background image

11

Once  the  HUM  jumper  is  cut  at  the  ECM  motor  interface 

module, the dehumidify function is enabled during a com-

bination call for cooling (T-Stat) and dehumidification (DE

-

HUMStat).

5

Y1

1

SW

IT

CH

8

7

6

5

4

3

2

1

W1

OT1

OT2

HUM

PJ6

PJ2

PJ4

W2

CR9

HEATER

W1

W2

C

R

24 VAC

CR8 
CR7 
CR6

J3

CR5

C2

4

1

J2

CR2

DS

1

CR1

R5

O

FF

O

N

D

IP

E

F1 

3A

M P

KESU

CR

1 0

R3

PN. PCB001 02

(CFM)

CONFIGURATION.

DIP SWITCH

FOR PROPER

TO MANUAL

PLEASE REFER

R1

R2

ED

W2

O

COM

YCON

R

HEATPUMP

CONDENSER

OUTDOOR

THERMOSTATS

HUMIDISTAT

HUM

Y/Y2

G

Y1

R

C

OT2

OT1

OTC

O

W/W2

E\W1

J1

HUM

PJ6

EMC Blower Motor Interface Module

Refer to the unit wiring diagram for electrical connections. 

When installed, the unit must be electrically grounded in ac-

cordance with local codes or in the absence of local codes, 

with the National Electrical Code, ANSI/NFPA No. 70, and/or 

the CSA C22.1 Electrical Code. Ensure low voltage connec-

tions are waterproof.

WARNING

To avoid the risk of electrical ground shock, wiring to the 

unit must be polarized and grounded.

CAUTION

To avoid property damage or personal injury due to fire, use 

only copper conductors.

WARNING

To prevent improper and dangerous operation due to 

wiring errors, label all wires prior to disconnection when 

servicing controls. Verify proper operation after servicing.

For unit protection, use a fuse or 

HACR

 circuit breaker that 

is in excess of the circuit ampacity, but less than or equal 

to the maximum overcurrent protection device. DO NOT 

EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE 

SHOWN ON UNIT DATA PLATE.

All line voltage connections must be made through weath-

erproof fittings. All exterior power supply and ground wiring 

must be in approved weatherproof conduit. Low voltage 

wiring from the unit control panel to the thermostat requires 

coded cable. See below for ground level and rooftop wiring.

Electrical Power Directly To Junction Box

Electrical Power Routed Through Bottom of Unit

Note:Junction box location

shown is optional and is

for illustration purposes only.

JUNCTION BOX

Electrical Power Routed Through Bottom of Unit 

Typical Electrical Wiring Unit Voltage

High Voltage Wiring

Rated Voltage

Minimum Supply 

Voltage

Minimum Supply 

Voltage

208/230V

197

253

The unit transformer is factory connected for 230V opera-

tion. If the unit is to operate on 208V, reconnect the trans-

former primary lead as shown on the unit wiring diagram. 

The induced draft blower on some models is equipped with 

a low speed 230V lead (blue) and a low speed 208V lead 

(black). If equipped, connect the induced draft blower low 

speed 208V lead (black) in place of the low speed 230V lead 

(blue). Place the unused 230V lead on the “PARK” terminal 

located on ignition control.

Branch Circuit 

Ampacity

15 20 25 30 35 40 45 50

SUPPLY WIRE 

LENGTH - FEET

200

6

4

4

4

3

3

2

2

150

8

6

6

4

4

4

3

3

100

10

8

8

6

6

6

4

4

50

14 12 10 10

8

8

6

6

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: