background image

Page B-651-438

15

Service Facts

*DY080R9V3W - FURNACE COOLING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

OUTDOOR

UNIT SIZE

(TONS)

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW  1

SW  2

SW  3

SW  4

0.1

0.3

0.5

0.7

0.9

2.0

LOW

(350 CFM/TON)

ON

ON

OFF

ON

CFM

WATTS

700

95

700
105

700
115

680
200

670
235

NORMAL

(400 CFM/TON)

ON

ON

OFF

OFF

CFM

WATTS

800
130

800
160

800
205

790
245

740
265

HIGH

(450 CFM/TON)

ON

ON

ON

OFF

CFM

WATTS

900
160

900
215

900
255

900
300

750
270

2.5

LOW

(350 CFM/TON)

OFF

ON

OFF

ON

CFM

WATTS

875
145

875
185

875
240

875
280

760
270

NORMAL

(400 CFM/TON)

OFF

ON

OFF

OFF

CFM

WATTS

1000

205

1000

265

1000

310

1000

340

800
295

HIGH

(450 CFM/TON)

OFF

ON

ON

OFF

CFM

WATTS

1150

295

1150

340

1150

385

1020

350

800
300

3.0

LOW

(350 CFM/TON)

ON

OFF

OFF

ON

CFM

WATTS

1050

235

1050

295

1050

340

1010

350

800
290

NORMAL

(400 CFM/TON)

ON

OFF

OFF

OFF

CFM

WATTS

1200

335

1200

385

1200

410

1040

365

840
310

HIGH

(450 CFM/TON)

ON

OFF

ON

OFF

CFM

WATTS

1350

455

1350

480

1210

435

1070

390

900
345

 NOTES:   * First letter may be "A" or "T"
 1. At continuous fan setting: Heating or Cooling airflows are approximately 50% of selected cooling value.
 2. LOW airflow (350 cfm/ton) is COMFORT & HUMID CLIMATE setting;
     NORMAL airflow (400 cfm/ton) is typical setting;
     HIGH airflow (450 cfm/ton) is DRY CLIMATE setting.

*DY080R9V3W FURNACE HEATING AIRFLOW (CFM) AND POWER (WATTS) VS. EXTERNAL STATIC PRESSURE WITH FILTER

1st STAGE CAPACITY =

2nd STAGE CAPACITY =

49,000
73,000

AIRFLOW

SETTING

DIP SWITCH SETTING

EXTERNAL STATIC PRESSURE

SW 7

SW 8

0.1

0.3

0.5

0.7

0.9

HEATING

1ST

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

800

56

130

800

56

170

800

56

210

790

56

245

-

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

900

49

162

900

49

210

900

49

260

900

49

295

-

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

1000

44

205

1000

44

265

1000

44

310

1000

44

345

800

56

295

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1170

38

305

1170

38

350

1170

38

400

1020

44

360

830

54

310

HEATING

2ND

STAGE

LOW

ON

ON

CFM

TEMP. RISE

WATTS

1150

60

285

1150

60

345

1150

60

385

1020

67***

360

830

83***

305

MEDIUM LOW

OFF

ON

CFM

TEMP. RISE

WATTS

1275

54

380

1275

54

445

1200

57

425

1040

66***

380

900

76***

350

NORMAL **

ON

OFF

CFM

TEMP. RISE

WATTS

1430

48

515

1340

51

490

1220

56

455

1090

63

410

930

74***

380

HIGH

OFF

OFF

CFM

TEMP. RISE

WATTS

1430

48

515

1340

51

490

1220

56

455

1090

63

410

930

74***

380

 NOTES:   * - First letter may be "A" or "T"
  ** Factory setting
  *** Above MAX Temperature change value

Summary of Contents for ADY060R9V3W

Page 1: ... is to remain with this unit Please return to service information pack upon completion of work DISCONNECT POWER BEFORE SERVICING WARNING UY060R9V3W Upflow Horizontal 39 000 37 000 60 000 56 000 35 65 DIRECT 10 x 8 1 Variable See Fan Performance Table 1 2 Variable 115 1 60 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Yes High Velocity 1 17x25 1 in 2 Round Aluminized Steel Type I 20 3 4...

Page 2: ...0 Yes High Velocity 2 16x20 1 in 3 Round Aluminized Steel Type I 20 6 45 6 56 Redundant Two Stage Hot Surface Igniter Multiport Inshot 6 115 1 60 15 2 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 206 196 DY100R9V4W Downflow Horizontal 65 000 60 000 100 000 94 000 35 65 DIRECT 10 x 10 1 Variable See Fan PerformanceTable 3 4 Variable 115 1 60 Centrifugal Direct Variable 1 50 5000 33 110 3 60 180 1 0 Ye...

Page 3: ... an electrical shock fire injury or death CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connecte...

Page 4: ...ced draft blower is switched to low speed and de energized after the post purge timer has expired The indoor blower motor will continue to operate after the flames are extinguished and then is switched to low heat speed for the FAN OFF period WARNING Should overheating occur or the gas supply fail to shut off shut off the gas valve to the unit before shutting off the electrical supply Failure to f...

Page 5: ...lean burners remove burner box cover 6 to 8 screws and top burner bracket Lift burners from orifices NOTE Be careful not to break igniter when removing burners Clean burners with brush and or vacuum cleaner Reas semble parts by reversal of the above procedure The burner box must be resealed when replacing box cover NOTE On LP propane units some light yellow tipping of the outer mantle is normal In...

Page 6: ...6 Page B 651 438 Service Facts UY WIRING DIAGRAM ...

Page 7: ...Page B 651 438 7 Service Facts UY SCHEMATIC DIAGRAM ...

Page 8: ...8 Page B 651 438 Service Facts DY WIRING DIAGRAM ...

Page 9: ...Page B 651 438 9 Service Facts DY SCHEMATIC DIAGRAM ...

Page 10: ... OFF CFM WATTS 1325 360 1325 425 1300 460 1175 425 1000 365 NOTES First letter may be A or T 1 At continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY060R9V3W FURNACE HEATING AIRFLOW CFM AND POWER WA...

Page 11: ...OW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 750 84 750 122 750 154 720 185 710 221 NORMAL 400 CFM TON ON ON OFF OFF CFM WATTS 840 109 840 146 840 181 840 226 820 264 HIGH 450 CFM TON ON ON ON OFF CFM WATTS 940 136 940 177 940 215 940 274 940 318 2 5 LOW 350 CFM TON OFF ON OFF ON CFM WATTS 850 113 850 150 ...

Page 12: ...N OFF OFF ON OFF CFM WATTS 1847 630 1863 735 1816 780 1687 720 1532 665 NOTES First letter may be A or T 1 At Continuous fan setting Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY100R9V4W FURNACE HEATING AIRFLOW CFM ...

Page 13: ...g Heating or Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting UY120R9V5W FURNACE HEATING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER 1st Stage Capacity 2nd Stage Capacity 74 000 112 000 AIRFLOW SETTING DIP SW...

Page 14: ...FLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 1 5 LOW 350 CFM TON OFF OFF OFF ON CFM WATTS 525 45 525 70 525 100 525 135 525 160 NORMAL 400 CFM TON OFF OFF OFF OFF CFM WATTS 600 55 600 85 600 120 600 150 600 185 HIGH 450 CFM TON OFF OFF ON OFF CFM WATTS 675 65 675 105 625 140 675 175 675 205 2 0 LOW 350 CFM TON ON ON OFF ON CFM WATTS 700 70 700 11...

Page 15: ... Cooling airflows are approximately 50 of selected cooling value 2 LOW airflow 350 cfm ton is COMFORT HUMID CLIMATE setting NORMAL airflow 400 cfm ton is typical setting HIGH airflow 450 cfm ton is DRY CLIMATE setting DY080R9V3W FURNACE HEATING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER 1st STAGE CAPACITY 2nd STAGE CAPACITY 49 000 73 000 AIRFLOW SETTING DIP SWITCH SETTING ...

Page 16: ...TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 2 5 LOW 350 CFM TON ON ON OFF ON CFM WATTS 870 100 885 140 887 185 881 230 876 270 NORMAL 400 CFM TON ON ON OFF OFF CFM WATTS 989 120 1018 180 1016 230 1012 285 999 325 HIGH 450 CFM TON ON ON ON OFF CFM WATTS 1124 175 1139 225 1130 275 1135 335 1135 390 3 0 LOW 350 CFM TON OFF ON OFF ON CFM WAT...

Page 17: ...ing DY120R9V5W FURNACE COOLING AIRFLOW CFM AND POWER WATTS VS EXTERNAL STATIC PRESSURE WITH FILTER OUTDOOR UNIT SIZE TONS AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL STATIC PRESSURE SW 1 SW 2 SW 3 SW 4 0 1 0 3 0 5 0 7 0 9 3 5 LOW 350 CFM TON OFF ON OFF ON CFM WATTS 1225 240 1225 280 1225 340 1225 400 1225 450 NORMAL 400 CFM TON OFF ON OFF OFF CFM WATTS 1400 310 1400 390 1400 470 1400 520 1400 570 ...

Page 18: ...ONTROL GREEN STATUS LED FLASH CODES Flashing Slow Normal No call for Heat Flashing Fast Normal Call for Heat Fault Code Reset The last 4 fault codes can be erased from memory by power ing up the control with G energized and then applying R to the W1 terminal 3 times within 6 seconds The control will acknowledge the reset by turning on the red LED for 2 seconds FAULT CODE RECOVERY On power up last ...

Page 19: ...Page B 651 438 19 Service Facts NOTES ...

Page 20: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75707 Formoreinformationcontact yourlocaldealer distributor ...

Reviews: