Component Specifications
October 2000
RT1300056 Rev.1
3
Illustration
Component
Test Procedure
B2150504
Drier
Drier must be changed every time the system is opened for testing or
compressor replacement.
Desiccant (20) 8 x 12 4AXH - 7 M>S> -Grams
12049801
Heater, evaporator
Volt
Wattage
Resistance
115 VAC
450
5% watts
29
5% ohms
12501001
Motor, auger
Volt
Rotation (facing end opposite
shaft)
RPM (no load)
Watt
Bimetal cut-out
Opens
Closes
115VAC, 60 Hz
Power to blue and white leads is clockwise
Power to white and orange leads is
counterclockwise
17 ±3 RPM
120 ±20 watts
194°F ±9°
149°F ±9°
10884501
Motor, condenser
Volt
Rotation (facing end opposite
shaft)
RPM
Watt
Current
Resistance
115 VAC, 60 Hz
Clockwise
1300 RPM
10.0 watts
0.15 amps
220
10% ohms
10513803
Motor, evaporator fan
(Used on all units with serial No. prefix
0006 through June 2000. Diameter of fan
blade on these units is 5.25
)
Volt
Rotation (facing end opposite
shaft)
RPM
Watt
115 VAC, 60 Hz
Clockwise
2500 RPM
12
15% watts
10449505
Motor, evaporator fan
(Used on all units with serial No. prefix
0007, starting July 2000. Diameter of fan
blade on these units is 3.85
)
Volts
Rotation (facing end opposite
shaft)
Speed
Watts
115 VAC, 60 Hz
Clockwise
2900 RPM
9.1 ±15% watts
10377015
Overload, 4TM
Volt
Ult. Trip amps @ 158°F (70°C)
Close temperature
Open temperature
Short time trip (seconds)
Short time trip (amps @77°F
(25°C))
115 VAC
3.51 amps
142°F (61°C ±9°)
257°F (125°C ±5°)
10 seconds ±5
14 amps
!
WARNING
To avoid risk of electrical shock that can cause death or severe personal injury, disconnect unit from power before
servicing unless tests require power. Discharge capacitors through a 10,000-ohm resistor before handling. Wires
removed during disassembly must be replaced on correct terminals to ensure proper grounding and polarization.