28
3. Piping/Connections
ALL
components/materials
must conform
to National Fuel Gas Code Specifications ANSI Z223.1-LATEST
EDITION, or in Canada, CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (liquid propane
[L.P.] Gas) or LATEST EDITION (for General Installation and Gas Plumbing), as well as local codes and
ordinances and
must be
done by a qualified professional. It is important that gas pressure regulators meet
applicable pressure requirements, and that gas meters be rated for the total amount of
ALL
the appliance
BTUs being supplied.
The dryer is provided with a 1-1/2” N.P.T. inlet pipe connection extending out the back area of the burner
box. The minimum pipe size (supply line) to the dryer is 1-1/2” N.P.T. For ease servicing, the gas supply
line of each dryer
must have
its own shutoff valve.
The size of the main gas supply line (header) will vary depending on the distance this line travels from the
gas meter or, in the case of L.P. gas, the supply tank, other gas operated appliances on the same line, etc.
Specific information regarding supply line size
should be
determined by the gas supplier.
NOTE
: Undersized gas supply piping can create a low or inconsistent pressure, which will result in
erratic operation of the burner ignition system.
Consistent gas pressure is essential at
ALL
gas connections. It is recommended that a 1-1/2” (3.18 cm)
pipe gas loop be installed in the supply line servicing a bank of dryers. An in-line pressure regulator
must
be
installed in the gas supply line (header) if the (natural) gas pressure exceeds 12.0 inches (29.9 mb) of
water column (W.C.) pressure.
NOTE
: A consistent water column test pressure of 3.5 inches (8.7 mb) for natural gas and 10.5 inches
(26.1 mb) for L.P. dryers is required at the gas valve pressure tap of each dryer for proper and
safe operation.
A 1/8" N.P.T. plugged tap, accessible for a test gauge connection,
must be
installed in the main gas supply
line immediately upstream of each dryer.
IMPORTANT
: Pipe joint compounds that resist the action of natural gas and L.P. gas
must be
used.
IMPORTANT
: Test
ALL
connections for leaks by brushing on a soapy water solution (liquid
detergent works well).
WARNING: NEVER TEST FOR LEAKS WITH A FLAME!!!
ALL
components/materials
must conform
to National Fuel Gas Code Specifications ANSI Z223.1-LATEST
EDITION, or in Canada, CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (L.P. Gas)
or LATEST EDITION (for General Installation and Gas Plumbing), as well as local codes and ordinances
and
must be
done by a qualified professional. It is important that gas pressure regulators meet applicable
pressure requirements, and that gas meters be rated for the total amount of
ALL
the appliance BTUs being
supplied.