background image

22

Figure 18

Fan and Limit Control

CAUTION

This unit should not be used as a “con-
struction heater” during the finishing
phases of construction on a new struc-
ture. This type of use may result in pre-
mature failure of the unit due to extremely
low return air temperatures and exposure
to very dirty atmospheres.

To Turn Off Unit

1. Set the thermostat to lowest setting.

2. Turn off the electrical power supply to the furnace.

3. Remove the right hand door on the front of the fur-

nace by removing screws.

4. Turn the gas control valve knob to the OFF position.

Do not force. See Figure 16.

5. Close manual gas shutoff valve external to the fur-

nace.

6. Replace the door on the unit.

7. If cooling and/or air circulation will be  desired, turn

ON the electrical power.

Cooling Startup

Compressor Protection Devices
The PGC and PGB includes components which are de-
signed to protect the compressor against abnormal op-
erating conditions. These include the short cycle pro-
tector, external compressor protector (PGC24-42, 60 and
PGB58 only), and high pressure cutout.

These controls reset automatically. Excessive cycling
of the controls should be investigated before continuing
operation.

(NOTE: The operation of the indoor blower will not be
affected by any of the above compressor protection de-
vices.)

WARNING

To avoid personal injury or death, always
disconnect electrical power before in-
specting or servicing the unit. All com-
pressor protection devices reset auto-
matically, energizing the contactor and
outdoor fan.

Short Cycle Protector (Figure 19)
The short cycle protector is located in the blower com-
partment. Each time the compressor shuts off for any
reason, the short cycle protector will open. It will take
about 3 to 4 minutes before the short cycle protector will
reset and allow compressor startup to occur.

All wiring connected to the short cycle protector is 24V.
If the compressor cycles on the short cycle protector
without cycling on any of the other compressor protec-
tion devices and before the call for cooling ends, com-
mon causes include:

Interruption of the line voltage power.

Improper thermostat installation, defective thermo-
stat wiring, or defective thermostat.

Rapid adjustments of the room thermostat.

Short Cycle

Protector

Figure 19

Short Cycle Protector Location

High Pressure Cutout  (Figure 20)
An automatic reset high pressure control is located in
the compressor discharge line. (See Figure 20) This
control protects the unit from excessively high refriger-
ant pressure.

High pressures can result from:

Inoperative outdoor fan motor.

Outdoor coil restricted with debris.

Recirculation of hot condenser air.

Overcharge of refrigerant.

Summary of Contents for PGB58B

Page 1: ...is a matter of common sense a matter of think ing before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual should not sup...

Page 2: ...ckout Timing sec 4 4 4 4 4 Flame Sense Current microamps Minimum 1 1 1 1 1 Maximum 6 6 6 6 6 Evaporator Coil Face Area Sq Ft 4 4 4 4 4 Rows Deep 2 2 2 4 4 Fins Inch 16 16 16 12 12 External Filter Size...

Page 3: ...in 24 24 24 24 24 24 CFM 3500 3500 3700 3700 4700 4700 Condenser Fan Motor Horsepower 1 4 1 4 1 2 1 2 1 3 1 3 R L Amps 1 5 1 5 1 5 1 5 2 5 2 5 L R Amps 3 4 3 4 3 6 3 6 6 4 6 4 Blower Motor Horsepower...

Page 4: ...Dia x Width in 11X8 11X8 11X8 Rated CFM Cooling 1750 1750 1750 Max External 0 5 wc 0 5 wc 0 5 wc Combustion Blower Diameter x Width in 4 x 1 25 4 x 1 25 4 x 1 25 No 1 1 1 Condenser Blower Motor H P 1...

Page 5: ...applicable for both vertical and horizontal airflow Table 2B PGB CFM Temperature Rise vs External Static Pressure Table External Static Pressure Inches Water Column Motor 0 1 0 2 0 3 0 4 0 5 0 6 0 7...

Page 6: ...r unit four hours prior to operat ing air conditioner after the electrical dis connect is off for a prolonged period of time during vacation etc This time lapse allows the compressor crankcase to atta...

Page 7: ...the unit to avoid these problems When the unit is heating the temperature of the re turn air entering the unit must be between 50 F and 100 F Ground Level Installations Only When the unit is installe...

Page 8: ...8 Figure 1 Required Clearances For All Installations...

Page 9: ...w local codes when disposing or recycling the packaging material Locating The Thermostat The thermostat should be mounted 5 feet above the floor on a vibration free inside wall in a room or a hallway...

Page 10: ...ssure to a lower pres sure reading than what is specified on the furnace name plate is not a proper derate procedure With a lower den sity of air and a lower manifold pressure at the burner orifice th...

Page 11: ...s no open flame in the vicinity during air bleeding procedure The unit is placed in operation by closing the main electrical disconnect switch for the furnace Tanks And Piping for Propane Gas Units WA...

Page 12: ...ntacting a propane gas supplier about installing a warning device to warn of a gas leak Propane gas is heavier than air and any leaking gas can settle in low areas or confined areas Propane gas odoran...

Page 13: ...he unit must be electrically grounded in accordance with local codes or in the ab sence of local codes with the latest edition of National Electrical Code ANSI NFPA No 70 WARNING To avoid death or per...

Page 14: ...Typical Wiring Ground Level Disconnect Switch High Voltage Source High Voltage Entrance Low Voltage Entrance Typical Wiring Rooftop Disconnect Switch High Voltage Source High Voltage Entrance Low Volt...

Page 15: ...8 60 or PGB58 PFK5B1 or PFK5B6 32 5 8 x 22 3 8 x 1 The Amana filter kit includes a permanent filter door label and installation instructions PFK3A1 and PFK5B1 contain filter label and instructions for...

Page 16: ...pliance not connected to the common venting system Turn on any exhaust fans such as the range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Clos...

Page 17: ...Combustion Product Purge Ends Air Blower OFF Combustion Blower OFF Figure 12 Timing Chart for Normal Robertshaw Operation PGB PGC Figure 13B PGC Timing Chart for Normal Cooling Operation On Off On Of...

Page 18: ...itioned space PGC Normal Sequence of Operations Cooling See Figure 13B 1 Thermostat calls for cooling The compressor in door fan and outdoor fan are energized 2 Approximately 30 seconds later the indo...

Page 19: ...kout by disengaging the electric disconnect switch to the furnace for thirty sec onds Operating Instructions Heating NOTE Figure 16 illustrates the proper gas valve mount ing location Flame Roll Out P...

Page 20: ...the burner orifices Check The Gas Input Natural Gas Only NOTE On outdoor equipment the gas input will vary with the temperature of the gas Rated input will be ob tained at approximately 10 F With war...

Page 21: ...rd lo cated on the blower housing The speed tap settings have been factory selected according to unit size and performance Field select taps are provided on the speed tap board to assist the final ins...

Page 22: ...be affected by any of the above compressor protection de vices WARNING To avoid personal injury or death always disconnect electrical power before in specting or servicing the unit All com pressor pro...

Page 23: ...during vacation etc This time lapse allows the compressor crankcase to attain a proper operating temperature NOTE Mechanical cooling cannot be reliably provided at ambient temperatures below 50 F If l...

Page 24: ...death due to electrical shock disconnect electrical power before performing any mainte nance Important Note Touching the ignitor body with bare fin gers rough handling or vibration could result in ear...

Page 25: ...ire oiling Flue Passages At the start of each heating season inspect and if nec essary clean the furnace flue passages Cleaning Flue Passages Qualified Servicer Only 1 Shut off electric power and gas...

Page 26: ...nd Functional Parts Accessories Additional Amana accessories can be purchased to fit specific application needs Accessories can be ordered by description in Table 5 Each accessory includes its own sep...

Page 27: ...8 89 255 10 7 8 87 251 13 4 8 85 275 16 2 95 72 13 88 251 10 6 13 86 249 13 3 13 85 274 16 1 67 18 88 252 10 7 18 86 249 13 3 18 84 274 16 1 62 23 87 254 10 7 23 85 249 13 3 23 83 274 16 1 77 8 88 23...

Page 28: ...256 21 3 10 80 268 29 2 95 72 13 82 258 19 6 13 85 257 21 2 16 80 267 29 2 67 18 82 257 19 5 19 84 256 21 2 22 79 267 29 2 62 24 81 256 19 5 25 84 255 21 1 28 78 266 29 1 77 8 82 241 18 8 8 84 240 20...

Page 29: ...29 XVI Wiring Diagram PGC24 36...

Page 30: ...30 PGC 42...

Page 31: ...31 PGC 48...

Page 32: ...IGNITION CONTROL L2 IGN IGN L1 RS TH VALVE GND NC NO COM BR 11 BK 27 C W G R Y TERMINAL BOARD YL 12 VT 20 RD 10 BK 33 GND OR 49 BU 10 BR 21 GY 30 RD 23 RD 22 BR 22 GY 70 OR 15 RD 1 CONTACTOR CC T2 T1...

Page 33: ...VT 47 RD 1 GND OR 49 BU 10 BR 21 RD 23 RD 22 BR 22 OR 15 OR 8 BU RD 230V BK 208V H H 3 1 FAN TIME DELAY FD FOR PROPER OPERATION ON 208 VOLT THE FOLLOWING CHANGES MUST BE MADE 208 VOLT INSTALLATION MOV...

Reviews: