background image

7

Roof Curb Installation

RIGGING DETAILS

WARNING

To prevent property damage, the unit should remain in an 

upright position during all rigging and moving operations. To 

facilitate lifting and moving when a crane is used, place the 

unit in an adequate cable sling. 

IMPORTANT  NOTE:

 If using bottom discharge with roof 

curb, ductwork should be attached to the curb prior to install-

ing the unit. Ductwork dimensions are shown in roof curb 

installation instructions.
Refer to the Roof Curb Installation Instructions for proper 

curb installation. Curbing must be installed in compliance 

with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging 

unit, center of gravity will cause condenser end to be lower 

than supply air end.

Rigging

GAS PIPING

IMPORTANT NOTE

: This unit is factory set to operate on natural 

gas at the altitudes shown on the rating plate. 

WARNING

To prevent property damage, personal injury or death when 

using propane gas alone or at higher altitudes, obtain and 

install the proper conversion kit(s). Failure to do so can 

result in unsatisfactory operation and/or equipment damage. 

High altitude kits are for the U.S. Installations only and are 

not approved for the use in Canada.

The rating plate is stamped with the model number, type of 

gas and gas input rating. Make sure the unit is equipped to 

operate on the type of gas available. Conversion to LP gas is 

permitted with the use of a factory authorized conversion kit. 

Contact your distributor or refer to the specification sheet for 

your model for a listing of approved LP gas conversion kit(s). 

Refer to the Installation Manual  provided with the LP kit for 

conversion from natural gas to propane gas.

Natural

Min. 5.0" W.C., Max. 10.0" W.C.

Propane

Min. 11.0" W.C., Max. 13.0" W.C.

INLET GAS PRESSURE

Inlet Gas Pressure Must Be Within the Minimum and  Maxi-

mum Value Shown in Table Above.

The minimum supply pressure should not vary from that 

shown in the Inlet Gas Pressure table because this could 

prevent the unit from having dependable ignition. In addition, 

gas input to the burners must not exceed the rated input 

shown on the rating plate. Overfiring of the unit could result 

in premature heat exchanger failure.

High Altitude Derate  (U.S. Installations Only)

Installation of this furnace at altitudes above 2000 ft (610 m) 

shall be made in accordance with the Listed High Altitude 

Conversion Kit available with this furnace. 

D’installation  de  ce  générateur  de  chaleur  à  des  altitudes 

supérieures à 2000 pi (610 m) doit être effectuée conformé

-

ment aux instructions accompagnant la trousse de conver-
sion pour haute altitude fournie avec cet appareil.

IMPORTANT NOTE: 

The gas/electric units naturally derate 

with  altitude.  Do  not  attempt  to  increase  the  fir ing  rate  by 

changing orifices or increasing the manifold pressure. This 

can cause poor combustion and equipment failure. At all alti-

tudes, the manifold pressure must be within 0.3 inches W.C. 

of that listed on the nameplate for the fuel used. At all alti-

tudes and with either fuel, the air tempera ture rise must be 

within the range listed on the unit nameplate. Contact your 

distributor or refer to the specification sheet for your model 

for listing of approved high altitude conversion kit(s). Refer 

to the Installation Manual provided with the high altitude kit 

for altitude adjustments.

NOTE:

 No changes are required up to 2,000 feet.  Use the 

appropriate high altitude kit above 2,000 feet.

Summary of Contents for APG 16 M Series

Page 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Page 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Page 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Page 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Page 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Page 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Page 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Page 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Page 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Page 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Page 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Page 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Page 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Page 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Page 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Page 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Page 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Page 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Page 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Page 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Page 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Page 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Page 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Page 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Page 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Page 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Page 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Page 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Page 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Page 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Reviews: