background image

© 2008 Trane

18-GE10D1-4

Installer’s Guide

6. It is recommended that the outline drawing be stud-

ied and dimensions properly noted and checked
against selected installation site. By noting in ad-
vance which knockouts are to be used, proper clear-
ance allowances can be made for installation and fu-
ture service.

7. Allow a 

minimum of 21 inches clearance

 in front

of the air handler to permit removal of COLLEC-
TION CELL and FIELD CHARGER.

8. Do not install air handler where air cleaner can be

exposed to UV light.

9. When the air handler with supplementary heater is

to be installed in the downflow position on combus-
tible flooring an accessory sub-base (TAYBASE101
for 2/4TEE3D31, TAYBASE100 for 2/4TEE3D37,
TAYBASE102 for 2/4TEE3D40-65) must be used.
See Figure 1.

10. If supplementary heat is to be added, power supply

must be sufficient to carry the load. In addition,
minimum airflow settings, unit and duct clearances
to combustible material must be maintained as
stated on the air handler rating nameplate.

CAUTION

!

For air handlers not equipped with a factory installed
electric heater, a field installed heater is available from
Trane. Only heaters built by Trane are approved for use
in the air handler. These heaters have been designed
and tested in accordance with UL standards to provide
safe and reliable operation. A list of approved heaters
is provided on the air handler rating nameplate. Heat-
ers that are not factory approved could cause damage
and are not covered under equipment warranty.

NOTE: If air handler is used WITHOUT a supplemen-
tary electric heater, a sheetmetal plate is required to
cover the open hole in the airflow system. See Figure
3

.

These air handlers are suitable for installation in a
closet, alcove or utility room with free, non-ducted, air
return, using the area space as a return air plenum.
With ducted supply air, if the minimum clearances to
combustible materials and service access are observed,
the above installations are suitable.

This area may also be used for other purposes, includ-
ing an electric hot water heater- 

but in no case shall

a fossil fuel device be installed and/or operated in
the same closet, alcove or utility room.

In addition, these air handlers are suitable for installa-
tion in an attic, garage or crawl space with ducted sup-
ply and return air.

This equipment has been evaluated in accordance with
the U.S. Department of Housing and Urban Develop-
ment code.  Air handler is Suitable for mobile home/
manufactured housing use.  Unit is also approved for
modular homes.

For proper installation the following items must be con-
sidered:

1. If adequate power is available and correct according

to nameplate specifications.

 2. 

Prior to unit installation, a heavy gauge steel

plate is attached to the bottom of the unit for
protection during shipping and handling.
Leave this plate in place until the unit is
ready to be connected to ductwork.

3. Insulate all ducts, particularly if unit is located out-

side of the conditioned space.

4. Pursuant to Florida Building Code 13-610.2.A.2.1,

this unit meets the criteria for a factory sealed
air handler.

5. To ensure maximum efficiency and system perfor-

mance, the existing supply and return duct system
static pressures must not exceed the total available
static pressure of the air handler. Reference ACCA
Manual D, Manual S and Manual RS along with the
air handler Product Data and Service Facts for addi-
tional information.

FLOOR OPENING - SIZE

 MODEL NO.

A

B

 TAYBASE100

23-3/4

14-13/16

 TAYBASE101

21-3/4

14-13/16

 TAYBASE102

26-3/4

14-13/16

AIR HANDLER SUB-BASE

Figure 1

Summary of Contents for 2TEE3D31A1000A

Page 1: ...r local distributor or the manufacturer as listed on the air handler name plate These Air Handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertibl...

Page 2: ...rs are suitable for installation in a closet alcove or utility room with free non ducted air return using the area space as a return air plenum With ducted supply air if the minimum clearances to comb...

Page 3: ...d to and claims made against the transporta tion company immediately Check to be sure all major components are in the unit Any missing parts should be reported to your supplier at once and replaced wi...

Page 4: ...that do not have a grill or return air duct installation will re quire the use of either BAYPLNM120 TASB215 TASB235 or TASB260 depending on cabinet size TASB accessories can be purchaed from Miami Tec...

Page 5: ...flow Ionizing pins must face downward into the return air stream and electrical contacts must be on the left side of the unit n Reinstall FIELD CHARGER retainer bracket o Install COLLECTION CELL as sh...

Page 6: ...GE10D1 5 Installer s Guide Figure 8 FIELD CHARGER Removal Figure 6 COLLECTION CELL Removal Figure 7 FIELD CHARGER Retainer Bracket Removal Figure 10 Drip Pan Foam Removal Figure 9 Protector Plate Rem...

Page 7: ...e of the drain pan See Figure 14 Fill the bend in the baffle which fits the in ner edge of the drain pan with non acetic acid RTV type adhesive sealant before installing the baffle Ensure sealant is d...

Page 8: ...cal contacts and ac tuator tab are on the right side of the unit t Install filter panel with thumbscrews u Openings where field wiring enters the cabinet must be completely sealed Location of power en...

Page 9: ...15 CAUTION When installing the narrow coil baffle make sure to align the baffle up with the holes so NOT to puncture the coil tubing f The coil is then inserted back into the cabinet on the opposite...

Page 10: ...he front of the unit to re move d Unit is shipped from the factory in the upflow or horizontal right configuration Unit conversion is not required e If the unit is suspended it must be supported from...

Page 11: ...NFLOW UPFLOW Actuator Tab Actuator Tab Electrical Contacts Electrical Contacts Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL Figure 18 COLLECTION...

Page 12: ...ttom side Electrical Contacts on Bottom side Electrical Contacts on Bottom side FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL HORIZONTAL RIGHT Actuator Tab Electrical Contacts Electrical...

Page 13: ...e made outside the cabinet NOTE TXV bulb MUST be protected wrap a wet rag around the suction line between the TXV bulb and the braze joint or removed while brazing the tubing Over heating of the sensi...

Page 14: ...t a clean out tee or cross be installed in the primary drain line for future main tenance See Figures 22 23 4 Do not use reducing fittings in the condensate drain lines 5 Slope the drain lines downwar...

Page 15: ...onnectors are provided for use with supplementary heaters IMPORTANT When supplementary heaters are installed inspect to insure that all packaging material has been removed J AIRFLOW ADJUSTMENT CAUTION...

Page 16: ...shock do not perform any servicing other than that contained in these operating instructions unless you are qualified to do so NOTE System Information Before cleaning the coil or ducts in the air hand...

Page 17: ...Push a block of foam down over the FIELD CHARGER Pin as in Figure 28 6 Rotate the foam block on the FIELD CHARGER Pin See Figure 29 7 Use the foam block to clean the faceplate opening edges 8 Repeat...

Page 18: ...R HANDLER AIR HANDLER 2 STAGE 2 STAGE AIR CONDITIONER AIR CONDITIONER COMFORT CONTROL COMFORT CONTROL 2 STAGE HEAT 2 STAGE HEAT 1 STAGE COOL 1 STAGE COOL VARIABLE SPEED VARIABLE SPEED AIR HANDLER AIR...

Page 19: ...ORT COMFORT CONTROL CONTROL VARIABLE SPEED VARIABLE SPEED AIR HANDLER AIR HANDLER HEAT PUMP HEAT PUMP O D SECTION O D SECTION SINGLE SPEED SINGLE SPEED 2 4TEE3D31 37 40 49 65A AIR HANDLERS WITH SINGLE...

Page 20: ...20 18 GE10D1 5 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3D31 37 40 49 65A1000A From Dwg D802101 Rev 5...

Page 21: ...Installer s Guide H W 21 0 2 4TEE3D31 37 40 49 65A AIR HANDLER DIMENSIONAL DATA Model No H W 2 4TEE3D31A 43 00 21 50 2 4TEE3D37A 45 00 23 50 2 4TEE3D40A 51 75 26 00 2 4TEE3D49A 57 90 26 00 2 4TEE3D65...

Page 22: ...22 18 GE10D1 5 Installer s Guide EXPLODED VIEW From Dwg D802038g05 Rev 11...

Page 23: ...ly for correct requirements per unit nameplate 8 Inform owner of proper procedure for cleaning COLLECTION CELL 9 Energize the system and carefully observe its opera tion make any necessary adjustment...

Page 24: ...TX 75707 For more information contact your local dealer distributor 02 08 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design an...

Reviews: