background image

5

1. Installation is to be adjusted to obtain temperature rise within the range specified on the rating plate.

2. The temperature rise is for units installed at 0-2000 feet. At higher altitudes, a properly derated unit will have

approximately the same temperature rise and CFM.

3. The chart is applicable for both vertical and horizontal airflow.

4. All speed tap settings are factory selected according to unit size.

5. Data shown without filters. Consult filter manufacturer for pressure drop to be added.

6. Motor is constant CFM for external static pressures 0.1" to 0.8" W.C.

7. Maximum External Pressure Limits

      PGC 24-42     0.8" W.C.

      PGC46 & 60   1.0 W.C.

Table 2A

PGC Temperature Rise Table

NOTE:

1. All airflow is dry coil.

2. Installation is to be adjusted to obtain temperatures rise within the range specified on the rating plate.

3. The above chart is for information only. For satisfactory operation, external static pressure should not exceed  value shown on the rating

plate. The shaded area (

) indicates in excess of maximum external static pressure allowable when heating.

4. This chart is for units installed at 0-2000 feet. At higher altitudes,  a properly derated unit will have approximately the same temperature

rise at a particular CFM, while ESP at that CFM will be lower.

5. Cooling operation may require a different fan speed than heating operation. For details, see Wiring Diagrams.

6. Above chart is applicable for both vertical and horizontal airflow.

Table 2B

PGB CFM& Temperature Rise vs. External Static Pressure Table

External Static Pressure, Inches Water Column

Motor

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

Model

Speed

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

Hi

2160

31

2120

31

2080

32

2030

33

1990

34

1945

34

1900

35

1835

36

PGB58B0902C

Med

1750

38

1750

39

1700

39

1680

40

1680

40

1615

41

1575

42

1490

45

Lo

1490

45

1480

45

1470

45

1450

46

1440

46

1415

47

1360

49

1280

52

Hi

2160

---

2120

---

2080

41

2030

42

1990

43

1945

44

1900

45

1835

46

PGB58B1152C

Med

1750

49

1750

49

1700

50

1680

51

1650

52

1615

53

1575

54

1470

57

Lo

1490

57

1480

58

1470

58

1460

58

1440

59

1415

60

1360

63

1280

67

Hi

2160

46

2120

47

2080

48

2030

49

1990

50

1945

51

1900

53

1835

54

PGB58B1352C

Med

1750

57

1750

58

1700

59

1680

60

1650

61

1615

62

1575

63

1490

67

Lo

1490

67

1480

68

1470

68

1460

68

1440

69

1415

---

1360

---

1280

---

Model

Nominal 

Cooling

Nominal 

Nominal 

Heating

Nominal Nominal

Temp.

Speed

Capacity 

(MBh)

Cooling 

CFM 

Capacity 

(Input)

Heating 

CFM

Fan Only  Rise (°F) 

Taps

(Y+G)

(W1)

(G)

Cool

Heat

PGC24B0452A

24000

850

45000

930

570

35

A

A

PGC24B0702A

24000

850

70000

1140

570

45

A

B

PGC30B0702A

30000

1100

70000

1140

570

45

B

B

PGC36BO702A

36000

1300

70000

1140

570

45

C

B

PGC36B0902A

36000

1300

90000

1350

570

55

C

C

PGC42B0902A

42000

1450

90000

1650

815

40

A

A

PGC42B1152A

42000

1450

115000

1530

815

55

A

B

PGC48B0902A

48000

1700

90000

1650

815

40

B

A

PGC48B1152A

48000

1700

115000

1530

815

55

B

B

PGC60B0902A

60000

1750

90000

1650

815

40

A

A

PGC60B1352A

60000

1750

135000

1900

815

55

A

B

Summary of Contents for PGB58B

Page 1: ...is a matter of common sense a matter of think ing before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual should not sup...

Page 2: ...ckout Timing sec 4 4 4 4 4 Flame Sense Current microamps Minimum 1 1 1 1 1 Maximum 6 6 6 6 6 Evaporator Coil Face Area Sq Ft 4 4 4 4 4 Rows Deep 2 2 2 4 4 Fins Inch 16 16 16 12 12 External Filter Size...

Page 3: ...in 24 24 24 24 24 24 CFM 3500 3500 3700 3700 4700 4700 Condenser Fan Motor Horsepower 1 4 1 4 1 2 1 2 1 3 1 3 R L Amps 1 5 1 5 1 5 1 5 2 5 2 5 L R Amps 3 4 3 4 3 6 3 6 6 4 6 4 Blower Motor Horsepower...

Page 4: ...Dia x Width in 11X8 11X8 11X8 Rated CFM Cooling 1750 1750 1750 Max External 0 5 wc 0 5 wc 0 5 wc Combustion Blower Diameter x Width in 4 x 1 25 4 x 1 25 4 x 1 25 No 1 1 1 Condenser Blower Motor H P 1...

Page 5: ...applicable for both vertical and horizontal airflow Table 2B PGB CFM Temperature Rise vs External Static Pressure Table External Static Pressure Inches Water Column Motor 0 1 0 2 0 3 0 4 0 5 0 6 0 7...

Page 6: ...r unit four hours prior to operat ing air conditioner after the electrical dis connect is off for a prolonged period of time during vacation etc This time lapse allows the compressor crankcase to atta...

Page 7: ...the unit to avoid these problems When the unit is heating the temperature of the re turn air entering the unit must be between 50 F and 100 F Ground Level Installations Only When the unit is installe...

Page 8: ...8 Figure 1 Required Clearances For All Installations...

Page 9: ...w local codes when disposing or recycling the packaging material Locating The Thermostat The thermostat should be mounted 5 feet above the floor on a vibration free inside wall in a room or a hallway...

Page 10: ...ssure to a lower pres sure reading than what is specified on the furnace name plate is not a proper derate procedure With a lower den sity of air and a lower manifold pressure at the burner orifice th...

Page 11: ...s no open flame in the vicinity during air bleeding procedure The unit is placed in operation by closing the main electrical disconnect switch for the furnace Tanks And Piping for Propane Gas Units WA...

Page 12: ...ntacting a propane gas supplier about installing a warning device to warn of a gas leak Propane gas is heavier than air and any leaking gas can settle in low areas or confined areas Propane gas odoran...

Page 13: ...he unit must be electrically grounded in accordance with local codes or in the ab sence of local codes with the latest edition of National Electrical Code ANSI NFPA No 70 WARNING To avoid death or per...

Page 14: ...Typical Wiring Ground Level Disconnect Switch High Voltage Source High Voltage Entrance Low Voltage Entrance Typical Wiring Rooftop Disconnect Switch High Voltage Source High Voltage Entrance Low Volt...

Page 15: ...8 60 or PGB58 PFK5B1 or PFK5B6 32 5 8 x 22 3 8 x 1 The Amana filter kit includes a permanent filter door label and installation instructions PFK3A1 and PFK5B1 contain filter label and instructions for...

Page 16: ...pliance not connected to the common venting system Turn on any exhaust fans such as the range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Clos...

Page 17: ...Combustion Product Purge Ends Air Blower OFF Combustion Blower OFF Figure 12 Timing Chart for Normal Robertshaw Operation PGB PGC Figure 13B PGC Timing Chart for Normal Cooling Operation On Off On Of...

Page 18: ...itioned space PGC Normal Sequence of Operations Cooling See Figure 13B 1 Thermostat calls for cooling The compressor in door fan and outdoor fan are energized 2 Approximately 30 seconds later the indo...

Page 19: ...kout by disengaging the electric disconnect switch to the furnace for thirty sec onds Operating Instructions Heating NOTE Figure 16 illustrates the proper gas valve mount ing location Flame Roll Out P...

Page 20: ...the burner orifices Check The Gas Input Natural Gas Only NOTE On outdoor equipment the gas input will vary with the temperature of the gas Rated input will be ob tained at approximately 10 F With war...

Page 21: ...rd lo cated on the blower housing The speed tap settings have been factory selected according to unit size and performance Field select taps are provided on the speed tap board to assist the final ins...

Page 22: ...be affected by any of the above compressor protection de vices WARNING To avoid personal injury or death always disconnect electrical power before in specting or servicing the unit All com pressor pro...

Page 23: ...during vacation etc This time lapse allows the compressor crankcase to attain a proper operating temperature NOTE Mechanical cooling cannot be reliably provided at ambient temperatures below 50 F If l...

Page 24: ...death due to electrical shock disconnect electrical power before performing any mainte nance Important Note Touching the ignitor body with bare fin gers rough handling or vibration could result in ear...

Page 25: ...ire oiling Flue Passages At the start of each heating season inspect and if nec essary clean the furnace flue passages Cleaning Flue Passages Qualified Servicer Only 1 Shut off electric power and gas...

Page 26: ...nd Functional Parts Accessories Additional Amana accessories can be purchased to fit specific application needs Accessories can be ordered by description in Table 5 Each accessory includes its own sep...

Page 27: ...8 89 255 10 7 8 87 251 13 4 8 85 275 16 2 95 72 13 88 251 10 6 13 86 249 13 3 13 85 274 16 1 67 18 88 252 10 7 18 86 249 13 3 18 84 274 16 1 62 23 87 254 10 7 23 85 249 13 3 23 83 274 16 1 77 8 88 23...

Page 28: ...256 21 3 10 80 268 29 2 95 72 13 82 258 19 6 13 85 257 21 2 16 80 267 29 2 67 18 82 257 19 5 19 84 256 21 2 22 79 267 29 2 62 24 81 256 19 5 25 84 255 21 1 28 78 266 29 1 77 8 82 241 18 8 8 84 240 20...

Page 29: ...29 XVI Wiring Diagram PGC24 36...

Page 30: ...30 PGC 42...

Page 31: ...31 PGC 48...

Page 32: ...IGNITION CONTROL L2 IGN IGN L1 RS TH VALVE GND NC NO COM BR 11 BK 27 C W G R Y TERMINAL BOARD YL 12 VT 20 RD 10 BK 33 GND OR 49 BU 10 BR 21 GY 30 RD 23 RD 22 BR 22 GY 70 OR 15 RD 1 CONTACTOR CC T2 T1...

Page 33: ...VT 47 RD 1 GND OR 49 BU 10 BR 21 RD 23 RD 22 BR 22 OR 15 OR 8 BU RD 230V BK 208V H H 3 1 FAN TIME DELAY FD FOR PROPER OPERATION ON 208 VOLT THE FOLLOWING CHANGES MUST BE MADE 208 VOLT INSTALLATION MOV...

Reviews: