SERVICING
62
Air Handler Display (B*)
LED Display
Menu Description
FCL
View 6 most recent fault codes and Clear Fault Codes if desired
(outdoor communicating units)
t gt
Menu is enabled if the CFS menu is set to 6. Select the target time
the system will attempt to satisfy the thermostat.
SUP
Menu is enabled if the CFS menu is set to 6. Select the percentage
past the target time when the system will enable electric heat
operation during heat mode.
Ot t
Menu is enabled if the CFS is set to 6. (Electric heat will run during
the next heat call if the heat pump fails to satisfy the custom target
time for this number of consecutive cycles) (default = 20 cycles)
vt t
Menu is enabled if the CFS menu is set to 6. (if the addition of low
stage electric heat is able to consecutively satisfy the thermostat
under the set target time for this number of cycles, the system will
transition to the heat pump for primary heating)
SdP
Menu is enabled if the CFS menu is set to 6. (this percentage will
help determine when switching back to heat pump only operation is
appropriate. Default = 20%. If target time = 20 minutes, the addtion
of low stage electric heat must staisfy the thermostat by less than 16
minutes. (target time - 20% default = 16 minutes).