background image

4

REMOVE BOTTOM COIL 
PANEL OFF PLATE

INSTALL FRONT
COIL PANEL

Fig. 3-4 DIFFERENT AIR SUPPLY

3.2.3 CONFIGURATIONS

 Fig.3-3 Space for frame mount

≥0"

Fig. 3-5 HEATER ELEMENTS INSTALLATION

ELECTRIC HEATER KITS

Bottom Return Conversion: Divert the return air from the factory 
standard front return to a bottom return.Remove the cross brace 
when converting cabinet to bottom return.

3.3 Duct Work

3.4 Condensate Drain

Field ductwork must comply with the National Fire Protection 

Association NFPA 90A, NFPA 90B and any applicable local 

ordinance.

WARNING

Do not, under any circumstances, connect return ductwork to any 

other heat producing device such as fireplace insert, stove, etc. 

Unauthorized use of such devices may result in fire, carbon 

monoxide poisoning, explosion, personal injury or property 

damage.

Sheet metal ductwork run in unconditioned spaces must be insulated 

and covered with a vapor barrier. Fibrous ductwork may be used if 

constructed and installed in accordance with SMACNA Construction 

Standard on Fibrous Glass Ducts. Ductwork must comply with 

National Fire Protection Association as tested by U/L Standard 181 

for Class I Air Ducts. Check local codes for requirements on 

ductwork and insulation.

•    Duct system must be designed within the range of external static 

pressure the unit is designed to operate against. It is important that 

the system airflow be adequate. Make sure supply and return 

ductwork, grills, special filters, accessories, etc. are accounted for in 

total resistance. See airflow performance tables in this manual. 

•    Design the duct system in accordance with “ACCA” Manual “0” 

Design for Residential Winter and Summer Air Conditioning and 

Equipment Selection. Latest editions are available from: “ACCA” Air 

Conditioning Contractors of America, 1513 16th Street, N.W., 

Washington, D.C. 20036. If duct system incorporates flexible air 

duct, be sure pressure drop Information (straight length plus all 

turns) shown in “ACCA” Manual “D” is accounted for in system. 

•    Supply plenum is attached to the 3/4” duct flanges supplied with 

the unit. 

IMPORTANT:

 If an elbow is included in the plenum close to the unit, 

it must not be smaller than the dimensions of the supply duct flange 

on the unit.

•    IMPORTANT: The front flange on the return duct if connected to 

the blower casing must not be screwed into the area where the 

power wiring is located. Drills or sharp screw points can damage 

insulation on wires located inside unit. 

The unit is supplied with primary and auxiliary condensate drains 

that have 3/4” NPT connections. Both drains must be trapped 

outside the unit and piped in accordance with applicable building 

codes. Do not reduce the drain line size less than the connection 

size on the drain pan. Condensate should be piped to an open drain 

or to the outside. All drains must pitch downward away from the unit 

a minimum of 1/4” per foot of line to ensure proper drainage. 

Insulate the primary drain line to prevent sweating where dew point 

temperatures may be met. (Insulation is optional depending on 

climate and application needs.)

•    Secure the supply and return ductwork to the unit flanges, using 

proper fasteners for the type of duct used and tape the duct-to-unit 

joint as required to prevent air leaks.

Important: 

If cleanout Tee is used, standpipe must be sealed/capped.

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

7)0575$16)250(5

)/)86(/,1.

)0)$102725

&$3

)$1 &$3$&,725

*1'

*5281'

),(/' 32:(5 :,5,1*

*1'

9ᨺ

&20

9

9

7)05

FM

%51&

%/8

<**1'

:+,7(

<(/1

%/./

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Blue Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.
7:Factory Wires May Be Present,DO NOT USE.

ć

Top vicw of the indoor unit clearancc(including air duct).

NJ

20"

≥0"

≥24"

≥0"

Front of unit 

AIRFLOW

7)0575$16)250(5

)/)86(/,1.

)0)$102725

*1'

&20

9

9

7)05

NOTES:
1: Use Copper  Wire (75

Min) Only Between Disconnect Swicth And Unit .

2: To Be Wired In Accordance With NEC And Local Codes.
3: If Any Of The Original Wire ,As Supplied,Must Be Replaced.Use The Same

Or Equivalent Type Wire.

4: Connect R To R,G To G,Etc.See Outdoor Instruction For Details.
5: To Change Speed Tap,Move Green Wire Desird Terminal.
6: See Airflow Tables For Tap Usage.

ć

FM

<**1'

1

&

/

Summary of Contents for TMM5A0B24M21SAA

Page 1: ...ed for upflow applications only 208 230 VAC OPERATION MULTI SPEED DIRECT DRIVE BLOWER CONSTANT TORQUE ECM MOTOR WITH FAN OFF TIME DELAY PROGRAMMING FACTORY INSTALLED R 410A THERMAL EXPANSION VALVE 1 2...

Page 2: ...ause rapid deterioration of the cabinet and internal components CAUTION SAFETY HAZARD Sharp Edge Hazard Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servi...

Page 3: ...bracket on the wall by using 3 wood screws not provided Make sure the bracket is level in order to provided proper drainage from the unit Note Do not attach the wall mounting bracket into unsupported...

Page 4: ...ACCA Manual 0 Design for Residential Winter and Summer Air Conditioning and Equipment Selection Latest editions are available from ACCA Air Conditioning Contractors of America 1513 16th Street N W Wa...

Page 5: ...will energize the fan on a demand for heat or cool Install the thermostat on an inside wall away from drafts lights or other heat sources in a location that has sufficient air circulation from other...

Page 6: ...uspension if used is secure and there are no tools or loose debris in around or on top of the unit 2 Properly insulate suction lines and fittings 3 Properly secure and isolate all refrigerant lines 4...

Page 7: ...onnect R To R G To G Etc See Outdoor Instruction For Details 5 To Change Speed Tap Move Blue Wire Desird Terminal 6 See Airflow Tables For Tap Usage 7 Factory Wires May Be Present DO NOT USE 2 Fig 4 2...

Page 8: ...0 1 02725 3 1 3 725 1 5281 32 5 5 1 1 1 COMPONENT ARRANGEMENT NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE CAUTION ATTENTION 9 9...

Page 9: ...ing and electric heat operation TMM5A0B24M21SAA TMM5A0B30M21SAA TMM5A0B36M31SAA Airflow Performance Standard CFM Shaded boxes represent airflow outside the required 300 450 cfm ton NOTES 9 0 0 1 0 2 0...

Page 10: ...male pipe thread NPT Primary drain conncetion 3 4 female pipe thread NPT Front return shown Units may also be installed as bottom return See the applications section for more detail NOTE Hand tighten...

Page 11: ......

Page 12: ...ighway Tyler TX 75707 www trane com www americanstandardair com The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specificati...

Reviews: