23
2. Electrical Service Specifications
IMPORTANT
: The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the left side panel area behind the top control (access) door. In the case of
208 VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label
exactly
.
WARNING
:
208 VAC AND 230/240 VAC ARE
NOT
THE
SAME.
Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE
:
ADC
reserves the right to make changes in specifications at any time without notice or
obligation.
IDG-170 (Gas)
IDS-170 (Steam)
ELECTRIC SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
: 208 VAC and 230/240 VAC
ARE NOT THE SAME
.
When ordering, specify
exact voltage
.
NOTES
: A. When fuses are used they
must be
dual element, time delay, current limiting, class RK1 or RK5
ONLY
.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes
to lised appliance amp draw data.
B. Circuit breakers are thermal magnetic (industrial) motor curve type
ONLY
. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
C . Circuit breakers for 3-phase dryers
must be
3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
208
3ø
3
30
30
*
50
60
230/240
3ø
3
29
--
*
40
60
380
3ø
3/4
--
16
*
25
30
416
3ø
3/4
--
16
*
25
30
440
3ø
3/4
15
--
*
25
30
480
3ø
3/4
15
--
*
25
30
*
AWG Stranded Type Wire...size wire as per National Electrical Code or local codes.