background image

 

PN 08220

 

04/2020

 

5.

 

Inspect the cylinder interior following CGA Visual Inspection Standard, Pamphlet C

-

6.

 

6.

 

Fill Amerex Model 570/B570 cylinder with 30 pounds (13.6 KG) of Amerex Super D (Sodium Chloride) dry 

powder. Use Amerex dry powder that has been kept moisture and contamination free.

 

7.

 

Clean cylinder O

-

ring seat and threads inside of cylinder collar with a small brush and wipe surfaces with 

a clean damp cloth to remove dust. Lightly brush the collar O

-

ring seat with V

-

711. Install the operating 

valve/downtube assembly hand tight.

 

8.

 

Attach the charging adapter to the valve discharge port.

 

WARNING:  THIS  EXTINGUISHER  IS  FACTORY  PRESSURIZED  USING  ARGON.  ARGON  IS  AN 

INERT  GAS  THAT  WILL  NOT  ADVERSELY  REACT  WITH  COMBUSTIBLE  METALS. 

NITROGEN  PRESSURIZING  GAS  COULD  CAUSE  A  REACTION  WHEN  USED  ON 

CERTAIN  TYPES  OF  COMBUSTIBLE  METAL  FIRES.  DRY

-

AIR  PRESSURIZATION 

SHALL  NEVER  BE  USED,    AS  EVEN  THE  SLIGHTEST  AMOUNT  OF  MOISTURE  WILL 

CAUSE A VIOLENT REACTION WITH CLASS

-

D MATERIALS.

 

9.

 

With the extinguisher properly secured in an upright position, connect your argon pressurizing line with a 

quick  connect  to  the  charging adapter. Set  the  Argon  supply  cylinder  regulator  to  no  more  than 220  psi 

(1520 kPa). Depress the extinguisher operating valve lever, and pressurize the extinguisher with argon to 

195 psi (1345 kPa). When the desired pressure has been reached, release the operating lever. Shut off 

Argon supply and remove the quick connect.

 

10.

 

Remove the charging adapter. Check extinguisher for leaks by applying leak detecting fluid or a solution 

of  soapy  water  to  the  valve

-

discharge orifice,  around  the  collar  O

-

ring  sealing area,  cylinder  welds,  and 

gauge. Remove leak detecting fluid from valve assembly by blowing out with air or argon. Wipe exterior of 

extinguisher to remove any remaining residue.

 

11.

 

Install the hose assembly to the operating valve. Reconnect the female swivel on the extension applicator 

to the male swivel on the hose. Rotate the hose assembly several times to verify that the swivel operates 

freely.  Disconnect  and  clean  the  inside  of  the  swivel  female  with  a  small  brush  and  compressed  air  if 

rotation is impeded. Install hose and extension applicator according to instructions on page 9.

 

12.

 

Install pull pin and tamper seal. Record recharge date, and attach new recharge tag.

 

13.

 

Weigh assembled extinguisher, and confirm that the total weight is within the allowable tolerances 
indicated in the "

Maintenance

" section of the nameplate (label).

 

COMPLETE MAINTENANCE (SIX

-

YEAR TEARDOWN)

 

Every 6 years, stored

-

pressure extinguishers shall be emptied and subjected to the applicable maintenance 

procedures. When the applicable maintenance procedures are performed during periodic recharging or 
hydrostatic testing, the 6

-

year requirement shall begin from that date. 

 

NOTE:  Some states require Complete Maintenance on an Annual Basis. Check with your 

Amerex servicing distributor to see if this applies to you. NFPA 10 requires that a 
"verification of service" external collar tag be installed on the extinguisher 
whenever "Six

-

Year Maintenance" is performed. The "verification of service" tag 

can only be installed if the operating valve has been removed. A "Six

-

Year 

Maintenance" service decal must also be attached to the extinguisher cylinder. 

 

Summary of Contents for 570

Page 1: ...EREX CORPORATION IT SHALL NOT BE DUPLICATED USED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESS WRITTEN CONSENT NOTES 1 THIS COVERSHEET FOR INFORMATIONAL PURPOSES ONLY DO NOT PRINT THIS PAGE IN MANUAL 2 DESCRIPTION MANUAL OWNER S SERVICE FOR MODEL B570 PORTABLE EXTINGUISHER 3 ACTUAL PRINTED MATERIAL TO CONSIST OF ATTACHED 4 OVERALL SIZE OF PRINTED DOCUMENT PAGES 8 1 2 X 11 ON 20 LB PAPER 5 PRINTED MAT...

Page 2: ...EDIATELY AFTER ANY USE OWNER S SERVICE MANUAL INSTALLATION OPERATING SERVICING INSTRUCTIONS MANUAL PN 08220 CLASS D PORTABLE EXTINGUISHER MODEL B570 AMEREX CORPORATION DOES NOT SERVICE MAINTAIN OR RECHARGE FIRE EXTINGUISHERS THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST QUALIFIED SERVICE PERSONNEL IN THE INSPECTION MAINTENANCE AND RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY NO INSTRUCTION MANUAL CA...

Page 3: ... applicable standards of Factory Mutual to ANSI UL 711 and ANSI UL 299 It also complies with industry standards as presented in the National Fire Protection Association Standard No 10 Standard for Portable Fire Extinguishers WARNINGS USE THIS EXTINGUISHER ONLY ON CLASS D BURNING METALS CLASS D FIRES NORMALLY GENERATE EXTREMELY HIGH HEAT AMEREX RECOMMENDS THE USE OF PROTECTIVE CLOTHING AND SELF CON...

Page 4: ...ess than 50 feet 15 m from the hazard leaving unobstructed access Avoid placing it in an extremely hot or cold place The operational temperature range is 40 F to 120 F 40 C to 49 C Adequately protect the extinguisher if temperatures outside this range are anticipated Keep the extinguisher clean and free from dirt ice chemicals and any contaminants that may interfere with its proper operation DO NO...

Page 5: ...ob the chemical onto the fire Be careful not to spread the fire surface when using this technique 4 Reapply powder to visible hot spots 5 To avoid re ignition allow metal to cool before cleanup 6 Evacuate and ventilate the area immediately after use The fumes and smoke from any fire may be hazardous and can be deadly INSPECTION INSPECTION NFPA 10 is a quick check intended to give reasonable assura...

Page 6: ...late label Recharge extinguisher if weight is not within indicated allowable tolerances see instructions in Recharge Procedure 4 Check the date of manufacture stamped on the bottom of the extinguisher or nameplate for model B570 and on the wall hanger loop for Model 570 Cylinder must be hydrostatically proof pressure tested every 12 years to the test pressure indicated on the nameplate 585 psi 403...

Page 7: ...available 4 Use a regulated pressurizing source of ARGON ONLY Set the regulator to no more than 220 psi 1520 kPa 5 Check and calibrate regulator gauge at frequent intervals The regulator gauge shall be used to determine when the intended charging pressure has been reached Do not use the extinguisher gauge for this purpose 6 Never leave an extinguisher connected to a regulator of a high pressure so...

Page 8: ... fluid or a solution of soapy water to the valve discharge orifice around the collar O ring sealing area cylinder welds and gauge Remove leak detecting fluid from valve assembly by blowing out with air or argon Wipe exterior of extinguisher to remove any remaining residue 11 Install the hose assembly to the operating valve Reconnect the female swivel on the extension applicator to the male swivel ...

Page 9: ...ROBLEM CORRECTIVE ACTION 1 Leak at operating valve col lar O ring Remove valve assemble clean collar thoroughly and install new collar O ring Lubricate with Bluestar V 711 2 Leak through valve Install new valve stem assembly Check valve seat scratches or foreign matter Install new valve stem assembly 3 Leak around gauge thread Remove gauge and reinstall using Teflon tape on the gauge threads 4 Def...