background image

10

18-HE58D1-3

Installer’s Guide

START-UP AND CHECK OUT PROCEDURE

1.

Make sure power is disconnect by unplugging electri-
cal  cord.

2.

Check field-supplied control wiring to insure proper
installation and that all connection are tight.

3.

Check field-supplied power supply for proper voltage

4.

Make sure that unit is securely mounted or sus-
pended and that there are no tools or loose debris in,
around or on top of the unit

5.

Check all duct connection to insure they are sealed

6.

Check all duct outlets. All outlets must be open

7.

Check unit filters.

8.

Close unit door – plug in unit.

9.

Turn all controls to off

10. Set timer to 10 %; unit should start and run for

approximately six minutes.

11.  Go to outside of building and check for airflow at inlet

and outlet hoods.  Check that weatherhood screens
are in place and clean.  Make sure that the intake
hood is positioned away from any exhausts or other
sources of pollutants.  The quality of the intro-
duced fresh air is the most important function
of this system!

12. If the unit has a push-button timer installed press it

one time after the unit has cycled off from the percent-
age timer’s cycle. Unit should run twenty minutes and
then cycle off.

13. Set percent timer to recommended percentage. (See

application guide) Place peel & stick dot on the face of
the percentage timer to indicate percentage proper
setting.

14. Instruct end user on proper operation procedures and

leave use and care manual with them.

Summary of Contents for AERVR100A9P00A

Page 1: ...ION NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE CAUTION To prevent shortening its service life the ERV should not be used during the finishing phases of construction Compounds used in c...

Page 2: ...uctural alterations necessary for installation must comply with all applicable building health and safety code requirements ERV LOCATION CONSIDERATIONS Select a location to install the ERV with the ob...

Page 3: ...S Access Door Swings Open Down The unit may be fastened directly to floor joists using the hanging bracket and integral flange Mount as described for installation on a concrete foundation wall except...

Page 4: ...The unit may be installed in a variety of positions EXCEPT as noted in Figure 6d APPROVED MOUNTING POSITIONS HINGE HINGE Figure 6a Hinges on Bottom HINGE HINGE Figure 6b Hinges on Right HINGE HINGE Fi...

Page 5: ...fan power humidifier Do not install a by pass humidifier as it can freeze based on the installation outdoor temperature and homeowner thermostat setback requirements APPROVED INSTALLATIONS I Separate...

Page 6: ...ing flexible duct band or tape the inner duct liner to the inner flange of appropriate collar Drive a sheet metal screw through the liner to secure the duct spiral wire to the collar Straighten insula...

Page 7: ...tall hood and ductwork through penetration See figure 13 for sealing duct penetration and duct collar Fill and seal COMPLETELY with Expanded Foam Figure 13 DUCTWORK CONNECTING ERV TO INDOOR TERMINATIO...

Page 8: ...ble from your local distributor MicroSoft Excel is required to run this program The calculator input can accept a minimum ventilation airflow requirement per local code or calculate the minimum airflo...

Page 9: ...ain and the unit will run 40 minutes A third press provides for 60 minutes of operation Percent Timer Control does not need to be on for the PB Control to operate the ERV unit You can cancel a cycle a...

Page 10: ...o 10 unit should start and run for approximately six minutes 11 Go to outside of building and check for airflow at inlet and outlet hoods Check that weatherhood screens are in place and clean Make sur...

Page 11: ...18 HE58D1 3 11 Installer s Guide...

Page 12: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75711 Formoreinformation...

Reviews: