background image

19

The diagnostic fault code is 1 flash for a lockout due to failed 

ignition attempts. The integrated control will automatically 

reset after one hour, or it can be reset by removing the ther-

mostat signal or disconnecting the electrical power supply 

for over five seconds. If the diagnostic red LED indicates an 

external lockout, perform the following checks:

 • 

Check the supply and manifold pressures

 • 

Check the gas orifices for debris

 • 

Check gas valve for proper operation

 • 

Check flame sensor

A drop in flame signal can be caused by nearly 

invisible coating on the sensor.  Remove the sensor 

and carefully clean with steel wool.

 • 

Auxiliary/Secondary Limit

 

A dirty filter, excessive duct static, insufficient air 

flow, a faulty limit, or a failed circulator blower can 

cause this limit to open. Check filters, total external 

duct static, circulator blower motor, blower motor 

speed tap (see wiring diagram), and limit. An 

interruption in electrical power during a heating 

cycle may also cause the auxiliary limit to open.  

The automatic reset secondary limit is located on 

top of the circulator blower assembly.

 • 

Rollout Limit

 

If the burner flames are not properly drawn into 

the heat exchanger, the flame rollout protection 

device will open. Possible causes are restricted 

or blocked flue passages, blocked or cracked 

heat exchanger, a failed induced draft blower, or 

insufficient combustion air. The rollout protection 

device is a manual reset limit located on the burner 

bracket. The cause of the flame rollout must be 

determined and corrected before resetting the limit.

 • 

Check wiring

Check wiring for opens/shorts and miswiring.

IMPORTANT  NOTE:

 If you have to frequently reset your 

gas/electric package unit, it means that a problem exists that 

should be corrected.  Contact a qualified servicer for further 

information.

Pressure Switch Stuck Open

A pressure switch stuck open can be caused by a faulty 

pressure switch, faulty wiring, a disconnected or damaged 

hose, a blocked or restricted flue, a blocked pressure tap or 

a faulty induced draft blower.
If the control senses an open pressure switch during the pre-

purge cycle, the induced draft blower only will be energized.  

If the pressure switch opens after ignition has begun the gas 

valve  is  de-energized,  the  circulator  blower  heat  off  cycle 

begins, and the induced draft blower remains on. The diag-

nostic LED (red) code is two (2) flashes.

Pressure Switch Stuck Closed

A stuck closed pressure switch can be caused by a faulty pres-

sure switch or faulty wiring. If the control encounters a pressure 

switch stuck closed, the induced draft blower remains off. The 

diagnostic red LED code for this fault is three (3) flashes.

Primary Limit

A primary limit will open due to excessive supply air tem-

peratures.  This  can  be  caused  by  a  dirty  filter,  excessive 

duct static, insufficient air flow, or a faulty limit. Check filters, 

total external duct static, blower motor, blower motor speed 

tap (see wiring diagram), and limit. This limit will automati-

cally reset once the temperature falls below a preset level.
If a limit switch opens, the gas valve is immediately de-en-

ergized, the induced draft and air circulating blowers are en-

ergized. The induced draft  and air circulator blowers remain 

energized until the limit switch re-closes. The diagnostic 

LED (red) code for an open limit is four (4) flashes.

NOTE: 

If  the  primary  limit  opens  five  (5)  times  within  the 

same call for heat, the ignition control will lock out for one 

(1) hour with the air circulating blower energized at high heat 

speed. The diagnostic LED (red) code for this condition is 

seven (7) flashes.

Flame Detected with Gas Valve Closed

If  flame  is  detected  with  the  gas  valve  de-energized,  the 

combustion and air circulator blowers are energized. The di-

agnostic fault code is five (5) flashes (red LED) for this con

-

dition. The flame diagnostic LED (amber) will flash (2) times 

to indicate this condition. The control can be reset by remov-

ing the power supply to the unit or it will automatically reset 

after one hour. Miswiring is the probable cause for this fault.

Low Flame Signal

Under some conditions, the fuel or air supply can create a 

nearly  invisible  coating  on  the  flame  sensor.  This  coating 

acts as an insulator causing a drop in the flame signal. If the 

flame signal drops below a predetermined value, the ignition 

control will display an error code of (1) flash on the amber 

diagnostic LED. The unit will continue to operate until the 

control can no longer detect flame.

Abnormal Operation - Cooling

Short Cycle Compressor Delay

The automatic ignition control has a built-in feature that pre-

vents damage to the compressor in short cycling situations.  

In the event of intermittent power losses or intermittent ther-

mostat operation, the ignition control will delay output to the 

compressor contactor for three minutes from the time power 

is restored or thermostat call for cooling is restored. (Com-

pressor is off a total of three minutes). The diagnostic red 

LED will flash six (6) times to indicate the compressor con

-

tactor output is being delayed.

NOTE:

 Some electronic thermostats also have a built-in 

compressor short cycle timer that may be longer than the 

three minute delay given above. If you are using an elec-

tronic thermostat and the compressor has not started after 

three minutes, wait an additional five minutes to allow the 

thermostat to complete its short cycle delay time.

High Pressure Switch/Loss of Charge Switch

Some models include a high pressure cutout switch and/

or a loss of charge cutout switch. The high pressure cutout 

switch protects the refrigeration system from excessive op-

erating pressures. The loss of charge cutout switch protects 

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: