background image

Page B-635-422

9

Service Facts

SCHEMATIC DIAGRAM

From Dwg. D341830 Rev. 1

Summary of Contents for TDE060A936M

Page 1: ... 1 2 H x W x D 41 3 4 x 16 1 2 x 30 1 2 119 110 TUE060A936L Upflow Horizontal 60 000 47 000 30 60 Direct 10 x 6 1 4 See Fan Performance Table 1 3 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 1 16x25 1 in 4 Round Alum Steel 20 3 45 3 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 3 115 1 60 9 0 15 1 2 H x W x D 41 3 4 x 16 1 2 x 30 1 2 127 118 TUE080A...

Page 2: ...ingle Stage Hot Surface Ignition Multiport Inshot 6 115 1 60 13 4 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 186 174 TUE080A948L Upflow Horizontal 80 000 64 000 30 60 Direct 10 x 8 1 4 See Fan Performance Table 1 3 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 1 17x25 1 in 4 Round Alum Steel 20 4 45 4 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 4 11...

Page 3: ...ee Fan Performance Table 1 2 1075 115 1 60 Centrifugal Direct 1 1 50 3180 115 1 60 1 09 No High Velocity 2 16x20 1 in 4 Round Alum Steel Type I 20 6 45 6 56 Redundant Single Stage Hot Surface Ignition Multiport Inshot 6 115 1 60 12 8 15 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 189 176 TDE060A936M Downflow Horizontal 60 000 48 000 30 60 DIRECT 10 x 7 1 4 See Fan Performance Table 1 2 1075 115 1 60 Ce...

Page 4: ...cle When the thermostat is satisfied R and W thermostat contacts open the gas valve will close the flames will extinguish and the induced draft blower will be de energized The indoor blower motor will continue to run for the fan off period Field selectable at 60 100 140 or 180 seconds then will be de energized by the control module CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outli...

Page 5: ...E On LP propane units some light yellow tipping of the outer mantle is normal Inner mantle should be bright blue Natural gas units should not have any yellow tipped flames This condition indicates that a service call is required For best operation burners must be cleaned annually using brushes and vacuum cleaner NOTE On LP propane units due to variations in BTU content and altitude servicing may b...

Page 6: ...6 Page B 635 422 Service Facts WIRING DIAGRAM continued on next page From Dwg D341828 Rev 1 ...

Page 7: ...Page B 635 422 7 Service Facts SCHEMATIC DIAGRAM From Dwg D341828 Rev 1 ...

Page 8: ...8 Page B 635 422 Service Facts continued on next page WIRING DIAGRAM From Dwg D341830 Rev 1 ...

Page 9: ...Page B 635 422 9 Service Facts SCHEMATIC DIAGRAM From Dwg D341830 Rev 1 ...

Page 10: ...0A948L 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 1880 1662 1428 1208 1846 1635 1421 1215 1799 1598 1402 1210 1740 1551 1370 1193 1669 1493 1326 1164 1595 1424 1269 1124 1489 1345 1199 1073 1381 1256 1117 1009 1260 1157 1022 935 TUE100A960L 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 2181 1908 1621 1443 2143 1888 1609 1419 2104 1868 1597 1395 2053 1834 1582 1381 2001 1800 ...

Page 11: ... Yellow LOW Red 1767 1382 1130 840 1731 1354 1138 831 1669 1323 1115 815 1615 1292 1085 792 1546 1254 1054 762 1469 1207 1015 731 1392 1177 977 700 1300 1108 938 654 1146 1038 877 625 TDE100A960M 4 3 2 1 HIGH Black MED HIGH Blue MED LOW Yellow LOW Red 2165 1962 1705 1492 2113 1927 1688 1467 2060 1891 1671 1442 1995 1839 1636 1414 1929 1786 1600 1385 1842 1724 1547 1346 1755 1662 1492 1307 1674 158...

Page 12: ...LASH CODES Flashing Slow Normal No call for Heat Flashing Fast Normal Call for Heat Continuous ON Replace IFC Continuous OFF Check Power 2 Flashes System Lockout Retries or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure switch problem c Inducer problem 4 Flashes Open Temperature Limit Circuit 5 Flashes Flame sensed when no flame should be present 6 ...

Reviews: