background image

 

8

The ventilation timer is an electronic timer that 
displays the current time. This timer has a battery 
backup, so it will not require resetting after a power 
outage. Following a prolonged power outage the 
display of the timer will flash on and off indicating a 
power outage has occurred. The one-minute time 
increments of the ventilation timer allow you to 
program the ventilation of your home to fit your 
schedule. 
 
The ventilation timer has six programs with each 
program having one “on” and one “off” event. A 
program allows the user to turn the ventilation on at a 
certain day and time, then it allows them to turn the 
ventilation off at a certain day and time. Each of these 
programs can be repeated daily or weekly or during a 
specified block of days. All six of the programs operate 
independently of each other. 
 
If the timer fails to operate or operates erratically, 
check that the control panel receives 24Vac from the 
DHV-150H. If 24Vac is present at the control panel, 
reset the timer by pressing the reset button at the 
bottom center of the timer face. The reset button is the 
small recessed button with an 

R

 beneath it located 

below the 

1…7

 and 

h

 buttons. Press the reset button 

in until the display clears. Release the reset button. 
The display will reappear as 00:00. Resetting the timer 
will clear the time and all program settings. After 
resetting the timer follow the instructions below to set 
the correct time and ventilation programs. 
 
The following instructions explain how to set the 
ventilation timer. First, set the correct time on the 
timer by sliding the switch in the upper right hand 
corner of the timer to the clock symbol 

 and pressing 

the 

1…7

 (DAY), 

h

 (HOUR), and 

m

 (MINUTE) buttons. 

Remember that this timer operates on a 24-hour 
(military time) clock. 
 
Next, set the ventilation time schedule. Slide the 
switch in the upper right hand corner to the program 
symbol  

P

. “ON” will appear to the right of the time and 

the number “1” will appear in the lower right hand 
corner of the display. The “1” and “ON” signify the turn 
on time for the first program. Press the 

1…7

 button to 

choose the days of the week for this program. You can 
choose Mon.-Sun, Mon.-Fri., Sat-Sun, or any single 
day of the week. The days chosen are shown along the 
top of the display on the ventilation timer. Next press 
the 

h

 button to set the hour for the start of the 

ventilation period. Remember that this timer operates 
on a 24-hour clock. Then press the 

m

 button to set the 

minutes past the hour to start the ventilation. Now, with 
the ventilation start time set; press the 

I/O

 button. The 

word “OFF” should appear to the right of the time and 
the number “1” should remain in the lower right hand 
corner of the display. The “1” and “OFF” signify the 

turn off time for the first program. Set the turn off time 
using the 

1…7

h

, and 

m

 buttons in the same way as 

described above and continue on to the second 
through sixth programs. When setting the ventilation 
programs, you can return to the current time display by 
sliding the switch in the upper right corner of the timer 
to RUN. The slide switch in the upper right must be set 
to 

RUN

 for the timer to operate with the scheduled 

programs. 
 
The slide switch in the upper left of the timer is used to 
choose between automatic and manual operation of 
the timer relay. When the slide switch in the upper left 
of the timer is set to AUTO mode, the central 
conditioning unit will ventilate when the scheduled 
programs call for ventilation. When the slide switch in 
the upper left of the timer is set to manual (set to hand 
symbol on the right), the operation of the timer is 
controlled by the 

I/O

 button only. Pressing the 

I/O

 

button will switch the ventilation timer between ON 
(detent) and OFF (detent). As you press the 

I/O

 button, 

“ON” or “OFF” will be displayed to the right of the time. 
The “ON” or “OFF” to the right of the time will indicate 
if the ventilation timer is on or off. The 

I/O

 button will 

manually override scheduled programs if the timer is 
in AUTO mode. 
 

3.6 High Efficiency Air filter

 

 
An optional high efficiency air filter is available for the 
DHV-150H. ASHRAE Dust Spot Test Method 52-76 
rates this filter 90-95% efficient. This filter is much 
more efficient than the standard air filter and is able to 
catch much smaller particles that can aggravate 
allergies. 
 
The high efficiency air filter is 4 inches thick and 
should be installed in the filter enclosure directly 
behind the standard air filter (See Figure 7). The 
standard air filter will act as a prefilter for the high 
efficiency air filter and will prolong the life of the high 
efficiency air filter. 
 

3.7 Low Pressure Control 

 
If the low side refrigerant pressure drops to 15 PSIG, 
the low-pressure control opens and shuts off the 
compressor and fan. It is an automatically reset control 
that will close when the pressure rises to 35 PSIG. Its 
primary function is to prevent damage to the 
compressor if a leak develops in the refrigeration 
system. It may also open if the unit is A) installed in a 
cool area (below 50 F) or B) installed where it is below 
40 F and then started. Under these conditions, the unit 
will restart within several minutes. Until the unit warms 
up, it may repeat the cycle several times. 

Summary of Contents for DHV-150H

Page 1: ...er 13 5 8 Defrost Thermostat 13 5 9 Electric Ventilation Damper 13 5 10 Low Pressure Control 13 5 11 Condensate Pump Kit 13 6 Electrical Schematic 14 7 Pictorial Electrical Diagram 15 8 Service Parts List 16 9 The DHV 150H 16 10 Optional Parts List 17 11 Accessories 17 12 Warranty Terms 18 Serial No ________________________________ Purchase Date ____________________________ Dealer s Name _________...

Page 2: ...mmon grounded outlet on a 15 or 20 Amp circuit It draws around 12 Amps under normal operating conditions If used in a wet area pool spa room or basement prone to flooding a ground fault interrupter protected circuit is required Install the remote control panel in a central area of the structure where it will sense the relative humidity of the structure accurately Avoid installing the control panel...

Page 3: ...tructure Ducting the DHV 150H as mentioned in sections 2 4A 2 4G requires consideration of the following points Duct Sizing For total duct lengths up to 25 use a minimum 10 diameter round or equivalent rectangular For longer lengths use a minimum 12 diameter or equivalent Grills or diffusers on the duct ends must not excessively restrict airflow Isolated Areas Effective dehumidification may requir...

Page 4: ...0H in a central area of the structure Duct the supply of the DHV 150H to a 10 x 10 x 10 tee damper that is 30 open to the crawl space if desired Duct the other side of the tee to the air supply of the existing HVAC system Connect an insulated duct from outside to the 6 collar of the DHV 150H if you wish to provide optional fresh make up air 2 4F Installation in an Attic with an Existing Forced Air...

Page 5: ... the support can easily be removed Cut the strips of metal on each end and remove the support section from the cabinet This will prevent the compressor from transmitting vibration to the cabinet Make sure none of the compressor tubes are pressed against the cabinet or access panel Check that the compressor tubes are centered in the holes where they pass through the drain pan A length of 10 feet or...

Page 6: ...6 Figure 1 DHV 150H in a Basement With a Forced Air System Incorporating a Central Return Figure 2 DHV 150H in an Attic with a Forced Air System Incorporating a Central Return ...

Page 7: ...r within the living space for accurate humidity sensing 3 3 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home The dehumidifier will run continuously until the relative humidity RH is reduced to the humidity control dial setting Setting the humidity control to lower RH levels will NOT increase the unit s dehumidification rate the unit will simply run lo...

Page 8: ...lation Now with the ventilation start time set press the I O button The word OFF should appear to the right of the time and the number 1 should remain in the lower right hand corner of the display The 1 and OFF signify the turn off time for the first program Set the turn off time using the 1 7 h and m buttons in the same way as described above and continue on to the second through sixth programs W...

Page 9: ...times before the high efficiency filter requires replacement Be careful not to damage the fabric media when handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 4 3 Optional Fresh Air Return Check and clean the screen on the outdoor fresh air return seasonally The screen may...

Page 10: ...on prevents fan impeller rotation 3 Defective fan 4 Defective fan relay 5 Defective fan capacitor Fan runs with fan switch ON Fan does not run with ventilation timer activated 1 Ventilation timer set to manual switched OFF 2 Time not correct on ventilation timer 3 Defective ventilation timer 4 Defective fan switch Evaporator coil frosted continuously low dehumidifying capacity 1 Dirty air filter s...

Page 11: ...110 volts from compressor terminal R to overload terminal 3 using an AC voltmeter If voltage is present go to step 3 If no voltage there may be a loose connection in the compressor circuit Test each component for continuity See the appropriate section if a defect is suspected 3 Unplug the unit and then disconnect the red and yellow wires from compressor terminals R S Using an ohmmeter check contin...

Page 12: ...l hole from becoming plugged A standing burn out does not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plugged Replace the suction filter drier if pressur...

Page 13: ...ventilating the structure when the unit is dehumidifying or recirculating the indoor air The electric ventilation timer operates on 24 Vac from the control circuit DO NOT connect high voltage to the damper motor or damage to the motor may result DO NOT force the blade of the damper by hand or damage to the damper motor may result If the electric ventilation damper fails to operate 1 Check that the...

Page 14: ...14 Figure 4 Electric Schematics of the DHV 150H ...

Page 15: ...15 Figure 5 Pictorial Electrical Diagrams of DHV 150H ...

Page 16: ...r 30 MFD 7 4022563 1 Condenser Coil 8 4021470 1 Defrost Thermostat 4021648 1 Defrost Thermostat Mounting Clip item 8 not shown 9 4022563 1 Evaporator Coil 10 4024270 1 Fan 11 4020924 1 Fan Relay SPDT 24 Vac 15A 12 4024360 1 Fan Run Capacitor 16MFD 13 4022593 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 ID x 8 15 4023875 1 Inlet Collar 10 Galvanized Steel 16 4023928 1 Inlet Collar 6 Galvanized Ste...

Page 17: ...t Damper 6 Diameter Electrically Actuated not shown 32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4020554 1 Switch Black SPDT ON OFF 37 4022486 1 Timer 7 Day 24 Vac Programmable 38 AL99982 1 Optional External Insulation Kit not shown 39 AL22023 1 6 Vent...

Page 18: ...r cause beyond American ALDES Ventilation Corporation s reasonable control Limitations and Exclusions If any American ALDES Dehumifier Dehumidifying Ventilator part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto All warranty periods shall be extended by the period of time if any that the unit is out of service while...

Page 19: ...19 Date Service Notes ...

Reviews: