voltage. When the programmed value of the output voltage is
less than 5% of full-scale, the OVP threshold will be set to a
fixed minimum value of 5.5% of full-scale.
•
In the event of a trip condition, the voltage at the output
terminals is reduced to less than the programmed set-point at
a rate of V
full-scale
/20ms, and to less than 1% of full-scale, plus
1V, within 20ms. An active downprogrammer discharges
output capacitance.
•
Accuracy: 1% of full-scale; Resolution: 0.027% of full-scale
R
EDUNDANT
O
VERVOLTAGE
(ROVP)
Tracking redundant overvoltage protection set at 120% of OVP value, or 3V
above OVP value, whichever is greater, measured at the output terminals.
Shorted or reversed sense leads will result in redundant overvoltage
shutdown.
O
VERCURRENT
(OCP)
The OCP operation is user selectable to be programmable or tracking. The
default mode of operation is programmable OCP.
•
Programmable operation: The OCP threshold is
programmable from 5 to 120% of full-scale output current.
•
Tracking operation: The OCP threshold is automatically
adjusted to 120% above the programmed value of the output
current. When the programmed value of the output current is
less than 5% of full-scale, the OCP threshold will be set to a
fixed minimum value of 6% of full-scale.
•
In the event of a trip condition, the voltage at the output
terminals is reduced to less than the programmed set-point at
a rate of V
full-scale
/20ms, and to less than 1% of full-scale, plus
1V, within 20ms. An active downprogrammer discharges
output capacitance.
•
Accuracy: 2% of full-scale; Resolution: 0.027% of full-scale
O
VERTEMPERATURE
Overtemperature protection is implemented with protection monitors that
sense excessive internal heatsink operating temperature. Excessive
temperature results in shut down of the power converter and output turn-off.
Summary of Contents for Elgar ReFlex Power
Page 1: ...M380056 01 Rev L www programmablepower com ReFlex Power Operation Manual...
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank...
Page 8: ...iv This page intentionally left blank...
Page 10: ...vi This page intentionally left blank...
Page 21: ...M380056 01 Rev L xvii This page intentionally left blank...
Page 22: ......
Page 85: ...ReFlex Power Controller ReFlex Power 3 22 M380056 01 Rev L This page intentionally left blank...
Page 89: ...AC Power Supplies ReFlex Power 4 4 M380056 01 Rev L Figure 4 1 ACPS Module Front Panel 875VA...
Page 120: ...ReFlex Power AC Power Supplies M380056 01 Rev L 4 35 Figure 4 11 Parallel Output Configuration...
Page 147: ...AC Power Supplies ReFlex Power 4 62 M380056 01 Rev L RST n...
Page 157: ...AC Power Supplies ReFlex Power 4 72 M380056 01 Rev L 26 Reset the unit RST n...
Page 274: ...ReFlex Power DC Power Supplies M380056 01 Rev L 6 71 18 Turn off the output RST n...
Page 275: ...DC Power Supplies ReFlex Power 6 72 M380056 01 Rev L This page intentionally left blank...
Page 279: ...Active Loads ReFlex Power 7 4 M380056 01 Rev L Figure 7 1 LPAL 375W Front Panel...
Page 280: ...ReFlex Power Active Loads M380056 01 Rev L 7 5 Figure 7 2 HPAL 750W Front Panel...
Page 281: ...Active Loads ReFlex Power 7 6 M380056 01 Rev L Figure 7 3 Typical Active Load Rear Panel...
Page 359: ...Active Loads ReFlex Power 7 84 M380056 01 Rev L This page intentionally left blank...