background image

18-GE06D1-4

5

Installer’s Guide

b. Remove the factory installed baffle assembly

from the apex of the coil by using a 5/16"
nutdriver to remove the screw. Replace this
baffle with the factory supplied narrow coil baffle
using the screws removed previously. See Figure
10. Reinstall coil assembly.

CAUTION

!

When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.

NOTE: Installation of the downflow baffle kit included
with unit is required on downflow applications. See
Figure 9.

c. Remove front shield by removing screws on

right side. Make sure to reinstall front shield af-
ter baffle changes. See Figure 9.

d. Remove the front triangular baffle from the coil

and install the 1/2" wide gasket provided per Fig-
ure 9. Trim the gasket length to fit the baffle. Re-
install the baffle to coil, with gasket material
compressed against the coil.

e. Install the water blow-off baffles provided on each

side of the coil with the flange at the top as
shown in Figure 9. The bottom of the baffle is to
be as close to the bottom of the coil as possible.

f. Install the 7/8" wide gasket in each side of the

drain pan as shown in Figure 9 (sect. X-X).

g. The 5 ton model (2/4TEE3D62) requires 2 water

diverter baffles to be placed underneath the coil
on the inside edge of the drain pan. See Figure 9.
Fill the bend in the baffle which fits the inner
edge of the drain pan with RTV type adhesive/
sealant before installing the baffle.

h. The unit is then placed with the blower side

down and the coil is replaced on the coil channel
supports with the drain connections at the bot-
tom. The unit is now in downflow position with
front access. Do not reattach coil support tab.

i. When supplementary heaters are used, accessory

subbase (TAYBASE102 for 2/4TEE3F62) must be
used. See Figure 1.

j. If a return duct is connected to the air handler, it

must be the same dimensions as the return
opening shown in the outline drawing on page
13.

k. Openings where field wiring enters the

cabinet must be completely sealed. Location
of power entry is shown on the outline drawing.
Use 2.5" clear stickers provided to seal all unused
electrical knockouts. See Figure 8.

l. After ductwork connections are made, seal air-

tight and per Local codes.

HORIZONTAL LEFT

 

a. For maximum efficiency and Customer ease of

filter maintenance, it is recommended that a
properly sized remote filter and grille be in-
stalled for horizontal applications. Airflow should
not exceed the face velocity of the filter being
used.  The factory installed filter should
then be removed from the unit
.

b. To convert the unit to horizontal left, front ac-

cess, slide the coil out on the coil channel sup-
ports and rotate the complete coil 180 degrees.

c. Remove the factory installed baffle assembly

from the apex of the coil by using a 5/16"
nutdriver to remove the hex head screw. There
is a coil support tab at the top of the coil con-
nected to the case must be removed first. Re-
place this baffle with the factory supplied narrow
coil baffle using the screws removed previously.
See Figure 10.

d. The coil is then inserted back into the cabinet on

the opposite side coil channel supports. The unit
is now horizontal left with front access. Do not
reattach coil support tab.

e. If the unit is suspended, it must be supported

from the bottom near both ends as well as the
middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup-
ported along the length of the front and back
with rails, the air handler only needs to be sus-
pended at both ends. See Figure 11.

Figure 8

Electrical Knockout Sticker Sheet

Summary of Contents for 2TEE3F62A1000A

Page 1: ...or or the manufacturer as listed on the air handler nameplate These air handlers are shipped from the factory in the upflow or horizontal right configuration and are fully convertible to downflow or h...

Page 2: ...aintained as stated on the air handler rating nameplate 10 If the unit is installed without a return air duct ap plicable local codes may limit this air handler to in stallation only in a single story...

Page 3: ...ater or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing 12 Make sure there are provisions...

Page 4: ...enough to support the total weight must be pro vided Provide a minimum height of 14 inches for proper unrestricted airflow d If a return air duct is connected to the air han dler it must be the same d...

Page 5: ...tab i When supplementary heaters are used accessory subbase TAYBASE102 for 2 4TEE3F62 must be used See Figure 1 j If a return duct is connected to the air handler it must be the same dimensions as th...

Page 6: ...n on the outline drawing Use 2 5 clear stickers provided to seal all unused electrical knockouts See Figure 8 k After ductwork connections are made seal air tight and per Local codes HORIZONTAL RIGHT...

Page 7: ...outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers provided to seal all unused...

Page 8: ...tion is the primary drain See Figure 14 3 4 NPT Secondary drain connection 3 4 NPT Primary drain connection Figure 14 BRAZE SHIELD Figure 13 Two secondary drain connections are provided for the differ...

Page 9: ...of the cross brace in the center of the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat...

Page 10: ...size tons cooling airflow adjustment Fan off delay options and heating airflow adjustment The switches appear as shown in Figure 18 If the airflow needs to be increased or decreased see the Airflow La...

Page 11: ...GLE SPEED AIR HANDLERS WITH 2 STAGE HEAT PUMP 2 STAGE HEAT AUTOMATIC OR MANUAL CHANGE OVER COMFORT CONTROL From Dwg 21B801073 COMFORT CONTROL AUTO 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER...

Page 12: ...CONTROL MANUAL 2 STAGE HEAT 2 STAGE COOL VARIABLE SPEED AIR HANDLER COOLING O D SECTION SINGLE SPEED COOLING O D SECTION SINGLE SPEED AIR HANDLER WITH 2 STAGE COOLING UNIT 2 STAGE HEAT AUTOMATIC CHANG...

Page 13: ...18 GE06D1 4 13 Installer s Guide OUTLINE DRAWING FOR 2 4TEE3F62...

Page 14: ...14 18 GE06D1 4 Installer s Guide 2 4TEE3F62 AIR HANDLERS H W 21 0 Model No H W 2TEE3F62A1000A 62 75 24 4TEE3D62B1000A 62 75 24...

Page 15: ...ed against the following checklist 1 Make sure power is OFF at power disconnect switch 2 Check all field wiring for tight connections See that grounding of unit is in accord with code 3 Make sure unit...

Page 16: ...ntinuous product and product data improvement it reserves the right to change design and specifications without notice American Standard Inc 6200 Troup Highway Tyler TX 75707 For more information cont...

Reviews: