background image

18

3.  Refer to the superheat table provided for 

proper system superheat. Add charge to lower 

superheat or recover charge to raise superheat. 

Superheat Formula = Suct. Line Temp. - Sat. Suct. 

Temp.

Superheat Adjustment

NOTE: 

The expansion valve will not need adjustment for 

most applications. Ensure system superheat is set within 

range listed on chart below.
To adjust superheat, unscrew the cover from the expansion 

valve, locate the adjustment screw, and turn it clockwise (in) 

to increase superheat or counterclockwise (out) to decrease 

superheat. Replace adjustment cap. Wait a minimum of 10 

minutes between adjustments to allow time for the TXV and 

pressures to stabilize.

65

70

75

80

85

100

-

-

-

10

10

95

-

-

10

10

10

90

-

-

12

15

18

85

-

10

13

17

20

80

-

10

15

21

26

75

10

13

17

25

29

70

10

17

20

28

32

65

13

19

26

32

35

60

17

25

30

33

37

Ambient 

Condenser Inlet 

Temp (°F Drybulb)

Return Air Temp. (°F Drybulb)

Checking Subcooling

Refrigerant liquid is considered subcooled when its tempera-

ture is lower than the saturation temperature corresponding 

to its pressure. The degree of subcooling equals the degrees 

of temperature decrease below the saturation temperature 

at the existing pressure.

1.  Attach an accurate thermometer or preferably a 

thermocouple type temperature tester to the liquid 

line close to the pressure switch.

2.  Install a high side pressure gauge on the liquid access 

fitting.

3.  Record the gauge pressure and the temperature of 

the line.

4. 

The difference between the thermometer reading and 

pressure to temperature conversion is the amount of 

subcooling.

Subcooling Formula = Sat. Liquid Temp. - Liquid 

Line Temp.

EXAMPLE:

a. Liquid Line Pressure = 417

b. Corresponding Temp. °F. = 120°

c. Thermometer on Liquid line = 109°F.

To obtain the amount of subcooling, subtract 109°F from 

120°F. The difference is 11° subcooling. See the specification 

sheet or technical information manual for the design subcool-

ing range for your unit.

Cooling Operation

NOTE:

 Mechanical cooling cannot be reliably provided at 

ambient temperatures below 50° F. 

1.  Turn on the electrical power supply to the unit. 

2. Place the room thermostat selector switch in the 

COOL position (or AUTO if available, and if automatic 

changeover from cooling to heating is desired).

3.  Set the room thermostat to the desired temperature. 

TROUBLESHOOTING

Ignition Control Error Codes

The following presents probable causes of questionable unit 

operation. Refer to 

Diagnostic Indicator Chart 

 for an inter-

pretation of the signal and to this section for an explanation.
Remove the control box access panel and note the num-

ber of diagnostic LED flashes. Refer to 

Diagnostic Indicator 

Chart 

for an interpretation of the signal and to this section for 

an explanation.

Fault Recall

The ignition control is equipped with a momentary push-but-

ton switch that can be used to display on the diagnostic LED 

the last five faults detected by the control. The control must 

be in Standby Mode (no thermostat inputs) to use the fea-

ture. Depress the push-button switch for approximately 2 

seconds. 

NOTE: Do not hold for longer than 4 seconds. 

Holding the button for 4 seconds or higher will erase the 

memory! 

Release the switch when the LED is turned off. 

The diagnostic LED will then display the flash codes associ

-

ated with the last five detected faults. The order of display is 

the most recent fault to the least recent fault.

Abnormal Operation - Heating

Internal Control Failure

If the integrated ignition control in this unit encounters an 

internal fault, it will go into a “hard” lockout and turn off the 

diagnostic LED. If diagnostic LED indicates an internal fault, 

check power supply to unit for proper voltage, check all fus-

es, circuit breakers and wiring. Disconnect electric power 

for five seconds. If LED remains off after restoring power, 

replace control.

External Lockout

An external lockout occurs if the integrated ignition control 

determines that a measurable combustion cannot be estab-

lished within three (3) consecutive ignition attempts.  If flame 

is not established within the seven (7) second trial for igni-

tion, the gas valve is de-energized, 30 second inter-purge 

cycle is completed, and ignition is re-attempted.  The control 

will repeat this routine three times if a measurable combus-

tion is not established. The control will then shut off the in

-

duced draft blower and go into a lockout state.

If flame is established but lost, the control will energize the 

circulator blower at the heat speed and then begin a new 

ignition sequence. If flame is established then lost on subse

-

quent attempts, the control will recycle the ignition sequence.

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: