background image

Power Off All Devices & Install Storm Trapper

1

2

 

WARNING:

 If wires are to be buried or covered, use conduit to protect the wires.

(Continued on back)

The following procedures are general steps for a typical installation. For additional information, please contact Technical 

Support at 1-800-229-3404 or support@aiworldwide.com. 

1

 

Ensure power has been terminated on rectifier and all devices.

2

  Install 

Storm Trapper HE Surge Arrester

 on 

AC

 input:

a

  Install black leads across 

Line 1 and Line 2 

of rectifier’s 

AC

 input. 

These lines should be routed to the breaker.

b

  Connect white lead to rectifier chassis.

NOTE:

 If an arrestor is already installed on the 

AC

 input, then install the 

Storm 

Trapper HE Surge Arrester

 in parallel. Replace spade terminals with  flat 

terminals for easier connection to where existing arrester is connected.

4

 

Secure 

Storm Trapper HE Surge Arrester 

by zip-tie to suitable location or 

place on floor of rectifier.

Installing the Surge Arrester Kit 

WARNING

:

 

To prevent electrostatic discharge (ESD) damage when handling electronic equipment, always wear an anti-static 

wrist strap attached to an unpainted, grounded metal object. Ensure the wrist strap has maximum contact with bare skin. 

Install DC Lightning Arrestor & Surge Detector

1

 

Attach 

DC Lightning Arrestor

’s black leads

 

to rectifier 

DC

 outputs. 

2

 Thread 

DC Lightning Arrestor’

s white wire through the hole (marked 

Pulse

) on 

the 

Surge Detector’

s current transformer.

3

  Connect a spade connector (included in kit) to the end of the 

DC Lightning 

Arrestor

’s white wire and connect to common ground location.

4

  Wire and connect the 

Surge Detector

 to the Bullhorn RMU’s digital 

Channel 5

. Be 

sure to observe proper polarity.

5

 Connect 

DC Lightning Arrestor

’s two yellow wires to Bullhorn RMU’s 

Channel 6

Polarity is not important as long as one wire is on the positive input and the other is 

on the negative input.

6

 

DC Lightning Arrestor

 

can be placed on rectifier floor or anywhere to keep the 

installation tidy.

Surge Detector

DC Lightning Arrestor

Storm Trapper HE

Surge Arrester

NOTE:

 For rectifier types other than 

JA 

— 

If a non-Delta high energy surge arrestor is already installed on the 

AC

 input, you 

do not

 need to install the 

Storm Trapper HE Surge Arrester

.

RM4010

Installation and Configuration

Quick Reference Guide

Part No. 122248-000 Rev. 1

1 of 2

April 2020

Required Tools

Lightning Arrester Surge Kit

Quick Reference Guide

 

Field Update Tool (FUT)

 

Windows

®

 Laptop PC

 

USB Mini-b cable

 

Bullhorn

®

 Tools configuration software

 

Installation tools

Optional Items

 

Hook-up wire for field installation

 

Ground rod and copper wire

Reviews: