78
18-CE12D1-1D-EN
1.
Slide PVC through vent outlet adaptor and insert into inducer
outlet.
2.
Twist to insure PVC is fully inserted.
3.
Tighten the two clamps.
4.
Install the combustion air inlet pipe.
Note:
The vent outlet adapter is used for strain relief against the
weight of the venting. The clamp should be tightened after the
internal connection is made.
Note:
If required, transition to larger venting within 2' of the cabinet.
An 2" x 3" offset coupling is required if the transition is made in
a horizontal plane. Use coupling CPL00938 (Canadian
applications may use BAYREDUCE to meet ULC-S636
requirements.) See Horizontal Venting section for proper
orientation of 2” x 3” offset coupling.
1.
Connect PS2 tubing to switch and sensing location.
Important:
Trim the PS2 pressure switch tubing to length to ensure
there is no sag or trap created
2.
Remove port cap at bottom of inducer and connect inducer
condensate tubing. Connect other end of inducer condensate
tubing to top port on the condensate trap. Cut tubing to length, if
necessary.
3.
Install previously removed port cap onto bottom port of the
inducer. (As viewed in upflow)
4.
Connect condensate pressure switch tubing to pressure port on
the condensate trap.
Important:
Trim the condensate pressure switch tubing to
length to ensure there is no sag or trap created.
5.
Remove port plug from rain gutter and install in new position on
opposite side of the rain gutter.
6.
Connect rain gutter condensate hose to the rain gutter and the
lower port of the condensate trap. Cut to length, if necessary.
3
4
2
5
6
1