months or as required.  When replacing a filter, it must be 

replaced with a filter of the same type and size.

Filter Removal

Depending on the installation, differing filter arrangements 

can be applied.  Filters can be installed in either the central 

return register or a side panel external filter rack (upflow only).  

A media air filter or electronic air cleaner can be used as an 

alternate filter.  Follow the filter sizes given in the Recom

-

mended Minimum Filter size table 7 on page 25 to ensure 

proper unit performance.
To remove filters from an external filter rack in an upright 

upflow installation, follow the directions provided with external 

filter rack kit.

Horizontal Unit Filter Removal

Filters in horizontal installations are located in the central return 

register or the ductwork near the furnace.
To remove:

1.  Turn OFF electrical power to furnace.

2.  Remove  filter(s)  from  the  central  return  register  or 

ductwork.

3.  Replace filter(s) by reversing the procedure for removal.

4.  Turn ON electrical power to furnace.

Media Air Filter or Electronic Air Cleaner Removal

Follow the manufacturer’s directions for service.

Burner

The Ultra Low NOx furnace uses a premix burner. The burner 

box is sealed to achieve safe and reliable operation. 

SCREW

SENSOR

GASKET

IGNITOR

GASKET

LIMIT

GASKET

BURNER BOX

Burner Box

Figure 37

Induced Draft and Circulator Blowers

The bearings in the induced draft blower and circulator blower 

motors are permanently lubricated by the manufacturer. No 

further  lubrication  is  required.    Check  motor  windings  for 

accumulation of dust which may cause overheating. Clean 

as necessary.

Condensate Trap and Drain System (Qualified Ser

-

vicer Only)

Annually inspect the drain tubes, drain trap, and field-sup

-

plied drain line for proper condensate drainage.  Check drain 

system for hose connection tightness, blockage, and leaks.  

Clean or repair as necessary.

Flame Sensor (Qualified Servicer Only)

Under some conditions, the fuel or air supply can create a 

nearly invisible coating on the flame sensor.  This coating 

acts as an insulator causing a drop in the flame sense signal.  

If the flame sense signal drops too low the furnace will not 

sense flame and will lock out.  The flame sensor should be 

carefully cleaned by a qualified servicer using emery cloth 

or steel wool.  Following cleaning, the flame sense signal 

should be as indicated in the Specifications Sheet.

Flue Passages (Qualified Servicer Only)

The heat exchanger flue passageways should be inspected 

at the beginning of each heating season.   

Before Leaving an Installation

• 

Cycle the furnace with the thermostat at least three 

times.  Verify cooling and fan only operation.

• 

Review the Owner’s Manual with the homeowner and 

discuss proper furnace operation and maintenance.

• 

Leave literature packet near furnace.

Repair and Replacement Parts

• 

When ordering any of the listed functional parts, be 

sure to provide the furnace model, manufacturing, and 

serial numbers with the order.

• 

Although only functional parts are shown in the parts 

list, all sheet metal parts, doors, etc. may be ordered 

by description.

• 

Parts are available from your distributor.

Functional Parts List-

Gas 

Valve 

  Blower 

Motor 

  

Gas Manifold   

 

Blower Wheel

Natural Gas Orifice 

 

Blower Mounting Bracket

Igniter   

 

 

Blower Cutoff

Flame Sensor   

 

Blower Housing  

 

Burner Temperature Switch 

Pressure Switches

Primary Limit Switch 

 

Burner Assembly 

Coil Front Cover 

 

Drain Trap 

 

Auxiliary Limit Switch   

Burner  Box  Gasket 

Transformer 

 

 

Integrated Control Module 

Door Switch    

 

Pressure Sensor

Induced Draft Blower 

Summary of Contents for MES96 U Series

Page 1: ...R SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE...

Page 2: ...Air Opening Upflow Models 24 Filters Read This Section Before Installing The Return Air Duct work 24 Upright Installations 25 Horizontal Installations 25 Drain Trap Priming 25 Furnace Operation 25 Ga...

Page 3: ...me trap at time of installation may have a negative effect on combustion quality and pressure switch action WARNING FIRE OR EXPLOSION HAZARD Failue to follow safety warnings exactly could re sult in s...

Page 4: ...d other discounts or reductions Copy of the inspection report issued by carrier s representative at the time damage is reported to carrier Electrostatic Discharge ESD Precautions NOTE Discharge your b...

Page 5: ...n instructions provided and per local and national codes It must be installed indoors in a building constructed on site It must be part of a ducted system and not used in a free air delivery applicati...

Page 6: ...eater POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAIN...

Page 7: ...Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizon tal pitch as required by the National Fuel Gas Code ANSI Z223 1 instructions Determine that ther...

Page 8: ...ization can cause back drafting or improper combustion of gas fired appliances thereby exposing building occupantstogascombustionproductsthatcouldincludecarbon monoxide If this furnace is to be instal...

Page 9: ...en marche alors que tous les autres appareils raccord s au syst me de ventila tion ne sont pas en marche 1 Sceller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst me d...

Page 10: ...onally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Condensate Drain Trap and Lines for further details If the drain trap and drain line...

Page 11: ...A masonry chimney may be used as a chase or passage way for approved venting materials providing the masonry chimney is not also being used to vent products of combustion Never common vent this appli...

Page 12: ...Lengths shown in table 3 apply to single pipe two pipe installations In a two pipe installation do not add intake and vent pipe lengths together Both pipes would normally be equal in length if differ...

Page 13: ...ng the horizontal alternate vent configuration you must use the RF000142 vent drain kit See Figures 10 11 follow steps below NOTE In the horizontal left installation position a means of condensate col...

Page 14: ...rect vent application must terminate at least 12 from any opening through which flue gases may enter a building door window or gravity air inlet The vent termination of vent pipe run vertically throug...

Page 15: ...HEIGHT DIFFERENCE 12 MIN TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL Figure 14 Vertical Termination STRAIGHT ELBOWS Figure 15 VENT FLUE TEE or 45 ELBOW TURNED DOWN or 90 ELBOW TURNED DOWN OPTIONAL 12 M...

Page 16: ...swiththeexhaustventandairintaketerminations of a single unit If more than one direct vent furnace is to be installed horizontally through a common side wall maintain the clearances as in the following...

Page 17: ...Drain Trap A condensing gas furnace achieves its high level of efficiency by extractingheatfromtheproductsofcombustiontothepointwhere condensation takes place The condensate must be collected in the f...

Page 18: ...barbed end goes in the cabinet through the hole in the left side of the cabinet and secure with two field supplied 8 self tapping screws see Figure 24 2 Locate the long drain hose 3 and cut at B line...

Page 19: ...rip leg port must be sealed to prevent flue gases from escaping Insert the rubber plug removed in step 6 into the unused elbow drain port Inserting a blunt tool such as a 3 16 Allen wrench into the ce...

Page 20: ...ctrical circuit containing prop erly sized wire and fuse or circuit breaker The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating...

Page 21: ...ERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY...

Page 22: ...rning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Maximum torque for the gas valve connection is 375 in lbs excessive over tightening may damage the...

Page 23: ...ressures in excess of psig 3 48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressure...

Page 24: ...e cor ners of the opening cut the sheet metal along the scribe lines to free the duct flanges Using the scribe line along the duct flange as a guide unfold the duct flanges around the perimeter of the...

Page 25: ...MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING Furnace Startup 1 Closethemanualgasshutoffvalveexternaltothefurnace 2 Turn off the electrical powe...

Page 26: ...ure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer Reinstall plug and tighten as needed before turni...

Page 27: ...essure cannot vary by more than 0 2 w c for Natural gas from the specified setting Consult your local gas supplier if additional input rate adjustment is required 4 Turn ON gas to and relight all othe...

Page 28: ...ule performs internal checks LED will flash once at power up then remain on Integrated control module monitors safety circuits continuously Furnace awaits call from thermostat Heating Mode The normal...

Page 29: ...osed electrically auto reset sensor This switch guards against the burner flames not being properly drawn into the heat exchanger Pressure Switches The pressure switches are normally open closed durin...

Page 30: ...ol will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Field Test Mode Function When the SW1 button is pressed and held until the LED is blinking in AMBER more t...

Page 31: ...ly Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as nece...

Page 32: ...Open RED When an open limit is detected the control energizes the blower at cooling speed and the inducer at the RUN setting no CFH required Once the limit closes and the CFH is present the furnace r...

Page 33: ...Press and hold the SW1 button for more than 5 seconds results in the display of this mode Releasing the Button during this indication will cause the Error History to be cleared The button must be rel...

Page 34: ...CFM Rise CFM CFM CFM Red High Cool 3 1350 NA 1310 NA 1273 NA 1234 NA 1198 NA 1156 1117 1078 Blue Med Hi Heat 2 5 1247 29 1212 30 1167 31 1129 32 1087 33 1043 997 952 Brown Med Low 2 1151 31 1107 32 1...

Page 35: ...ore servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring d...

Page 36: ...a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminsh their warranty rights Fo...