27
3.9 Functional Test
CAUTION:
Work carefully when performing these tests, hazardous voltages
are present on the input and output during this test.
Refer to Figure 3-8 for the test set up.
1. Connect an oscilloscope, voltmeter and/or distortion analyzer to the AC source output at the
output terminal block (TB2).
2. With the AC mains verified as being off, apply the correct three phase AC power input
voltage connections to the AC source input terminals barrier (TB1). Apply the AC mains
power and turn on the main circuit breaker on the AC source front panel.
3. Verify the front panel LCD display lights up with the initial start up screen showing the unit ID
and serial number. A self check routine screen with follow and finally the system will display
the main “Menu 1” screen with the cursor highlighting the “Program” selection.
4.
Press “ENTER” and the unit will display the Program selection screen. Set the following
output parameters: output voltage = 150 volts, frequency = 60 Hz, voltage range = 150 volts,
and current limit = 20.0 amps (3001iX) or 33.3 amps (5001iX). Press “ENTER”.
5.
Enable the output by pressing the output “on/off” button below the front panel display screen.
The green LED next to the button will light green when the output is on. The output should
be a clean 150 volt AC sinewave having less than 1% distortion.
6. Apply full load to the output of the source and verify the output remains within 2% of the initial
150 volt value. The output should still be clean and the distortion should still be less than 1%
at 60 Hz.
7. Using the PROGRAM screen set the output current limit value to 17 amps. The system
should go into current limit. Return the current value to 20.0 amps (3001iX) or 33.3 amps
(5001iX) and press the output on/off button to turn the output off. Disconnect the load.
8. Repeat steps 4 through 7 but set the output for the following: output voltage = 300 volts,
output range = 300 volts, current limit = 10.0 amps (3001iX) or 16.7 amps (5001iX). For step
7, the current limit value can be set to 8 amps.
In the unlikely event the power source does not pass the functional test, refer to the
calibration procedure in Section 6 or
call California Instrument‟s customer satisfaction
department for further assistance.
Summary of Contents for 10001i
Page 2: ......
Page 3: ......
Page 6: ...ii This page intentionally left blank...
Page 38: ...User Manual 24 i Series iX Series Figure 3 5 Rear Panel View for the 3001i 3001iX...
Page 39: ...User Manual i Series iX Series 25 Figure 3 6 Rear Panel View for the 5001i 5001iX...
Page 43: ...User Manual i Series iX Series 29 Figure 3 8 Functional Test Setup...
Page 44: ...User Manual 30 i Series iX Series Figure 3 9 Single Phase 10000 VA System 10001iX i...
Page 46: ...User Manual 32 i Series iX Series Figure 3 11 Single Phase 15000 VA System 15001iX i...
Page 48: ...User Manual 34 i Series iX Series Figure 3 13 Connection With MODE Option...
Page 118: ...User Manual 104 i Series iX Series Figure 5 2 Power Source Module Block Diagram...
Page 121: ...User Manual i Series iX Series 107 Figure 5 3 5001i Internal Layout...
Page 122: ...User Manual 108 i Series iX Series Figure 5 4 Logic Board LED s...
Page 124: ...User Manual 110 i Series iX Series Figure 5 5 AC Power Stage Layout...
Page 125: ...User Manual i Series iX Series 111 Figure 5 6 AC Control Logic Block Diagram...
Page 138: ...User Manual 124 i Series iX Series Figure 6 3 Adjustment Location...
Page 152: ...User Manual 138 i Series iX Series Figure 9 4 Voltage Modulation...
Page 219: ...User Manual i Series iX Series 205 Figure 9 36 Example Connection With 5001iX and EOS 1...
Page 221: ...User Manual i Series iX Series 207 Figure 9 38 15003iX CTS EOS3 LR3...
Page 222: ...User Manual 208 i Series iX Series Figure 9 39 15003iX 3 EOS3...
Page 233: ...User Manual i Series iX Series 219 Figure 9 41 Example Connection With MODE iX...
Page 240: ...User Manual 226 i Series iX Series Figure 9 42 Example Connections With OMNI 1 18i...
Page 241: ...User Manual i Series iX Series 227 Figure 9 43 Example Connections With OMNI 3 18i...