background image

Installer’s Guide

ZZSENSAL0400AA

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

Remote Indoor Temperature Sensor

( Use with *CONT402 Comfort Controls)

18-HD31D1-1

APPLICATION

This Wall Mount Temperature Sensor is used with the
*CONT402 Comfort Control.

SPECIFICATIONS

Operating Ambient Temperature Range:

20° to 120°F (-6.7° to 48.9°C).

Display Range:

20° to 120°F (-6.7° to 48.9°C).

Sensor Accuracy:

+/-.5°F at 75°F

Operating Relative Humidity:

5% to 90% non-condensing.

Finish:

White.

Dimensions in in. (mm):

1.54 (39) wide x 1.93 (49) high x .745 (19) deep.

Storage Temperature:

-40° to 140°F (-40° to 60°C)

INSTALLATION

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.

2.

Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.

ti

on

CAUTION

!

Disconnect power supply before connecting wiring.
Failure to do so may cause equipment damage.

3.

Installer must be a trained, experienced service techni-
cian.

4.

After installation is complete, check out product opera-
tion as provided in these instructions.

3.

Make sure there is good air circulation at average
temperature at the chosen location. Avoid the following
locations because they can introduce errors in sensor
measurements. See Fig. 2.

a. Hot areas caused by:

(i)

Concealed pipes or ducts.

(ii) Drafts from fireplaces or other heat

sources.

(iii) Convection or radiant heat from the sun

or  electrical equipment.

b. Cold areas caused by:

(i)

Concealed pipes or ducts.

(ii) Drafts from windows and doors.
(iii) Unheated areas on the other side of the

wall location.

c.

Dead air areas:

(i)

Behind doors, furniture and curtains.

(ii) In corners and alcoves.

4.  Remove remote indoor sensor cover by grasping the cover at

the top and the bottom and gently pulling it straight off
the subbase.  Position and level the subbase (for appear-
ance only).  Device functions correctly even when not level.

5.  Use a pencil to mark the wiring opening hole.  Remove the

subbase from the wall and drill one hole in the wall for
the wiring opening.

6.  Run wire cable to the wiring opening hole at the selected

wall location.  Pull approximately three inches of wire
through the wiring opening in the wall.  18-gauge thermo-
stat wire is recommended.

7. Position and level the subbase on the wall with the thermo-

stat wire protruding through the wiring opening hole of
the subbase.  Slide the subbase a short distance up the
wall until the thermostat wire rests against the bottom

Location and Mounting (Fig. 2)

CAUTION

!

If the Remote Indoor Temperature Sensor fails, control
reverts to the on-board temperature sensor. Therefore, the
Comfort Control must be installed in the conditioned space.

1.

Choose a location for mounting the Sensor on an inside
wall about 5 ft. (1.5m) above the floor.

2.

Be sure cable distance between the Sensor and
 the Comfort Control is less than 200 feet.

Fig. 1.  ZZSENSAL0400AA Sensor.

Summary of Contents for ZZSENSAL0400AA

Page 1: ...led pipes or ducts ii Drafts from fireplaces or other heat sources iii Convection or radiant heat from the sun or electrical equipment b Cold areas caused by i Concealed pipes or ducts ii Drafts from windows and doors iii Unheated areas on the other side of the wall location c Dead air areas i Behind doors furniture and curtains ii In corners and alcoves 4 Remove remote indoor sensor cover by gras...

Page 2: ... Do not route temperature sensor wiring with building power wiring next to control contactors or near light dimming circuits electric motors or welding equipment Avoid poor wiring connections Avoid intermittent or missing building earth ground CAUTION Disconnect power supply before connecting wiring Failure to do so may cause equipment damage Wiring must comply with applicable codes ordinances and...

Page 3: ...es See Table 1 The Sensor can be used to provide one remote input see Fig 3 or as a temperature averaging network with multiple Sensors connected as shown in Fig 5 CHECKOUT For best results leave the Remote Indoor Temperature Sensor at a stable room ambient for a minimum of twenty minutes before taking a resistance measurement With an accurate thermometer 1 F 0 5 C measure the temperature at the s...

Page 4: ...7 0K 58 14 4 16 1K 60 15 6 15 3K 62 16 7 14 5K 64 17 8 13 8K 66 18 9 13 1K 68 20 0 12 5K 70 21 1 11 9K 72 22 2 11 3K 74 23 3 10 8K 76 24 4 10 2K 78 25 6 9 8K 80 26 7 9 3K 82 27 8 8 9K 84 28 9 8 5K 86 30 0 8 1K 88 31 1 7 7K 90 32 2 7 3K 92 33 3 7 0K 94 34 4 6 7K 96 35 6 6 4K 98 36 7 6 1K 100 37 8 5 8K Table 1 Sensor Resistance at Room Temperature Installer s Guide CALIBRATION The Remote Indoor Temp...

Reviews: