Service Facts

PERIODIC SERVICING REQUIREMENTS

1. GENERAL INSPECTION — Examine the furnace

installation annually for the following items:

a. All flue product carrying areas external to the furnace

(i.e. chimney, vent connector) are clear and free of
obstruction.  A vent screen in the end of the vent (flue)
pipe must be inspected for blockage annually.

b. The vent connector is in place, slopes upward and is

physically sound without holes or excessive corrosion.

c. The return air duct connection(s) is physically sound,

is sealed to the furnace and terminates outside the
space containing the furnace.

d. The physical support of the furnace should be sound

without sagging, cracks, gaps, etc., around the base so
as to provide a seal between the support and the base.

e. There are no obvious signs of deterioration of the

furnace.

2. FILTERS — Filters should be cleaned or replaced (with

high velocity filters only), monthly and more frequently
during high use times of the year such as midsummer or
midwinter.

3. BLOWERS — The blower size and speed determine the

air volume delivered by the furnace. The blower motor
bearings are factory lubricated and under normal
operating conditions do not require servicing.  If motor
lubrication is required it should only be done by a
qualified servicer.  Annual cleaning of the blower wheel
and housing is recommended for maximum air output,
and this must be performed only by a qualified servicer
or service agency.

4. IGNITER — This unit has a special hot surface direct

ignition device that automatically lights the burners.
Please note that it is very fragile and should be handled
with care.

WARNING

!

Do not touch igniter. It is extremely hot.  Failure to follow
this warning could result in severe burns.

5. BURNER — Gas burners do not normally require

scheduled servicing, however, accumulation of foreign
material may cause a yellowing flame or delayed igni-
tion. Either condition indicates that a service call is
required. For best operation, burners must be cleaned
annually using brushes and vacuum cleaner.

Turn off gas and electric power supply. To clean burners,
remove the top burner bracket. Lift burners from
orifices.

NOTE:
Be careful not to break igniter when removing burners.

Clean burners with brush and/or vacuum cleaner.
Reassemble parts by reversal of the above procedure.

NOTE:
On LP (propane) units, some light yellow tipping of the
outer mantle is normal. Inner mantle should be bright blue.

Natural gas units should not have any yellow tipped flames.
This condition indicates that a service call is required. For
best operation, burners must be cleaned annually using
brushes and vacuum cleaner.

NOTE:
On LP (propane) units, due to variations in BTU content
and altitude, servicing may be required at shorter intervals.

WARNING

!

CARBON MONOXIDE POISONING HAZARD

Failure to follow the installation instructions for the venting
system being placed into operation could result in carbon
monoxide poisoning or death.

6. HEAT EXCHANGER/FLUE PIPE — These items must

be inspected for signs of corrosion, and/or deterioration
at the beginning of each heating season by a qualified
service technician and cleaned annually for best opera-
tion. To clean flue gas passages, follow recommendations
below:

a. Turn off gas and electric power supply.

b. Inspect flue pipe exterior for cracks, leaks, holes or

leaky joints.

c. Remove burner compartment door from furnace.

d. Inspect around insulation covering flue collector box.

Inspect induced draft blower connections to the flue
pipe connection.

e. Remove burners. (See 4.)

f. Use a mirror and flashlight to inspect interior of heat

exchanger, be careful not to damage the igniter, flame
sensor or other components.

g. If any corrosion is present, contact a service agency.

Heat exchanger should be cleaned by a qualified
service technician.

h. After inspection is complete replace burners and

furnace door.

i. Restore gas supply. Check for leaks using a soap

solution. Restore electrical supply. Check unit for
normal operation.

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.

Never test for gas leaks with an open flame.  Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections.  A fire or
explosion may result causing property damage, personal
injury, or loss of life.

7. COOLING COIL CONDENSATE DRAIN — If a cooling

coil is installed with the furnace, condensate drains
should be checked and cleaned periodically to assure
that condensate can drain freely from coil to drain. If
condensate cannot drain freely water damage could
occur.  (See Condensate Drain in Installer’s Guide)

CAUTION

!

Label all wires prior to disconnection when servicing
controls.  Wiring errors can cause improper and dangerous
operation.

Verify proper operation after servicing.

Summary of Contents for TDE060A936M

Page 1: ... 1 2 H x W x D 41 3 4 x 16 1 2 x 30 1 2 119 110 TUE060A936L Upflow Horizontal 60 000 47 000 30 60 Direct 10 x 6 1 4 See Fan Performance Table 1 3 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 1 16x25 1 in 4 Round Alum Steel 20 3 45 3 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 3 115 1 60 9 0 15 1 2 H x W x D 41 3 4 x 16 1 2 x 30 1 2 127 118 TUE080A...

Page 2: ...ingle Stage Hot Surface Ignition Multiport Inshot 6 115 1 60 13 4 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 186 174 TUE080A948L Upflow Horizontal 80 000 64 000 30 60 Direct 10 x 8 1 4 See Fan Performance Table 1 3 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 1 17x25 1 in 4 Round Alum Steel 20 4 45 4 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 4 11...

Page 3: ...ee Fan Performance Table 1 2 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 2 16x20 1 in 4 Round Alum Steel Type I 20 6 45 6 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 6 115 1 60 12 8 15 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 189 176 TDE060A936M Downflow Horizontal 60 000 48 000 30 60 DIRECT 10 x 7 1 4 See Fan Performance Table 1 2 1075 115 1 60 Ce...

Page 4: ...cle When the thermostat is satisfied R and W thermostat contacts open the gas valve will close the flames will extinguish and the induced draft blower will be de energized The indoor blower motor will continue to run for the fan off period Field selectable at 60 100 140 or 180 seconds then will be de energized by the control module CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outli...

Page 5: ...E On LP propane units some light yellow tipping of the outer mantle is normal Inner mantle should be bright blue Natural gas units should not have any yellow tipped flames This condition indicates that a service call is required For best operation burners must be cleaned annually using brushes and vacuum cleaner NOTE On LP propane units due to variations in BTU content and altitude servicing may b...

Page 6: ...6 Page B 635 422 Service Facts WIRING DIAGRAM continued on next page From Dwg D341828 Rev 1 ...

Page 7: ...Page B 635 422 7 Service Facts SCHEMATIC DIAGRAM From Dwg D341828 Rev 1 ...

Page 8: ...8 Page B 635 422 Service Facts continued on next page WIRING DIAGRAM From Dwg D341830 Rev 1 ...

Page 9: ...Page B 635 422 9 Service Facts SCHEMATIC DIAGRAM From Dwg D341830 Rev 1 ...

Page 10: ...0A948L 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 1880 1662 1428 1208 1846 1635 1421 1215 1799 1598 1402 1210 1740 1551 1370 1193 1669 1493 1326 1164 1595 1424 1269 1124 1489 1345 1199 1073 1381 1256 1117 1009 1260 1157 1022 935 TUE100A960L 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 2181 1908 1621 1443 2143 1888 1609 1419 2104 1868 1597 1395 2053 1834 1582 1381 2001 1800 ...

Page 11: ... Yellow LOW Red 1767 1382 1130 840 1731 1354 1138 831 1669 1323 1115 815 1615 1292 1085 792 1546 1254 1054 762 1469 1207 1015 731 1392 1177 977 700 1300 1108 938 654 1146 1038 877 625 TDE100A960M 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 2165 1962 1705 1492 2113 1927 1688 1467 2060 1891 1671 1442 1995 1839 1636 1414 1929 1786 1600 1385 1842 1724 1547 1346 1755 1662 1492 1307 1674 158...

Page 12: ...LASH CODES Flashing Slow Normal No call for Heat Flashing Fast Normal Call for Heat Continuous ON Replace IFC Continuous OFF Check Power 2 Flashes System Lockout Retries or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure switch problem c Inducer problem 4 Flashes Open Temperature Limit Circuit 5 Flashes Flame sensed when no flame should be present 6 ...