustion air (optional) and one for the flue outlet (required). Vent pipe must be either 2” 

or 3” in diameter, depending upon furnace input, number of elbows, length of run and installation (1 or 2 pipes). The optional Combustion Air 
Pipe is dependent on installation/code requirements and must be 2” or 3” diameter PVC.

•  Line voltage wiring can enter through the right or left side of the furnace. Low-voltage wiring can enter through the right or left side of furnace.
•  Conversion kits for high-altitude natural gas operation are available. Contact your Goodman distributor or dealer for details.
•  Installer must supply following gas line fittings, according to which entrance is used: 

Left—Two 90º elbows, one close nipple, straight pipe 
Right—Straight pipe to reach gas valve

•  For bottom return: Failure to unfold flanges may reduce airflow by up to 18%. This could result in performance and noise issues.

Summary of Contents for ACMV960604CX

Page 1: ...et air circulation Auto Comfort and enhanced dehumidification modes available Variable speed induced draft blower All models comply with California NOx emissions standards Cabinet Features Fully insulated heavy gauge steel cabinet with durable baked enamel finish Foil faced insulation lines the heat exchanger section Designed for multi position installation AMVM96 upflow horizontal left or right A...

Page 2: ... Gas H High Airflow X Low NOx K Dedicated Upflow M Upflow Horizontal Cabinet Width A 14 Descrip6on Motor B 17 V Two Stage Variable speed C 21 H Two Stage Mul speed D 24 S Single Stage Mul speed E Two Stage High Efficiency Maximum CFM 0 5 ESP 3 1200 SystemType 4 1600 C ComfortNet Communica ng System 5 2000 M Modula ng Furnace MBTU h 045 45 000 AFUE 060 60 000 96 96 9 90 080 80 000 95 95 8 80 100 100 000...

Page 3: ... 15 0 15 0 15 0 15 0 15 0 15 0 Ship Weight lbs 135 145 170 170 139 165 Natural Gas BTU h DOE AFUE based upon Isolated Combustion System ICS Installer must supply one or two PVC pipes one for combustion air optional and one for the flue outlet required Vent pipe must be either 2 or 3 in diameter depending upon furnace input number of elbows length of run and installation 1 or 2 pipes The optional C...

Page 4: ...21 28 40 21 19 16 16 17 AMVM961005DX 24 28 40 24 23 20 19 20 AMVM961155DX 24 28 40 24 23 20 19 20 Notes Installer must supply one or two PVC pipes one for combustion air optional and one for the flue outlet required Vent pipe must be either 2 or 3 in diameter depending upon furnace input number of elbows length of run and installation 1 or 2 pipes The optional Combustion Air Pipe is dependent on i...

Page 5: ...DE DRAIN LINE HOLES DRAIN TRAP C L 28 5 16 11 1 2 9 13 16 15 1 2 UNFOLDED FLANGES 1 3 4 18 5 8 2 5 8 HIGH VOLTAGE ELECTRICAL HOLE 20 5 32 AIR DISCHARGE LEFT SIDE VIEW 3 4 2 1 16 2 UNFOLDED FLANGES DISCHARGE CONDENSATE DRAIN TRAP w 3 4 PVC DISCHARGE RIGHT OR LEFT SIDE 40 8 1 4 FOLDED FLANGES RETURN 3 4 HIGH VOLTAGE ELECTRICAL HOLE LOW VOLTAGE ELECTRICAL HOLE RIGHT SIDE DRAIN LINE HOLES ALTERNATE VE...

Page 6: ... w c ESP AMVM961005DX AMVM961155DX High Stage Low Stage High Stage Low Stage Tap Adjust CFM Tap Adjust CFM Tap Adjust CFM Tap Adjust CFM A Minus 711 A Minus 459 A Minus 711 A Minus 459 Normal 790 Normal 510 Normal 790 Normal 510 Plus 869 Plus 561 Plus 869 Plus 561 B Minus 990 B Minus 639 B Minus 990 B Minus 639 Normal 1100 Normal 710 Normal 1100 Normal 710 Plus 1210 Plus 781 Plus 1210 Plus 781 C M...

Page 7: ...1155DX Rise Range 35 65 F Adjust Tap CFM Rise F Adjust Tap CFM Rise F Minus 1 629 54 Minus 1 629 62 Normal 1 810 49 Normal 1 810 56 Plus 1 991 44 Plus 1 991 51 Minus 1 665 53 Minus 1 665 60 Normal 1 850 48 Normal 1 850 54 Plus 2 035 43 Plus 2 035 49 Minus 1 701 52 Minus 1 701 59 Normal 1 890 47 Normal 1 890 53 Plus 2 079 43 Plus 2 079 48 Minus 1 746 51 Minus 1 746 58 Normal 1 940 46 Normal 1 940 5...

Page 8: ...is desirable Operation is recommended below 5 w c ESP in heating mode Operating CFM between 5 and 8 w c is tabulated for cooling purposes only ACVM960805DX High or Single Stage Low Stage Cooling Speed Tap Adjust Tap CFM Cooling Speed Tap Adjust Tap CFM A Minus 810 A Minus 477 Normal 900 Normal 530 Plus 990 Plus 583 B Minus 990 B Minus 657 Normal 1100 Normal 730 Plus 1210 Plus 803 C Minus 1287 C Mi...

Page 9: ...881 38 Minus 1 314 40 Minus 1 620 44 Normal 1 460 36 Normal 1 800 39 Plus 1 606 33 Plus 1 980 36 Minus 1 431 37 Minus 1 719 41 Normal 1 590 33 Normal 1 910 37 Plus 1 749 30 Plus 2 101 34 1 5 w c ESP 1 5 w c ESP Notes All furnaces ship as high speed for cooling Installer must adjust blower speed as needed For most jobs about 400 CFM per ton when cooling is desirable Operation is recommended below 5...

Page 10: ...100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 2000 2200 2400 CFM FORMULAS BTU OUTPUT CFM x 1 08 x RISE RISE BTU OUTPUT 1 08 CFM 800 Output BTU h x 1 000 Formulas BTU h Output CFM x 1 08 x Rise Rise BTU H Output CFM x 1 08 Temperature Rise ...

Page 11: ... ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE USED WHEN SERVICING 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS BK BLACK PU PURPLE YL YELLOW BL BLUE WH WHITE BR BROWN PK PINK COLOR CODES PLUG CONNECTION INTEGRATED CONTROL INTERNAL TO HI VOLTAGE FIELD HI VOLTAGE 115V LOW VOLTAGE 24V LOW VOLTAGE FIELD PROT DEVICE SWITCH PRESSURE SWITCH TE...

Page 12: ...ersion Kits LPKM0D080UF LPKM0D100UF LPKM0D115UF LPKM0D060CF LPKM0D080CF EFR01 External Filter Rack DCVK 20 Horizontal Vertical Concentric Vent Kit 2 DCVK 30 Horizontal Vertical Concentric Vent Kit 3 CFB21 Downflow Floor Base CFB24 Downflow Floor Base 0170K00000S Flush mount vent kit Notes Indicates available for this model For installation in Canada gas furnaces are certified only to 4 500 Thermos...

Reviews: