DC Power Supplies
ReFlex Power™
6-8
M380056-01 Rev L
V
OLTAGE
T
EMPERATURE
D
RIFT
0.01% of full-scale/°C, maximum
V
OLTAGE
S
TABILITY
0.05% of full-scale after 24 hours at constant line, load, and temperature
1.0% of full-scale after 2000 hours at constant line, load, and temperature
V
OLTAGE
L
OAD
R
EGULATION
RFP-D1016-021-XXXX, RFP-D1065-5A1-XXXX:
less than 0.01% of full-scale plus 10 mV for 100% load change
RFP-D2033-030-XXXX, RFP-D2050-020-XXXX, RFP-D2050-025-XXXX,
RFP-D2120-8A3-XXXX, RFP-D2450-2A3-XXXX:
less than 0.03% of full-scale plus 10 mV for 100% load change
V
OLTAGE
L
INE
R
EGULATION
RFP-D1016-021-XXXX, RFP-D1065-5A1-XXXX:
less than 0.01% of full-scale plus 10 mV for a 10% line change
RFP-D2033-030-XXXX, RFP-D2050-020-XXXX, RFP-D2050-025-XXXX,
RFP-D2120-8A3-XXXX, RFP-D2450-2A3-XXXX:
less than 0.03% of full-scale plus 10 mV for a 10% line change
V
OLTAGE
L
OAD TRANSIENT
Less than 5% of full-scale excursion returning to the steady-state value, within
0.5% of full-scale, in 2 ms maximum, and within DC regulation limits after 10
ms for 10, 50, and 90% load step above and below 50% load.
V
OLTAGE
L
INE TRANSIENT
Less than 1% of full-scale excursion returning to steady-state value, within
0.1% of full-scale, in 0.5ms maximum for 10% line change
R
EMOTE
S
ENSE
C
APABILITY
•
Remote sense compensates for at least 1.5V per load line connection.
•
Maximum output power rating is valid at module output terminals,
since line drop subtracts from maximum load voltage.
•
Neither the module nor the load would be damaged by opening the
sense leads during operation; module will continue to maintain output,
but with reduced programming accuracy to 5%, maximum.
•
Misconnection of the sense leads would not result in an output voltage
in excess of the over-voltage protection limit.
•
Output Shutdown would occur if any of the following happen:
•
Sense leads connected with reversed polarity
•
Sense leads short-circuited
•
Excessive load line voltage drop
Summary of Contents for Elgar ReFlex Power
Page 1: ...M380056 01 Rev L www programmablepower com ReFlex Power Operation Manual...
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank...
Page 8: ...iv This page intentionally left blank...
Page 10: ...vi This page intentionally left blank...
Page 21: ...M380056 01 Rev L xvii This page intentionally left blank...
Page 22: ......
Page 85: ...ReFlex Power Controller ReFlex Power 3 22 M380056 01 Rev L This page intentionally left blank...
Page 89: ...AC Power Supplies ReFlex Power 4 4 M380056 01 Rev L Figure 4 1 ACPS Module Front Panel 875VA...
Page 120: ...ReFlex Power AC Power Supplies M380056 01 Rev L 4 35 Figure 4 11 Parallel Output Configuration...
Page 147: ...AC Power Supplies ReFlex Power 4 62 M380056 01 Rev L RST n...
Page 157: ...AC Power Supplies ReFlex Power 4 72 M380056 01 Rev L 26 Reset the unit RST n...
Page 274: ...ReFlex Power DC Power Supplies M380056 01 Rev L 6 71 18 Turn off the output RST n...
Page 275: ...DC Power Supplies ReFlex Power 6 72 M380056 01 Rev L This page intentionally left blank...
Page 279: ...Active Loads ReFlex Power 7 4 M380056 01 Rev L Figure 7 1 LPAL 375W Front Panel...
Page 280: ...ReFlex Power Active Loads M380056 01 Rev L 7 5 Figure 7 2 HPAL 750W Front Panel...
Page 281: ...Active Loads ReFlex Power 7 6 M380056 01 Rev L Figure 7 3 Typical Active Load Rear Panel...
Page 359: ...Active Loads ReFlex Power 7 84 M380056 01 Rev L This page intentionally left blank...