background image

7

1. Remove refrigerant tubing panel or coil (lower) access

panel.

2. Remove access valve fitting cap and depress the valve

stem in access fitting to release pressure. No pressure
indicates possible leak.

3. Replace the refrigerant tubing panel.

4. Remove the spin closure on both the liquid and suction

tubes using a tubing cutter.

5. Insert liquid line set into liquid tube expansion and slide

grommet about 18" away from braze joint.

6. Insert suction line set into suction tube expansion and

slide insulation and grommet about 18" away from braze
joint.

7. Braze joints. Quench all brazed joints with water or a

wet rag upon completion of brazing.

REFRIGERANT BULB
MUST BE POSITIONED
BETWEEN 10 & 2 O’CLOCK

REFRIGERANT BULB
MUST BE POSITIONED
BETWEEN 10 & 2 O’CLOCK

Figure 10

NOTE: The sensing bulb must be permanently located.  A
heat shield, heat trap, or wet rag must be used during braz-
ing to prevent damage to the TXV valve.

8. Replace access panels, suction line grommet, insulation

and all screws.

RUBBER
GROMMET

SUCTION LINE
WITH SPIN CLOSURE

Suction Line Grommet

Figure 11

8

Condensate Drain Lines

The coil drain pan has a primary and a secondary drain with
3/4" NPT female connections. The connectors required are
3/4" NPT male, either PVC or metal pipe, and should be hand
tightened to a torque of no more than 37 in-lbs. to prevent
damage to the drain pan connection. An insertion depth of
approximately 3/8” to 1/2” (3-5 turns) should be expected at
this torque.

1. Ensure drain pan hole is not obstructed.

2. To prevent potential sweating and dripping on to finished

space, it may be necessary to insulate the condensate
drain line located inside the building. Use Armaflex

®

 or

similar material.

A secondary condensate drain connection has been provided
for areas where the building codes require it. Pitch all drain
lines a minimum of 1/4" per foot to provide free drainage.
Provide required support to the drain line to prevent bowing.
If the secondary drain line is required, run the line separately
from the primary drain and end it where condensate discharge
can be easily seen.

NOTE: 

Water coming from secondary line means the coil

primary drain is plugged and needs immediate attention.

Insulate drain lines located inside the building or above a
finished living space to prevent sweating. Install a conden-
sate trap to ensure proper drainage.

NOTE: 

When units are installed above ceilings, or in other

locations where damage from condensate overflow may
occur, it is 

MANDATORY 

to install a field fabricated auxiliary

drain pan under the coil cabinet enclosure.

CAUTION

If secondary drain is not installed, the secondary
access must be plugged.

The installation must include a “P” style trap that is located
as close as is practical to the evaporator coil. See 

Figure 12

for details of a typical condensate line “P” trap.

NOTE: 

Trapped lines are required by many local codes. In

the absence of any prevailing local codes, please refer to the
requirements listed in the Uniform Mechanical Building Code.

A drain trap in a 

draw-through 

application prevents air from

being drawn back through the drain line during fan operation
thus preventing condensate from draining, and if connected
to a sewer line to prevent sewer gases from being drawn into
the airstream during blower operation.

Field experience has shown condensate drain traps with an
open vertical Tee between the air handler and the conden-
sate drain trap can improve condensate drainage in some
applications, but may cause excessive air discharge out of
the open Tee.  Goodman

®

 does not prohibit this type of drain

but we also do not recommend it due to the resulting air leak-
age. Regardless of the condensate drain design used, it is
the installer’s responsibility to ensure the condensate drain
system is of sufficient design to ensure proper condensate
removal from the coil drain pan.

Summary of Contents for AVPTC**14 Series

Page 1: ...4 Start Up Procedure 11 15 Regular Maintenance 11 Circulator Blower 13 Troubleshooting 17 ComfortNet System 18 Start Up Procedure 19 Regular Maintenance 20 Troubleshooting 23 Diagnostic Codes 27 Wiring Diagrams 28 RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION ATTENTION INSTALLING PERSONNEL Prior to installation thoroughly familiarize yourself with this Installation Manual Observe all safety warning...

Page 2: ...onents are present and intact Report any missing components im mediately to Goodman or to the distributor Use only factory authorized replacement parts see Section 5 Make sure to include the full product model number and serial number when reporting and or obtaining service parts HIGH VOLTAGE Failure to do so may cause property damage personal injury or death Disconnect ALL power before servicing ...

Page 3: ...E Installation of unmatched systems is not permit ted and will void the product warranty 5 3 Interconnecting Tubing Give special consideration to minimize the length of re frigerant tubing when installing air handlers Refer to Re mote Cooling Heat Pump Service Manual RS6200006 and TP 107 Long Line Set Application R 410A for tubing guidelines If possible allow adequate length of tubing such that th...

Page 4: ...ttom left drain connection is for the secondary drain line if used The bottom left drain connection is the primary drain for this application and condensate drain line must be at tached to this drain connection The top connection of the three drain connections on the drain pan must remain plugged for this application The bottom right drain con nection is for the secondary drain line if used Screw ...

Page 5: ...l INTERNAL PART TERMINOLOGY Figure 6 NOTE If removing only the coil access panel from the unit the filter access panel must be removed first Failure to do so may result in panel damage Secondary Drain Port for Upflow Downflow Application Secondary Drain Port for Horizontal Application Blower Access Panel Coil Access Panel Tubing Panel Thumb Screw EXTERNAL PART TERMINOLOGY Figure 7 ...

Page 6: ...ting of the casing On these installations a wrap of 2 fiberglass insulation with a vapor barrier is recommended 7 1 Tubing Size For the correct tubing size follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refriger ant leaks The suction line is spun closed and requir...

Page 7: ...imum of 1 4 per foot to provide free drainage Provide required support to the drain line to prevent bowing If the secondary drain line is required run the line separately from the primary drain and end it where condensate discharge can be easily seen NOTE Water coming from secondary line means the coil primary drain is plugged and needs immediate attention Insulate drain lines located inside the b...

Page 8: ...r using the factory filter rails or externally such as a return air filter grille When using the factory filter rails a nominal 16x20x1 20x20x1 or 24x20x1 actual dimension must be less than 23 x20 fil ter can be installed on a B C and D cabinet respectively the cabinet size is the seventh letter of the model number 11 Electric Heat Refer to the installation manual provided with the electric heat k...

Page 9: ...rical and Control Wiring IMPORTANT All routing of electrical wiring must be made through provided electrical knockouts Do not cut puncture or alter the cabinet for electrical wiring 12 1 Building Electrical Service Inspection This unit is designed for single phase electrical supply only DO NOT OPERATE ON A THREE PHASE POWER SUPPLY Measure the power supply to the unit The supply voltage must be mea...

Page 10: ...rea Attach the Supply wires to the air handler conductors as shown in the unit wiring diagram using appropriatelysizedsolderlessconnectorsorotherNEC or CEC approved means 12 4 2 Air Handler Non Circuit Breaker Heat Kits A terminal block is provided with the HKS kit to attach the power supply and air handler connections Follow the HKS Installation Manual and wiring diagram for com plete wiring deta...

Page 11: ... air handler s integrated control module provides termi nals for Y1 and Y2 and W1 and W2 thermostat con nections This allows the air handler to support the systems shown in the following table Refer to the following figures for typical connections to the integrated control module Ther mostat wiring entrance holes are located in the top of the blower Wire routing must not interfere with circulator ...

Page 12: ...the air handler NOTE Ground wire may not be present on all dehumidistats 5 To enable the dehumidification function move the de humidification dip switch S7 from OFF to ON See following figure 6 Turn ON power to air handler ON OFF Move to the ON position to enable dehumidification S5 S6 S7 S8 Dip Switches Dehumidification Enable AUXILIARY ALARM SWITCH The control is equipped with two Auxiliary Alar...

Page 13: ...er If the cooling capacity is in BTU hr divide it by 12 000 to convert capacity to TONs Example Cooling Capacity of 30 000 BTU hr 30 000 12 000 2 5 Tons 2 Determine the proper airflow for the cooling system Most cooling systems are designed to work with airflows between 350 and 450 CFM per ton Most manufactur ers recommend an airflow of about 400 CFM per ton Example 2 5 tons X 400 CFM per ton 1000...

Page 14: ...ction indicates factory setting 75 100 S12 S13 S12 S13 S12 S13 S13 OFF OFF OFF OFF ON ON ON ON Fan Only Selection indicates factory setting 6 The multi speed circulator blower also offers several custom ON OFF ramping profiles These profiles may be used to enhance cooling performance and increase comfort level The ramping profiles are selected using DIP switches 5 and 6 Refer to the following Dip ...

Page 15: ... The adjust setting already es tablished by the cooling speed selection also applies to the electric heater kit airflow Thus the electric heater airflow is adjusted by the same amount This does not apply to systems setup with a communicating thermo stat See Set Up section in the AIR HANDLER ADVANCED FEATURES MENU on page 22 Verify selected CFM by counting the green CFM LED blinks If an electric he...

Page 16: ...ofile see profiles above Set dip switches S5 and S6 to appropriate ON OFF positions Dehumidification To enable set dip switch S7 to ON Cooling airflow will be reduced to 85 of nominal value during cool call when Dehum command is present To disable set S7 to OFF Continuous Fan Speed Use dip switches S12 and S13 to select one of 4 continuous fan speeds Tap A is 25 Tap B is 50 Tap C is 75 Tap D is 10...

Page 17: ...t touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discharge your body to ground before removing a new control from its container Follow steps 1 through 3 if installing the control on a blower Return any old or new controls to their containers before touching any ungrounded object DIAGNOSTIC CHART HIGH VOLTAGE TO AVOID P...

Page 18: ...d features of the ComfortNet sys tem Two way digital communications is accomplished using only two wires The thermostat and subsystem controls are pow ered with 24 VAC Thus a maximum of 4 wires between the equipment and thermostat is all that is required to operate the system AIRFLOW CONSIDERATION Airflow demands are managed differently in a fully commu nicating system than they are in a non commu...

Page 19: ...between Air Handler and Thermostat COMFORTNET SYSTEM ADVANCED FEATURES The ComfortNet system permits access to additional system information advanced set up features and advanced diag nostic troubleshooting features These advanced features are organized into a menu structure See the AIR HANDLER ADVANCED FEATURES MENU section for layout of menu shortcuts DIAGNOSTICS Accessing the air handler s diag...

Page 20: ...ctionable odors flammable vapors or prod ucts of combustion such as carbon monoxide CO which may cause serious personal injury or death REGULAR MAINTENANCE HIGH VOLTAGE Disconnect ALL power before servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death The only item to be maintained on a regular basis by the user i...

Page 21: ... handler is installed as a non communicating traditional system x Check communications wiring data 1 data 2 wires x Check wire connections at terminal block x Verify air handler installation type non communicating traditional or communicating x Check data 1 data 2 voltages x Turn power OFF prior to repair x Verify wires at terminal blocks are securely twisted together prior to inserting into termi...

Page 22: ...t most recent fault For display only Fault 6 FAULT 6 Least recent fault For display only Clear Fault History CLEAR NO or YES Selecting YES clears the fault history NOTE Consecutively repeated faults are shown a maximum of 3 times DIAGNOSTICS Submenu Item Indication for Display Only not User Modifiable Model Number MOD NUM Displays the air handler model number Serial Number SER NUM Displays the air...

Page 23: ...d in shared data set HTR TOO SMALL EC x Heater kit selected via dipswitches is too small for heater kits in shared data set x Verify electric heat dipswitch settings x Verify the installed electric heater is valid for the air handler blower Check nameplate or Specification Sheet applicable to your model for allowable heater kit s x Verify shared data set is correct for the specific model Re popula...

Page 24: ... Data not yet on network NO NET DATA d0 x Air handler blower does not contain any shared data x Populate shared data set using memory card x Turn power OFF prior to repair x Use memory card for the specific model x Insert memory card BEFORE turning power ON Memory card may be removed after data is loaded x Error code will be cleared once data is loaded x Turn power off before removing memory card ...

Page 25: ...rse power MOTOR MISMATCH b2 x Incorrect circulator blower motor in air handler blower x Incorrect shared data set in integrated control module x Verify circulator blower motor horse power is the same specified for the specific air handler blower model Replace is necessary x Verify shared data set is correct for the specific model Re populate data using correct memory card if required x Turn power ...

Page 26: ... Check power to air handler blower Verify line voltage to blower is within the range specified on the air handler blower rating plate x See Installation Instructions for installation requirements x Turn power OFF prior to repair x Air handler blower fails to operate x Integrated control module LED display provides indicated error code x ComfortNet thermostat Call for Service icon illuminated x Com...

Page 27: ...TRIP OR LOST ROTOR b5 BLOWER MOTOR ROTOR LOCKED b6 OVER UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP b7 INCOMPLETE PARAMETER SENT TO MOTOR b9 LOW INDOOR AIRFLOW C1 LOW STAGE COOL LEGACY MODE ONLY C2 HIGH STAGE COOL LEGACY MODE ONLY P1 LOW STAGE HEAT PUMP HEAT LEGACY MODE ONLY P2 HIGH STAGE HEAT PUMP HEAT LEGACY MODE ONLY h1 EMERGENCY HEAT LOW COMMUNICATING MODE ONLY h2 EMERGENCY HEAT HIGH COMMUNICA...

Page 28: ... R2 HTR2 5 M2 W1 1 M4 BK C L1 8 TWO 2 ELEMENT ROWS RD DEHUM TX 3 BL TWO STAGE INTEGRATED CONTROL MODULE TL 3 GND TL NOTE WHEN INSTALLING HEATER KIT ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED MBS SPECIFIED FOR THE AIRHANDLER HEATER HTR2 BL R 6 HEAT SEQUENCER R2 RD TRANSFORMER RD FL YL M7 24 V THERMOSTAT CONNECTIONS 2 HEAT SEQUENCER R1 GN 7 WH TR BK RD FL 2 FL L2 BLWR 8 HTR1 BK BK YL EQUI...

Page 29: ...G MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring 3 Phase Heat Kit WIRING DIAGRAMS ...

Page 30: ...3 BL PU PU L2 L1 CB4 CB3 CB1 CB2 WH PU TL FL TL FL TL FL TL FL COLOR CODE BK BLACK BL BLUE BR BROWN PK PINK RD RED WH WHITE YL YELLOW WIRING CODE HIGH VOLTAGE LOW VOLTAGE COMPONENT CODE PC 9 PIN CONNECTOR HTR HEATER ELEMENT TL THERMAL LMT RS RELAY SEQUENCER TB TERMINAL BLOCK CB CIRCUIT BREAKER CC CONTACTOR FL FUSE LINK TR TRANSFORMER SR STRAIN RELIEF EM EVAPORATOR MOTOR EBTDR ELEC BLOWER TIME DELA...

Page 31: ...e airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refrigerant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless y...

Page 32: ...facturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com or www amana hac com is a registered trademark of Maytag Corporation or its related entities and is used under license All rights reserved ...

Reviews: