DC Power Supplies
ReFlex Power™
6-56
M380056-01 Rev L
S
ERIES
/P
ARALLEL
C
ONFIGURATION
The series output configuration could be combined with the parallel
configuration to produce a composite series/parallel configuration. Only
modules of the same model could be interconnected in series/parallel. The
restrictions listed in the sections on the series and parallel configurations
must be followed: the parallel modules must be physically contiguous, while
the series grouping is not location dependent. The outputs must be hardwired
as parallel groups connected in series. The remote sense leads are
connected only to the paralleling-master modules; ensure that single point
connections are maintained for the series connected sense leads. Figure
6-22 shows the series/parallel connection of six units with remote sensing.
The series/paralleled modules are programmed as a single, virtual channel
with a current rating equal to the sum of the number of modules connected in
parallel, and a voltage rating equal to the sum of the number of modules
connected in series. The master and slave supplies of a parallel group will
share the output current equally, while the series connected parallel groups of
modules will equally share the output voltage. Fault shutdown is coordinated
across all modules: a fault within any module of the group will result in
shutdown of all modules.
C
AUTION
To prevent damage to a supply, do not exceed the float voltage
specification limit for either of the output terminals to chassis.
Summary of Contents for Elgar ReFlex Power
Page 1: ...M380056 01 Rev L www programmablepower com ReFlex Power Operation Manual...
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank...
Page 8: ...iv This page intentionally left blank...
Page 10: ...vi This page intentionally left blank...
Page 21: ...M380056 01 Rev L xvii This page intentionally left blank...
Page 22: ......
Page 85: ...ReFlex Power Controller ReFlex Power 3 22 M380056 01 Rev L This page intentionally left blank...
Page 89: ...AC Power Supplies ReFlex Power 4 4 M380056 01 Rev L Figure 4 1 ACPS Module Front Panel 875VA...
Page 120: ...ReFlex Power AC Power Supplies M380056 01 Rev L 4 35 Figure 4 11 Parallel Output Configuration...
Page 147: ...AC Power Supplies ReFlex Power 4 62 M380056 01 Rev L RST n...
Page 157: ...AC Power Supplies ReFlex Power 4 72 M380056 01 Rev L 26 Reset the unit RST n...
Page 274: ...ReFlex Power DC Power Supplies M380056 01 Rev L 6 71 18 Turn off the output RST n...
Page 275: ...DC Power Supplies ReFlex Power 6 72 M380056 01 Rev L This page intentionally left blank...
Page 279: ...Active Loads ReFlex Power 7 4 M380056 01 Rev L Figure 7 1 LPAL 375W Front Panel...
Page 280: ...ReFlex Power Active Loads M380056 01 Rev L 7 5 Figure 7 2 HPAL 750W Front Panel...
Page 281: ...Active Loads ReFlex Power 7 6 M380056 01 Rev L Figure 7 3 Typical Active Load Rear Panel...
Page 359: ...Active Loads ReFlex Power 7 84 M380056 01 Rev L This page intentionally left blank...