21
TABLE 5
MANIFOLD GAS PRESSURE IN INCHES
OF WATER COLUMN (ALL MODELS*)
TYPE OF GAS
NATURAL
PROPANE
3.5
10.0
Gas pressure specified in Table 5, refer to flow pressure taken at
pressure tap of automatic gas valve while heater is operating.
TABLE 6
APPROXIMATE TIME REQUIRED TO CONSUME
1 CU. FT. OF GAS AT FULL CAPACITY
INPUT RATE
(BTUH)
TYPE OF GAS BTUH PER
CU. FT.
TIME
REQ’D TO
CONSUME
1 CU. FT. OF
GAS
120,000
NATURAL
PROPANE
1050
2500
31.5 SEC.
75.0 SEC.
154,000
NATURAL
PROPANE
1050
2500
24.5 SEC.
58.4 SEC.
180,000
NATURAL
PROPANE
1050
2500
21.1 SEC.
50.3 SEC.
199,000
NATURAL
PROPANE
1050
2500
19.0 SEC.
47.4 SEC.
250,000
NATURAL
PROPANE
1050
2500
15.1 SEC.
35.3 SEC.
251,000
NATURAL
PROPANE
1050
2500
15.06 SEC.
35.1 SEC.
275,000
NATURAL
PROPANE
1050
2500
13.75 SEC.
32.2 SEC.
305,000
NATURAL
PROPANE
1050
2500
12.4 SEC.
29.5 SEC.
365,000
NATURAL
PROPANE
1050
2500
10.4 SEC.
24.7 SEC.
390,000
NATURAL
PROPANE
1050
2500
9.5 SEC.
22.6 SEC.
Figures shown are valid for 0-2000 ft.(0-610m) installations. See
“HIGH ALTITUDE INSTALLATIONS” for deration requirements
over 2000 ft.(610m).
TABLE 7
PILOT BURNER INFORMATION
MODEL
TYPE OF
GAS
PILOT BURNER
PART NUMBER
(WITH ORIFICE)
RATED
ORIFICE
SIZE
ALL
MODELS
NATURAL
193314-004
0.018
PROPANE
193314-003
0.014
Summary of Contents for ABCG3
Page 33: ...33 NOTES ...
Page 34: ...34 NOTES ...
Page 35: ...35 NOTES ...
Page 36: ...36 P O Box 1597 500 Princeton Road Johnson City TN 37605 ...