background image

 

7

3 Operation

 

 
The DHV-150H can be equipped with various 
accessories to enhance its operation. A remote control 
panel must be used with the DHV-150H. There are two 
remote control panels from which to choose. The 
humidity/fan control panel is used to control humidity 
and the fan. The ventilation timer and humidity control 
panel is used to control ventilation, humidity and the 
fan. 
 

3.1 Humidity/Fan Control Panel 

 
See Figure 7: The humidity/fan control panel 
automatically controls the humidity of the living space. 
The humidity/fan control panel contains an adjustable 
humidity control and a fan switch. This panel should be 
mounted in a central area of the structure where it can 
accurately sense the humidity of the air in the living 
space. The panel has a cover that must remain open 
to the air within the living space for accurate humidity 
sensing. 
 
The humidity/fan control panel can be used in 
conjunction with the optional fresh air damper. When 
used with the optional fresh air damper, the fan/filter 
switch will act as a fresh air ventilation control. When 
the switch is ON (in this configuration), the fan will run, 
the fresh air damper will open, and fresh air will be 
filtered and brought into the structure. When the switch 
is OFF, the fresh air damper will close and the fan will 
operate only when the humidity control calls for 
dehumidification. Contact the factory for instructions 
on this type of installation. 
 

3.2 Ventilation Timer and  

Humidity Control Panel

 

 
See Figure 7: The ventilation timer and humidity 
control panel automatically controls both the 
ventilation and the humidity of the living space. The 
ventilation timer and humidity control panel contains 
an adjustable humidity control, a fan switch, and a 
ventilation timer. This panel will control the humidity 
and allow programmed ventilation of the living space. 
This panel works in conjunction with the optional fresh 
air damper to provide ventilation. 
 
This panel should be mounted in a central area of the 
structure where it can accurately sense the humidity of 
the air in the living space. The panel has a cover that 
must remain open to the air within the living space for 
accurate humidity sensing. 

3.3 Humidity Control Adjustment

 

 
Set the humidity control to the desired humidity level 
for the home. The dehumidifier will run continuously 
until the relative humidity (RH) is reduced to the 
humidity control dial setting. Setting the humidity 
control to lower RH levels will 

NOT

 increase the unit's 

dehumidification rate; the unit will simply run longer to 
reduce the area's RH to the setting. The DHV-150H 
unit (and refrigerant-based dehumidifiers in general) 
will reduce a warm space's RH to a lower level than 
that of a cool space. It is therefore pointless to set the 
humidity control to excessively low levels in cool 
rooms; doing so will result in long periods of ineffective 
dehumidifier run time. 
 
Quality humidity meters are available from the factory 
and are recommended to accurately monitor humidity 
levels. 

 

3.4 Fan/Filter Switch

 

 
Turning ON the fan/filter switch will cause the central 
conditioning unit's internal fan to run continuously, 
whether the central conditioning unit is dehumidifying 
or not. This function is desirable if the central 
conditioning unit is used for air circulation and filtration 
to achieve maximum indoor air quality. When the 
switch is ON; air will be constantly filtered through the 
central conditioning unit and circulated throughout the 
house. When the switch is OFF the fan will operate 
only when the humidity control calls for 
dehumidification or when the ventilation timer calls for 
ventilation. 
 

3.5 Ventilation Timer

 

 
The ventilation timer controls the fan and the 
motorized fresh air damper. When the ventilation timer 
is activated, the central conditioning unit will circulate 
the indoor air, and bring in fresh air from outside. The 
ventilation timer should be set for the required 
ventilation of the residence. The home should be 
ventilated with fresh air as suggested by applicable 
codes and standards. 
 
In cold climates or areas where the outdoor dew point 
is low at times, ventilation can be used to dehumidify 
the structure.  This approach is often more economical 
than running the dehumidifier to remove excess 
moisture from the structure. For example, in a house 
that experiences condensation on the interior surface 
of the windows during the winter, increasing the 
amount of ventilation will often cure the problem. 
 

Summary of Contents for DHV-150H

Page 1: ...er 13 5 8 Defrost Thermostat 13 5 9 Electric Ventilation Damper 13 5 10 Low Pressure Control 13 5 11 Condensate Pump Kit 13 6 Electrical Schematic 14 7 Pictorial Electrical Diagram 15 8 Service Parts List 16 9 The DHV 150H 16 10 Optional Parts List 17 11 Accessories 17 12 Warranty Terms 18 Serial No ________________________________ Purchase Date ____________________________ Dealer s Name _________...

Page 2: ...mmon grounded outlet on a 15 or 20 Amp circuit It draws around 12 Amps under normal operating conditions If used in a wet area pool spa room or basement prone to flooding a ground fault interrupter protected circuit is required Install the remote control panel in a central area of the structure where it will sense the relative humidity of the structure accurately Avoid installing the control panel...

Page 3: ...tructure Ducting the DHV 150H as mentioned in sections 2 4A 2 4G requires consideration of the following points Duct Sizing For total duct lengths up to 25 use a minimum 10 diameter round or equivalent rectangular For longer lengths use a minimum 12 diameter or equivalent Grills or diffusers on the duct ends must not excessively restrict airflow Isolated Areas Effective dehumidification may requir...

Page 4: ...0H in a central area of the structure Duct the supply of the DHV 150H to a 10 x 10 x 10 tee damper that is 30 open to the crawl space if desired Duct the other side of the tee to the air supply of the existing HVAC system Connect an insulated duct from outside to the 6 collar of the DHV 150H if you wish to provide optional fresh make up air 2 4F Installation in an Attic with an Existing Forced Air...

Page 5: ... the support can easily be removed Cut the strips of metal on each end and remove the support section from the cabinet This will prevent the compressor from transmitting vibration to the cabinet Make sure none of the compressor tubes are pressed against the cabinet or access panel Check that the compressor tubes are centered in the holes where they pass through the drain pan A length of 10 feet or...

Page 6: ...6 Figure 1 DHV 150H in a Basement With a Forced Air System Incorporating a Central Return Figure 2 DHV 150H in an Attic with a Forced Air System Incorporating a Central Return ...

Page 7: ...r within the living space for accurate humidity sensing 3 3 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting Setting the humidity control to lower RH levels will NOT increase the unit s dehumidification rate the unit will simply run lo...

Page 8: ...lation Now with the ventilation start time set press the I O button The word OFF should appear to the right of the time and the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs W...

Page 9: ...times before the high efficiency filter requires replacement Be careful not to damage the fabric media when handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 4 3 Optional Fresh Air Return Check and clean the screen on the outdoor fresh air return seasonally The screen may...

Page 10: ...on prevents fan impeller rotation 3 Defective fan 4 Defective fan relay 5 Defective fan capacitor Fan runs with fan switch ON Fan does not run with ventilation timer activated 1 Ventilation timer set to manual switched OFF 2 Time not correct on ventilation timer 3 Defective ventilation timer 4 Defective fan switch Evaporator coil frosted continuously low dehumidifying capacity 1 Dirty air filter s...

Page 11: ...110 volts from compressor terminal R to overload terminal 3 using an AC voltmeter If voltage is present go to step 3 If no voltage there may be a loose connection in the compressor circuit Test each component for continuity See the appropriate section if a defect is suspected 3 Unplug the unit and then disconnect the red and yellow wires from compressor terminals R S Using an ohmmeter check contin...

Page 12: ...l hole from becoming plugged A standing burn out does not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plugged Replace the suction filter drier if pressur...

Page 13: ...ventilating the structure when the unit is dehumidifying or recirculating the indoor air The electric ventilation timer operates on 24 Vac from the control circuit DO NOT connect high voltage to the damper motor or damage to the motor may result DO NOT force the blade of the damper by hand or damage to the damper motor may result If the electric ventilation damper fails to operate 1 Check that the...

Page 14: ...14 Figure 4 Electric Schematics of the DHV 150H ...

Page 15: ...15 Figure 5 Pictorial Electrical Diagrams of DHV 150H ...

Page 16: ...r 30 MFD 7 4022563 1 Condenser Coil 8 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 8 not shown 9 4022563 1 Evaporator Coil 10 4024270 1 Fan 11 4020924 1 Fan Relay SPDT 24 Vac 15A 12 4024360 1 Fan Run Capacitor 16MFD 13 4022593 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 ID x 8 15 4023875 1 Inlet Collar 10 Galvanized Steel 16 4023928 1 Inlet Collar 6 Galvanized Ste...

Page 17: ...t Damper 6 Diameter Electrically Actuated not shown 32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4020554 1 Switch Black SPDT ON OFF 37 4022486 1 Timer 7 Day 24 Vac Programmable 38 AL99982 1 Optional External Insulation Kit not shown 39 AL22023 1 6 Vent...

Page 18: ...r cause beyond American ALDES Ventilation Corporation s reasonable control Limitations and Exclusions If any American ALDES Dehumifier Dehumidifying Ventilator part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto All warranty periods shall be extended by the period of time if any that the unit is out of service while...

Page 19: ...19 Date Service Notes ...

Reviews: