background image

5

GENERAL INFORMATION

WARNING

To prevent the risk of property damage, personal injury, 

or death due to fire, explosions, smoke, soot, condensation, 

electric shock or carbon monoxide, thus unit must be 

properly installed repaired, operated, and maintained.

This  unit  is  approved  for  outdoor  installation  ONLY. 

Rated performance is achieved after 20 hours of operation. 

Rated performance is delivered at the specified airflow. See 

outdoor unit specification sheet for split system models or 

product specification sheet for packaged and light commer

-

cial models. Specification sheets can be found at 

www.ama-

na-hac.com

 for Amana

®

 brand products. Within the website, 

please select the residential or commercial products menu 

and then select the submenu for the type of product to be 

installed, such as air conditioners or heat pumps, to access 

a list of product pages that each contain links to that model’s 

specification sheet.
To  assure  that  your  unit  operates  safely  and  efficiently,  it 

must be installed, operated, and maintained in accordance 

with these installation and operating instructions, all local 

building codes and ordinances, or in their absence, with the 

latest edition of the National Fuel Gas Code NFPA 54/ANSI 

Z223.1 and National Standard of Canada CAN/CSA B149 

Installation Codes.
The heating and cooling capacities of the unit should be 

greater than or equal to the design heating and cooling loads 

of the area to be conditioned. The loads should be calculated 

by an approved method or in accordance with A.S.H.R.A.E. 

Guide or Manual J - Load Calculations published by the Air 

Conditioning Contractors of America. 

B10259-216

CO can cause serious illness including permanent brain

damage or death.

Advertencia especial para la instalación de calentadores ó manejadoras 

de aire en áreas cerradas como estacionamientos ó cuartos de servicio.

B10259-216

El monóxido de carbono puede causar enfermedades severas 

como  daño cerebral permanente ó muerte.

Las emisiones de monóxido de carbono pueden circular a través

del aparato cuando se opera en cualquier modo. 

B10259-216

RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE

Le monoxyde de 

des 

carbone peut causer des maladies graves telles que

dommages permanents au cerveau et meme la mort.

Cette ventilation est nécessaire pour éviter le danger d'intoxication

au CO pouvant survenir si un appareil produisant du monoxyde 

de carbone continue de fonctionner au sein de la zone confinée.

Obtain from:

American National Standards Institute 

25 West 43rd Street, 4th Floor 

New York, NY 10036

Transportation Damage

Check the carton upon arrival for external damage. If dam-

age is found, a request for inspection by carrier agent should 

be made in writing immediately.
Carefully inspect the unit for damage including damage to 

the cabinetry. Any bolts or screws which may have loosened 

in transit must be re-tightened. In the event of damage, the 

receiver should:

1. Make notation on delivery receipt of any visible 

damage to shipment or container.

2.  Notify carrier promptly and request an inspection.

3. In case of concealed damage, carrier should be 

notified as soon as possible-preferably within 5 days.

4.  File the claim with the following supporting documents:

a. Original Bill of Lading, certified copy, or indemnity 

bond.

b. Original paid freight bill or indemnity in lieu thereof. 

c. Original invoice or certified copy thereof, showing 

trade and other discounts or reductions.

d. Copy of the inspection report issued by carrier 

representative at the time damage is reported to 

the carrier. The carrier is responsible for making 

prompt inspection of damage and for a thorough 

investigation of each claim. The distributor or 

manufacturer will not accept claims from dealers 

for transportation damage.

NOTE:

 When inspecting the unit for transportation damage, 

remove all packaging materials. Recycle or dispose  of the 

packaging material according to local codes.

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: