UNIT LOCATION

WARNING

To prevent possible equipment damage, property damage, 

personal injury or death, the following bullet points must 

be observed when installing this unit.

IMPORTANT NOTE: 

Remove wood shipping rails prior to 

installation of the unit.

All Installations:

• 

For proper flame pattern within the heat exchanger 

and proper condensate drainage, the unit must be 

mounted level.

•  The flue outlet hood must be at least 12 inches from 

any  opening  through  which  flue  gases  could  enter 

a building, and at least three feet above any forced 

air inlet located within ten feet. The economizer/

manual fresh air intake/motorized fresh air intake 

and combustion air inlet mounted on the unit are not 

affected by this restriction. 

•  To avoid possible corrosion of the heat exchanger, 

do not locate the unit in an area where the outdoor 

air (i.e. combustion air for the unit) will be frequently 

contaminated by compounds containing chlorine or 

fluorine. Common sources of such compounds include 

swimming pool chemicals and chlorine bleaches, paint 

stripper, adhesives, paints, varnishes, sealers, waxes 

(which are not yet dried) and solvents used during 

construction and remodeling. Various commercial and 

industrial processes may also be sources of chlorine/

fluorine compounds.  

• 

To avoid possible illness or death of the building 

occupants, do NOT locate outside air intake device 

(economizer, manual fresh air intake, motorized 

fresh air intake) too close to an exhaust outlet, gas 

vent termination, or plumbing vent outlet. For specific 

distances required, consult local codes.

• 

Allow minimum clearances from the enclosure for fire 

protection, proper operation, and service access (see 

appendix). These clearances must be permanently 

maintained.

• 

The combustion air inlet and flue outlet hoods on the 

unit must never be obstructed. If used, do not allow 

the economizer/manual fresh air damper/ motorized 

fresh air damper to become blocked by snow or debris. 

In some climates or locations, it may be necessary to 

elevate the unit to avoid these problems. 

• 

When the unit is heating, the temperature of the return 

air entering the unit must be between 50° F and 100° F.

• 

Units manufactured on or after May 1, 2017 are not 

permitted to be used in Canada for heating of buildings 

or structures under construction.

Ground Level Installations Only:

• 

When the unit is installed on the ground adjacent 

to the building, a level concrete (or equal) base is 

recommended. Prepare a base that is 3” larger than 

the package unit footprint and a minimum of 3” thick.

• 

The base should also be located where no runoff of 

water from higher ground can collect in the unit.

Outside Slab Installation

Rooftop Installations Only:

NOTE: 

To ensure proper condensate drainage, unit must be 

installed in a level position.

  To avoid possible property damage or personal injury, 

the  roof  must  have  sufficient  structural  strength  to 

carry the weight of the unit(s) and snow or water 

loads as required by local codes. Consult a structural 

engineer to determine the weight capabilities of the 

roof.

  The unit may be installed directly on wood floors or on 

Class A, Class B, or Class C roof covering material.

  To avoid possible personal injury, a safe, flat surface 

for service personnel should be provided.

Rooftop Installation

Roof Curb Installations Only:

• 

Sufficient structural support must be determined prior 

to locating and mounting the curb and package unit.

• 

Ductwork must be constructed using industry 

guidelines. The duct work must be placed into the 

roof curb before mounting the package unit.

• 

Curb  insulation,  cant  strips,  flashing  and  general 

roofing material are furnished by the contractor.

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: