background image

113335 - 12

www.amdry.com

11

Exhaust Transition Piece

(Gas and Electric Only!)

Inside the tumbler of this dryer is an exhaust transition piece
that must be installed on the outlet of the exhaust before any
further venting is connected:

Remove the exhaust transition piece from the tumbler and
place it on the exhaust outlet.

Using the screws provided, secure the exhaust transition
piece to the dryer.

NOTE: It is recommended that this joint be taped as well
as all other duct joints to prevent moisture and lint from
escaping into the building.

WARNING

An exhaust duct transition piece is shipped inside of the
dryer’s tumbler and 

MUST

 be installed on the dryer’s

exhaust duct, with the hardware provided, 

BEFORE

location venting is connected to the dryer.

THIS EXHAUST DUCT TRANSITION PIECE

MUST BE INSTALLED FIRST!

Failure to observe this installation requirement may result
in damage to the dryer, create a 

FIRE HAZARD

 and will

VOID

 the manufacturer’s warranty.

012999JEV-GS/cj

P/N:  114092

A

40-inches (101.6 cm) for optimum opening of load door.

B

The maximum thickness of the bulkhead is 4-inches (10.16 cm).  For electric
dryers the maximum thickness of the bulkhead is 1-inch (2.54 cm) within
3-inches (7.62 cm) from the top of the control door.

C For gas and electric dryers a minimum overhead clearance of 12-inches

(30.48 cm) is required, providing no sprinkler is located above the dryer.
For steam dryers or if a sprinkler is located above the dryer, 18-inches
(45.72 cm) is required.

D Dryer should be positioned 24-inches (60.96 cm) away from the nearest

obstruction and 36-inches (91.44 cm) is recommended for ease of
installation, maintenance, and service.

E

2-inch (5.08 cm) minimum is required for opening the control door.

F

Flooring should be level or below dryer cabinet for ease of removing panels
during maintenance.

G Dryers may be positioned sidewall to sidewall, however a 1/16” (1.5875

mm) minimum allowance must be made for the opening and closing of the
control door, along with the removal of panels during maintenance.

Even though a 12-inch (30.48 cm) clearance is acceptable,
it is recommended that the rear of the dryer be positioned
approximately 2 feet (0.61 meters) from the nearest
obstruction (i.e., wall) for ease of installation, maintenance,
and service.  Bulkheads and partitions should be made from
noncombustible materials.  The clearance between the
bulkhead header and the dryer must be a minimum of
4-inches (10.16 cm) and must not extend more than 4-inches
(10.16 cm) to the rear of the front.  The bulkhead facing must
not be closed in all the way to the top of the dryer.  A 2-inch
(5.08 cm) clearance is required.

NOTE: Bulkhead facing should not be installed until after
the dryer is in place.  Ceiling area must be located a
minimum of 12-inches (30.48 cm) above the top of the
dryer.

IMPORTANT: Even though a minimum of only 12-inches
(30.48 cm) is required, 18-inches (45.72 cm) or more is
suggested, for steam dryers and especially in cases where
sprinkler heads are over the dryers.

NOTE: When fire sprinkler systems are located above the
dryers, a minimum of 18-inches (45.72 cm) above the
dryer console (module) is suggested.  Dryers may be
positioned side wall to side wall, however, 1- or 2-inches
(2.54 or 5.08 cm) is suggested for ease of installation and
maintenance.  Allowances must be made for the opening
and closing of the control door and the lint door.

Dryer Enclosure Requirements _______

Bulkheads and partitions should be made of noncombustible
material.

NOTE: Allowances must be made for opening the control
door.

To Remove Top Console (Module)

Disconnect the ground wire (A) at the rear upper left hand
corner of dryer.

Remove the 8 sets of nuts and washers (B) holding the
console (module) to base.

Open the control door/control panel and disconnect the white
15-pin plug connector (C) (illustration below) located in the
base of the control box.

Disconnect white plug connector located outside backside
of the control box (provides power to heat circuit).

Lift the console (module) off the dryer base.

IMPORTANT: The dryer must be transported and handled
in an upright position at all times.

Summary of Contents for ML-130 III

Page 1: ...s de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareils ...

Page 2: ...___________________________________________________________________ SERIAL NUMBER S __________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ Replacement parts can be obtain...

Page 3: ...e dryer in the presence of dry cleaning fumes Dryer must not be installed or stored in an area where it will be exposed to water or weather The wiring diagram for the dryer is located in the front electrical control box area List of Acronyms _____________________ D M S Drill Measurement Size DSI Direct Spark Ignition F S S Fire Suppression System HSI Hot Surface Ignition HVAC Heating Ventilating a...

Page 4: ...r washed fabrics Do not dry articles spotted or washed in dry cleaning solvents a combustible detergent or all purpose cleaner Explosion could result Do not dry rags or articles coated or contaminated with gasoline kerosene oil paint or wax Explosion could result Do not dry mop heads Contamination by wax or flammable solvents will create a fire hazard WARNING WARNING Do not use heat for drying art...

Page 5: ...___________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ______________...

Page 6: ...APPROX NET WEIGHT 1 260 lb 571 53 kg APPROX SHIPPING WEIGHT 1 400 lb 635 03 kg AIRFLOW 60 Hz 2 150 cfm 60 88 cmm 50 Hz 1 792 cfm 50 73 cmm EXHAUST CONNECTION DIAMETER 14 35 56 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE kW Btu hr kcal hr 72 245 729 61 923 75 6 258 023 65 021 VOLTAGE AVAILABLE 208 575v 3ø 3 4w 50 60 Hz APPROX NET WEIGHT 1 421 lb 644 55 kg APPROX SHIPPING WE...

Page 7: ...113335 12 www amdry com 7 ML 130 Specifications _____________________________________________________________ ...

Page 8: ...260 lb 571 53 kg APPROX SHIPPING WEIGHT 1 400 lb 635 03 kg AIRFLOW 1 750 cfm 49 55 cmm HEAT INPUT 300 000 Btu hr 75 599 kcal hr EXHAUST CONNECTION DIAMETER 12 30 48 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION 1 F N P T VOLTAGE AVAILABLE N A APPROX NET WEIGHT APPROX SHIPPING WEIGHT AIRFLOW EXHAUST CONNECTION DIAMETER COMPRESSED AIR CONNECTION COMPRESSED AIR VOLU...

Page 9: ...113335 12 www amdry com 9 ML 130DR Specifications __________________________________________________________ ...

Page 10: ...r to Dryer Enclosure Requirements Provisions must be made for adequate clearances for servicing and for operation as noted in this manual refer to Dryer Enclosure Requirements The dryer must be installed with a proper exhaust duct connection to the outside as noted in this manual refer to Exhaust Requirements The dryer must be located in an area where correct exhaust venting can be achieved as not...

Page 11: ...closing of the control door along with the removal of panels during maintenance Even though a 12 inch 30 48 cm clearance is acceptable it is recommended that the rear of the dryer be positioned approximately 2 feet 0 61 meters from the nearest obstruction i e wall for ease of installation maintenance and service Bulkheads and partitions should be made from noncombustible materials The clearance be...

Page 12: ...ich results in slow drying increased use of energy overheating of the dryer and shutdown of the burner by the airflow sail switch burner hi limit or tumbler hi heat thermostat The dryer must be installed with a proper exhaust duct connection to the outside CAUTION This dryer produces combustible lint and must be exhausted to the outdoors Improperly sized or installed exhaust ductwork can create a ...

Page 13: ...ters or has numerous elbows the cross sectional area of the ductwork must be increased in proportion to the length and number of elbows in it IMPORTANT For extended ductwork runs the cross section area of the duct can only be increased to an extent When the ductwork approaches the maximum limits as noted in this manual a professional HVAC firm should be consulted for proper venting information Mul...

Page 14: ...rcuit The dryer must be connected with copper wire only Do not use aluminum wire which would cause a fire hazard The copper conductor wire cable must be of proper ampacity and insulation in accordance with electric codes for making all service connections NOTE The use of aluminum wire will void the warranty Wiring diagrams are affixed to the inside at the top front control door and to the rear upp...

Page 15: ...t connection is made into the terminal block located at the upper rear of the dryer refer to the illustration below For electric model dryers made to operate at 380 VAC 416 VAC 440 VAC or 480 VAC the electrical input connection is made to the oven relay located at the upper rear of the dryer refer to the illustration below Input connection wiring must be sized properly to handle the dryer s curren...

Page 16: ...or hot water pipe The grounded cold water pipe must have metal to metal connections all the way to electrical ground If there are any nonmetallic interruptions such as a meter pump plastic rubber or other insulating connectors they must be jumped out with no 4 copper wire and securely clamped to bare metal at both ends IMPORTANT For personal safety and proper operation the dryer must be grounded F...

Page 17: ... gas pressure regulators meet applicable pressure requirements and that gas meters be rated for the total amount of all the appliance Btu being supplied The dryer is provided with a 1 N P T inlet pipe connection extending out the back area of the burner box The minimum pipe size connection supply line to the dryer is 1 diameter For ease of servicing the gas supply line of each dryer must have its ...

Page 18: ...formance and can cause component failure Clean dry and regulated steam must be provided to the dryer IMPORTANT Steam coil failure due to water hammer by wet steam will void the warranty The pressure of the condensate in the steam supply line will cause water hammer and subsequent heat exchanger steam coil failure The steam supply connection into the main supply line must be made within a minimum 1...

Page 19: ...ine just before the dryer connection This is necessary to ensure that correct and clean air pressure is achieved Steam Damper System Operation The steam damper as shown in the illustration below allows the coil to stay constantly charged eliminating repeated expansion and contraction When the damper is opened the air immediately passes through the already hot coil providing instant heat to start t...

Page 20: ... marginal location installation conditions Turn on electric power to the dryer Make sure the main door is closed and the lint drawer is securely in place Refer to the Operating Instructions for starting your particular model dryer Check to ensure that the tumbler starts in the clockwise direction Additionally check the direction of the blower motor impellor fan to ensure that the blower motor impe...

Page 21: ...op during travel If either of these conditions occur the flow control must be adjusted Refer to the Cool Down Mode in bottom illustration on page 19 for air adjustment instructions Make a complete operational check of all safety related circuits i e lint drawer switch and sail switch on gas models Reversing tumbler dryers should never be operated with less than an 80 lb 36 3 kg load dry weight sin...

Page 22: ...leted and returned for each individual dryer NOTE Be sure to include the installation date when returning the warranty card s Warranty For a copy of the ADC commercial warranty covering your particular dryer s contact the ADC reseller from whom you purchased the equipment and request a dryer warranty form If the reseller cannot be contacted or is unknown warranty information can be obtained from t...

Page 23: ...exhaust ducting and remove any lint buildup Suggested Cleaning Schedule Daily beginning of each work shift Clean lint from screen Inspect lint screen and replace if torn Weekly Clean lint accumulation from lint chamber thermostat and microprocessor temperature sensor sensor bracket area Lint from most fabrics is highly combustible The accumulation of lint can create a potential fire hazard Keep dr...

Page 24: ...ing American Dryer Corporation certain information is required to ensure proper service parts information from ADC This information is on the data label located on the left side panel wall area behind the control door When contacting ADC please have the model number and serial number available 1 Model Number Describes the size of the dryer and the type of heat gas electric or steam 2 Serial Number...

Page 25: ...trials If the flame is not sensed at the end of the third retry trial inter purge period of 30 seconds the DSI module will LOCKOUT L E D diagnostic indicator flashes A steady L E D indicator indicates normal operation No L E D indicator indicates a power or an internal failure has occurred For Models with DSI Module Type II Theory of Operation Start the drying cycle When the gas burner ignites wit...

Page 26: ...TANT It is your responsibility to have all plumbing connections made by a qualified professional to ensure that the plumbing installation is adequate and conforms to local state and federal regulations or codes It is the installer s or owner s responsibility to see that the necessary or required water water pressure pipe size or connections are provided The manufacturer assumes no responsibility i...

Page 27: ...ill be inoperative WARNING Notes ______________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ _______...

Page 28: ...ADC Part No 113335 12 07 31 08 5 ...

Reviews: