Security II Rackmount UPM Specifications
North American 700 VA Models - Medical
Front Panel Controls
• Power On/Off
• Test
• Load Level LED Gauge
• Battery Charge LED Gauge
• Voltage Manager Boost LED
• Voltage Output On LED
• Voltage Manager Buck LED
• On Battery LED
• Replace Battery LED
• Overload LED
• Fault Code LED
• System Over Temperature LED
Rear Panel Information and Controls
• 6 Foot Power Cord with NEMA 5-15P Hospital Grade Plug
• Integrated Switched Power Distribution Unit
(Requires SNMP / Web Card)
•
Configuration Manager DIP Switches
• Communications Manager DB9 Port, USB Port
• Circuit Breaker (AC and DC)
• AC Inlet Module
• Communication Option Slot: SNMP / Web Card, Isolated
Relay Contacts Card, or Remote Off Card
• DC External Battery Cabinet Connector
• Fan (Forced Cooling)
Internal Batteries
• User Hot-Swappable (See Instruction Manual)
• Type: 12 Volt, High Rate 23W
• Quantity: 4 Batteries
• Recharge Time: 6 Hours to 80%, 24 Hours to Full Charge
(For Internal Batteries Only)
Environmental
•
Temperature: 0 - +40℃(32 to 104℉) Operating
-20 to 60℃(-40 to 140℉) Shipment/
Storage
• Humidity:
5 to 90% Non-Condensing (Operating,
Shipment/Storage)
• Altitude:
3,000m (10,000 ft) max. Operating;
12,000m (40,000 ft) max. Shipment/Storage
Safety Agency and EMC Compliance:
All Units are Listed by UL and Marked With the UL/cUL Marking
Medical UPM:
• UL60601-1 2nd and 3rd Edition, CE Mark with CB Report
• CSA 22.2 No. 601.1-M89
• CSA 22.2 No. 107-1-M91
• CSA 22.2 Nos. 0-M1982
• CSA 22.2 Nos. 0.4-M1982
Products in Compliance with:
• FFCC-Part 15, Subpart B, Sections 15.107b & 15.109b
Class A Digital Device*
• CISPR11:2009, A1; 2010, Class A*
• EN60601-1-2 : 2007
*Note: Class B is Available as an Option
Please Consult Your Powervar Sales Representative
RoHS Compliance:
All Products (Standard and Medical) are RoHS Compliant
700 VA MODELS TYPICAL RUN-TIMES (MINs)
10% (63W)
20% (126W)
30% (189W) 40% (252W) 50% (315W) 60% (378W) 70% (441W) 80% (504W) 90% (567W) 100% (630W)
Internal Batteries Only
130
90
52
38
23
20
15
12
10
9
In 1) E4804-12
1030
480
292
188
143
110
85
77
66
64
In 2) E4804-12
1930
870
532
338
263
200
155
142
122
119
In 3) E4804-12
2830
1260
772
488
383
290
225
207
178
174
In 4) E4804-12
3730
1650
1012
638
503
380
295
272
234
229
In 5) E4804-12
4630
2040
1252
788
623
470
365
337
290
284
In 6) E4804-12
5530
2430
1492
938
743
560
435
402
346
339
In 7) E4804-12
6430
2820
1732
1088
863
650
505
467
402
394
In 8) E4804-12
7330
3210
1972
1238
983
740
575
532
458
449
NOISE REJECTION-ISOLATION:
With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise
output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY:
Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200 amps, 0.5
usec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 usec risetime, 100 kHZ decay.
Warranty/Support:
Powervar warrants the electronics and transformers used in its uninterruptible power managers to be free from defects in materials and work-
manship for a period of five years from the date of shipment. Batteries are warranted for a period of two years from the date of shipment. For service or support on
any Powervar product, please contact Powervar Technical Support at (800) 369-7179 or visit the Powervar website at
www.powervar.com
.
Battery Life Disclaimer: Powervar’s standard battery warranty applies only to UPS and UPM products which are continuously connected to AC mains power,
except during utility power outages. Products which are regularly and intentionally disconnected from AC mains power will experience battery discharge/charge
cycles potentially far more numerous than those for which the battery was designed. As a result, products used in such applications will experience substantially
reduced battery life. For that reason, Powervar’s standard battery warranty does not apply for applications in which the UPS or UPM product is regularly and
intentionally disconnected from AC mains power. Powervar UPS and UPM products used in such applications shall receive a 90 day warranty on batteries.
Security II Rackmount UPM Specifications
North American 700 VA Models - Medical