User Manual
i Series / iX Series
137
VOLT FREQ MAX
This test will set the voltage and frequency to levels defined by Table 9-2. The test will last for 30
minutes. The test will be repeated for the EURO standard using the Voltage setting from
Table 9-1 and the frequency from Table 9-2. The CLR Key in local operation will terminate the test
at any time. Group execute trigger will terminate the test remotely. The unselected phases will
remain at 115 volts. The
key (backspace) will terminate the test at any time.
VOLT UNBALANCE
Standard/Group
RTCA
Group1
Group2
Group3
Voltage offset
6
6
6
9
Frequency
400
400
360/650
360/800
Table 9-3: Normal Voltage Unbalance
This test will change the output voltage for each phase from 115 volts to 115V + offset. Refer to
Table 9-3 for the offset value and the Frequency. The test will last 30 minutes. The test will be
repeated for a second Frequency if applicable. The test can be terminated at any time.
The
key will terminate the test at any time.
WAVEFORM DISTORTION
This test will generate a 5% THD voltage distortion on the output voltage waveform. The
distortion is generated by using a clipped sinewave. The test will last for 30 minutes. The
key
(backspace) will terminate the test at any time.
VOLTAGE MODULATION
This test requires a numeric value entry equal to the modulation rate in Hz. This entry value
must be between 1 Hz and 200 Hz. The amplitude modulation is calculated based on the
modulation rate as defined in Figure 9-4. This test will last for 2 minutes.
Summary of Contents for 10001i
Page 2: ......
Page 3: ......
Page 6: ...ii This page intentionally left blank...
Page 38: ...User Manual 24 i Series iX Series Figure 3 5 Rear Panel View for the 3001i 3001iX...
Page 39: ...User Manual i Series iX Series 25 Figure 3 6 Rear Panel View for the 5001i 5001iX...
Page 43: ...User Manual i Series iX Series 29 Figure 3 8 Functional Test Setup...
Page 44: ...User Manual 30 i Series iX Series Figure 3 9 Single Phase 10000 VA System 10001iX i...
Page 46: ...User Manual 32 i Series iX Series Figure 3 11 Single Phase 15000 VA System 15001iX i...
Page 48: ...User Manual 34 i Series iX Series Figure 3 13 Connection With MODE Option...
Page 118: ...User Manual 104 i Series iX Series Figure 5 2 Power Source Module Block Diagram...
Page 121: ...User Manual i Series iX Series 107 Figure 5 3 5001i Internal Layout...
Page 122: ...User Manual 108 i Series iX Series Figure 5 4 Logic Board LED s...
Page 124: ...User Manual 110 i Series iX Series Figure 5 5 AC Power Stage Layout...
Page 125: ...User Manual i Series iX Series 111 Figure 5 6 AC Control Logic Block Diagram...
Page 138: ...User Manual 124 i Series iX Series Figure 6 3 Adjustment Location...
Page 152: ...User Manual 138 i Series iX Series Figure 9 4 Voltage Modulation...
Page 219: ...User Manual i Series iX Series 205 Figure 9 36 Example Connection With 5001iX and EOS 1...
Page 221: ...User Manual i Series iX Series 207 Figure 9 38 15003iX CTS EOS3 LR3...
Page 222: ...User Manual 208 i Series iX Series Figure 9 39 15003iX 3 EOS3...
Page 233: ...User Manual i Series iX Series 219 Figure 9 41 Example Connection With MODE iX...
Page 240: ...User Manual 226 i Series iX Series Figure 9 42 Example Connections With OMNI 1 18i...
Page 241: ...User Manual i Series iX Series 227 Figure 9 43 Example Connections With OMNI 3 18i...