2. Electrical Service Specifications
IMPORTANT:
The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the back of the dryer, at the upper right hand corner. In the case of 208
VAC or 240 VAC, the supply voltage
must match
the electric service specifications
of the data label
exactly
.
IMPORTANT:
The wire size
must be
properly sized to handle the related current.
WARNING: 208 VAC and 240 VAC ARE
NOT
THE
SAME.
Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC
reserves the right to make changes in specifications at any time, without notice or
obligation.
M LG-82 (Gas)
M LS-82 (Steam)
E
LECTRIC
S
ERVICE
S
PECIFICATIONS
(
PER DRYER
)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTE:
A.
Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B.
Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
CIRCUIT
BREAKER
60 Hz 50 Hz
208
3ø
3
13.2
--
#14
25
240
3ø
3
12.2
14
#14
25
380
3ø
3
--
7.3
#14
15
416
3ø
3
--
7.1
#14
15
460/480
3ø
3
6.6
--
#14
15
* AWG Stranded Wire Type for individual lengths less than 100 feet (30.48 meters).