PROGRAMMING
7
Ex2: If the flashing value is set to 100P (100%), the door frame heater will run continuously.
run for 2 minutes and it will be off for
: Do not set Door Frame Heater Percent to 0P (0%) unless you want to turn the door frame heater
off.
Ex3: If the flashing value is set to 0P (0%), the door frame heater will not run at all.
Ex4: If the flashing value is set to 50P (50%), the door frame heater will
2 minutes. The cycle will repeat for as long as the controller will be on.
Note
Press
when done.
larm Settings - High Air Alarm
A
The display will show:
(Default value for freezers)
(Default value for coolers)
Press
or
to change the flashing value representing degrees Fahrenheit. If the air temperature
goes above this set point, the alarm will go off.
Press
when done.
Alarm Settings - Low Air Alarm
(Default value for coolers)
(Default value for freezers)
The display will show:
Press
or
to change the flashing value representing degrees Fahrenheit. If the air temperature
goes below this set point, the alarm will go off. You can set low air alarm anywhere between -30
0
F and 50
0
F.
Press
when done.